FLUE
Essential requirements for correct appliance operation:
the internal section must preferably be circular;
the appliance must be thermally insulated and impermeable and built with suitable materials which are resistant to heat,
combustion products and any condensation;
there must be no narrowing and vertical passages with deviations must not be greater than 45°;
if already used, it must be clean;
all the sections of the ue gas duct must be accessible to inspection;
inspection openings must be provided for cleaning.
the technical data from the instruction manual must be respected;
If the ues are of a square or rectangular section, the internal edges must be rounded with a radius of not less than 20 mm.
For the rectangular section, the maximum ratio between the sides must be ≤ 1.5.
A section which is too small causes a reduction in draught. A minimum height of 4 m is advisable.
The following materials are FORBIDDEN and compromise the good operation of the appliance: asbestos cement, galvanised steel, rough and
porous internal surfaces. Picture 1 shows some example solutions.
For a correct installation please respect the sections/lengths of the ue shown in the technical data table. By installations
with dierent dimensions the ue must be suitably sized in accordance with EN13384-1.
The draught created by your ue must be sucient but not excessive.
A section of the ue which is too large can present a volume which is too large to heat and therefore cause operating diculties for the
appliance; to avoid this, it is necessary to intubate the appliance for its entire height. A section which is too small causes a reduction in draught.
ATTENTION: as far as concern the realisation of the ue connection and ammable materials please follow the requirements
provided by UNI 10683 standard. The ue must be at a suitably distance from ammable or combustible material using
suitable insulation or an air space.
It is FORBIDDEN to pass system piping or air ducts inside the ue. It is also forbidden to create moveable or xed openings on
the ue itself, for the connection of further dierent appliances (See chapter CONNECTING A FIREPLACE OR OPEN HEARTH TO THE
FLUE).
CHIMNEY POT
The ue draught depends on the suitability of the chimney pot.
It is therefore essential that, if built in a handcrafted way, the exit section is more than twice the internal section of the flue (Picture 2) .
As it must always go past the ridge of the roof, the chimney pot must ensure exhaust even in the presence of wind (Picture 3).
The chimney pot must meet the following requirements:
Have an internal section equivalent to that of the chimney.
Have a useful exit section of double the internal section of the ue.
Be built so as to prevent rain, snow or any foreign body entering the ue.
Be easy to inspect, for any maintenance and cleaning operations.
CONNECTION TO THE CHIMNEY
Products with automatic door closing (type 1) must operate, for safety reasons, with the furnace door closed (except during the fuel loading
or ash removal phases).
Products with non-automatic door closing (type 2) must be connected to their own ue.
Operation with doors open is only allowed when supervised.
The connection pipe to the ue must be as short as possible, straight horizontal and positioned slightly in ascent, and watertight.
Connection must be carried out with stable and robust pipes,comply with all current Standards and Regulations and to those envisioned by
the law, and be hermetically secured to the ue. The internal diameter of the connection pipe must correspond to the external diameter of the
appliance ue gas exhaust stub pipe (DIN 1298).
ATTENTION: as far as concern the realisation of the ue connection and ammable materials please follow the requirements
provided by UNI 10683 standard. The ue must be properly spaced from any ammable materials or fuels through a proper
insulation or an air cavity. Minimum distance safety 25 cm.
The chimney pressure (DRAUGHT) must be at least (see chap. TECHNICAL DATA SHEET) Pascal. The measurement has always to be carried
out with hot device (rated thermal performance).
When the depression exceeds 17 20 Pa (=1.7 =2 mm of column of water), it is necessary to reduce the same by installing an additional draught
regulator (buttery valve) on the exhaust pipe or in the chimney, according to the regulations in force.
For correct appliance operation, it is essential that sucient air for combustion is introduced into the place of installation (see
paragraph VENTILATION AND AERATION OF THE INSTALLATION PREMISES).
CONNECTING A FIREPLACE OR OPEN HEARTH TO THE FLUE
The ue gas channel is the stretch of piping which connects the product to the ue. In the connection, these simple but extremely important
principles must be respected:
under no circumstances use a ue gas channel with a diameter less than that of the exhaust clamp with which the product is equipped;
each metre of the horizontal stretch of the ue gas channel causes a slight loss of head which must be compensated if necessary by
elevating the ue;
25
25

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw La Nordica Wanda Evo bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van La Nordica Wanda Evo in de taal/talen: Duits, Engels, Frans, Italiaans, Spaans als bijlage per email.

De handleiding is 9,82 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

loading

Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info