Warnings (for using R-290 refrigerant only)
1. Transport of equipment containing flammable refrige-
rants.
See transport regulations
2. Marking of equipment using signs
See local regulations
3. Disposal of equipment using flammable refrigerant
See national regulations.
4. Storage of equipment/appliances
The storage of equipment should be in accordance with
the manufacturer’s instructions.
5. Storage of packed (unsold) equipment
Storage package protection should be constructed
such thay mechanical damage to the equipment insi-
de the package will not cause a leak of the refrigerant
charge.
The maximum number of pieces of equipment permi-
tted to be stored together will be determined by local
regulations.
6. Information on servicing
1) Check to the area
Prior the beginning work on systems containing flam-
mable refrigerants, safety checks are necessary to en-
sure that the risk of ignition is minimised. For repair
to the refrigerating system, the following precautions
shall be complied with the prior to conducting work on
the system.
2) Work procedure
Work shall be undertaken under a controlled procedu-
re so as to minimise the risk of a flammable gas or va-
pour being present while the work is being performed.
3) General work area
All maintenance staff and others working in the local
area shall be instructed on the nature of work being
carried out. Work in confined spaces shall be avoided.
The area around the workspace shall be sectioned off.
Ensure that the conditions within the area have been
made safe by control of flammable refrigerants.
4) Checking for presence of refrigerant
The are shall be checked with an appropiate refrige-
rant detector prior to and during work, to ensure the te-
chnician is aware of potentially flammable atmosphe-
res. Ensure that the leak detection equipment being
used is suitable for use with flammable refrigerants,
i.e. non-sparking, adequately sealed or instrinsically
safe.
5) Presence of fire extinguisher
If any hot work is to be conducted on the refrigeration
equipment or any associated parts, appropiate fire ex-
tinguishing equipment shall be available to hand. Have
a dry powder or CO2 fire extinguisher adjacent to the
charging area.
6) No ignition sources
No person carrying out work in relation to a refrige-
rantion system which involves exposing any pipe work
that contains or has contained flammable refrigerant
shall use any sources of ignition in such a manner that
it may lead to the risk of fire or explosion. All possible
ignition sources, incluiding cigarrette smoking, should
be kept sufficiently far away from the site of installa-
tion, repairing, removing and disposal, during which
flammable refrigerant can possibly be released to the
surrounding space. Prior to work takking place, the
area around the equipment is to be surveyed to make
sure that there are no flammable hazards or ignition
risks. No Smoking signs shall be displayed.
7) Ventilated area
Ensure that the area is in the open or that it is ade-
quately ventilated before breaking into the system or
conducting any hot work. A degree of ventilation shall
continue during the period that the work is carried out.
The ventilation should safely disperse any released
refrigerant and preferably expel it externally into the
atmosphere.
8) Checks to the refrigeration equipment
Where electrical components are being changed, they
shall be fit for the purpose and to the correct specifica-
tion. At all times the manufacturer’s maintenance and
service guidelines shall be followed. If in doubt consult
the manufacturer’s technical department for assistan-
ce. The following checks shall be applied to installa-
tions using flammable refrigerants:
The charge size is in accordance with the room size
within which the refrigerant containing parts are ins-
talled;
The ventilation machinery and outlet are operating
adequately and are not obstructed;
If an indirect refrigerating circuit is being used, the se-
condary circuit shall be checked for the presence of
refrigerant;
Marking to the equipment continues to be visible and
legible. Markings and signs that are illegible shall be
corrected;
Refrigeration pipe or components are installed in a po-
sition where they are unlikely to be exposed to any
substance which may corrode refrigerant containing
components, unless the components are constructed
of materials which are inherently resistant to being co-
rroded or are suitably protectec against being so co-
rroded.
9) Checks to electrical devices
Repair and maintenance to electrical components sha-
ll include intitial safety checks and component inspec-
tion procedures. If a fault exists that could comprise
safety, then no electrical supply shall be connected to
the circuit until it is satisfactorily dealt with. If the fault
cannot be corrected immediately but it is necessary
to continue operation, an adequate temporary solution
shall be used. This shall be reported to the owner of
the equipment so all parties are advised.
Intitial safety checks shall include:
That capacitors are discharged: this shall be done in a
safe manner to avoid possibility of sparking;
6

Hulp nodig? Stel uw vraag in het forum

Spelregels
1

Forum

Kaysun-KP-35-HP10

Zoeken resetten

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Kaysun KP-35 HP10 bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Kaysun KP-35 HP10 in de taal/talen: Engels als bijlage per email.

De handleiding is 2,6 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

loading

Andere handleiding(en) van Kaysun KP-35 HP10

Kaysun KP-35 HP10 Gebruiksaanwijzing - Nederlands - 20 pagina's

Kaysun KP-35 HP10 Gebruiksaanwijzing - Deutsch - 20 pagina's


Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info