771475
33
Verklein
Vergroot
Pagina terug
1/48
Pagina verder
32
NOTE
off
-4
on
7.3 Operating characteristics
1. Set temperature in cooling
Range:10~20℃ (default12℃)
If the set temperature is between 10~13, the compressor start and
shut down according to the difference between the inlet temperature
and the set temperature as follows:
Tin-Ts
2
If the set temperature is between 14~20℃,the compressor start and
shut down according to the difference between the inlet temperature
and the set temperature as follows:
Tin-Ts
2
2. Set temperature in heating
Range:35~50℃ (default40℃)
If the set temperature is between 35~44℃,the compressor start and
shut down according to the difference between the inlet temperature
and the set temperature as follows:
Tin-Ts
2
If the set temperature is between 45~50℃,the compressor start and
shut down according to the difference between the inlet temperature
and the set temperature as follows:
Tin-Ts
0
5. Fan speed control
For correct operation of the unit with different ambient
temperatures, the microprocessor controls the fan speed based
on the ambient temperature and the condensing or evaporation
temperature as well as compressor frequency, thus enabling heat
exchange to be increased and/or decreased, maintaining the
condensing or evaporation temperature practically constant.
6. Frost prevention protection
To prevent the water freezing and damaging the plate heat
exchanger, the microprocessor will perform antifreeze protection
program if the heat exchanger temperature or the water
temperature below a certain temperature.
a. In the cooling mode or water pump mode: if the heat exchanger
temperature or the outlet temperature sensor is less than 3, the
compressor will shut down and the controller display Pb code, the
water pump will continue to run until the heat exchanger
temperature or the outlet temperature sensor is above 8and the
unit will resume normal operation.
b. In the heating mode or standby mode: if the heat exchanger
temperature or the inlet temperature sensor is less than 8, the
controller display Pb code, the water pump will continue to run until
the heat exchanger temperature or the inlet temperature sensor is
above 15. If the heat exchanger temperature or the inlet
temperature sensor continues to fall below 5, the unit will be
forced heating operation, the compressor and the water pump will
be running until the heat exchanger temperature or the inlet
temperature sensor is above 15.
c. If the ambient temperature is less than 8and the heat
exchanger temperature or the inlet temperature sensor is less
than 2, the electric exchanger temperature heating will turn on
until the heat exchanger temperature or the inlet temperature
sensor is above 7℃.
If the unit is likely to operate below 0, it is advisable to add
antifreeze to the water system to prevent the unit from freezing the
system in the event of a power cut off or failure.
7. Fin heat exchanger high temperature protection
When the fin heat exchanger temperature over than 62°C, system
will shut down, but not returns to normal operation until the
temperature decreased less than 52°C.
8. Comp. discharge temperature protection
If the compressor discharge temperature is more than 115℃,the
compressor will be stop running until the temperature is lower than
83. The compressor starts with a 5-minute delay protection.
The set temperature refers to the set return water temperature or
inlet temperature;
In the event of a temporary power failure, when power returns, the
mode set previously will be retained in the memory.
3. Compressor start up delay
To prevent the compressor frequent start and stop, the compressor
must ensure that each start since the last stop since the minimum
time of 300 seconds.
4. The pump control and the flow switch control
The electronic board includes two pumps control output. The pump 1
running 3 seconds, the pump 2 starts running. The pump 1 starts
when the assembly is powered up and at least 285 seconds before
the compressor starts up and stops 120 seconds after the assembly
shuts down.
After the first 120 seconds of pump1 operation when the water flow
meets the operating requirements, the water flow alarm functions are
activated (differential pressure switch or flow switch). If the differential
pressure switch (or flow switch) detects a continuous closure for 15
seconds, the unit can run normally, otherwise, it will shut down and
display C8 fault.
In the unit operation process, if the continuous 10 seconds to detect
the differential pressure switch (or flow switch) is opened, the unit will
stop running and display C8 fault.
If there is a possibility that the outside temperature may drop
below zero, there is the risk of freezing.
The water circuit MUST BE EMPTIED AND SHUT OFF
POWER (when draining after heat pump operation take care
as the water may be hot) or antifreeze must be added in the
proportion recommended by the manufacturer.
8.
TROUBLE SHOOTING
This section provides useful information for diagnosing and
correcting certain troubles which may occur in the unit.
This troubleshooting and related corrective actions may only be
carried out by your local technician.
CAUTION
on
off
-1
on
off
-2
off
-2
on
33

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Kaysun KEM-14 DTN bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Kaysun KEM-14 DTN in de taal/talen: Engels als bijlage per email.

De handleiding is 7.07 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

loading

Andere handleiding(en) van Kaysun KEM-14 DTN

Kaysun KEM-14 DTN Gebruiksaanwijzing - Nederlands - 48 pagina's


Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info