554807
1
Verklein
Vergroot
Pagina terug
1/2
Pagina verder
The JA-82ST wireless combined smoke and heat detector MZZ57300
The JA-82ST wireless combined smoke and heat detector
The JA-82ST is a wireless component of the JABLOTRON ALARMS
OASIS security system. It is used to detect fire hazards in the interior of
residential or commercial buildings. It is not designed to be installed in
industrial premises. The JA-82ST detector uses wireless communication
and it is powered with three AA 1.5V alkaline batteries.
The JA-82ST consists of two independent detectors – an optical
smoke detector and a heat detector. The optical smoke detector works on
the principle of scattered light and is very sensitive to large dust particles
which are present in dense smoke. It is less sensitive to smaller particles
generated by the combustion of liquids such as alcohol. That is why there
is also a built-in heat detector which has a slower reaction but is much
better at detecting fire which generates heat quickly with a small amount
of smoke. The microprocessor performs digital analysis of these values
which markedly increases false alarm immunity.
Detector range
The smoke detector must be installed so that any smoke easily drifts
into the detector, e.g. on the ceiling. It is suitable for residential buildings
but not suitable for free spaces, outdoor environments or interiors with
extremely high ceilings (above 5 m) where fire by-products can disperse
over a large area – the smoke would not reach the detector position.
The detector must always be placed in the section leading to the exit
of the building (escape route), see Figure 1. If the building has a floor
area greater than 150 m2, installation of an additional detector in some
other suitable place is required, see Fig.2.
1
2
33
4
Fig 1
2
1
3
3
4
3
Fig 2
1-kitchen
2-living room
3-bedroom
4-children’s bedroom
- Basic security
- For more security
1
3
3
3
Fig 3
For large buildings it is recommended to place additional detectors in
rooms where people sleep and in rooms with an increased risk of fire -
see Fig.3.
Installation on level ceilings
Place the detector in the centre of the room if possible. The detector
must not be recessed into the ceiling due to the possible existence of a
cool air layer on the ceiling. Never place the detector in the corner of
the room though (always keep at least a 0.5 m distance from the corner)
see Fig 4.
Installation on sloping ceilings
If the ceiling is not suitable for mounting on a level surface (e.g. a
room under a roof ridge), the detector can be installed as in Fig. 5
0.5m
TOP
Fig 4
0,9 m
Fig 5
centre of the room, best location acceptable location
Walls, partitions, barriers and lattice ceilings
The JA-82ST detector must not be installed closer than 0.5 m
from any wall or partition. A narrow room with a width of less than 1.2m
requires the detector(s) to be placed at a distance of at least one third of
the room’s width away. In the case of separating walls (partitions,
warehouse objects) which do not reach the ceiling, the space is
considered to be fully separated if the gap between the top of the
separating wall and the ceiling does not exceed 0.3 m. A free space
of at least 0.5m is required under the detector. Any irregularities of the
ceiling (e.g. girders) exceeding 5 % of the ceiling height shall be
considered a wall and the above mentioned limitations shall apply.
Ventilation and air circulation
The detectors must not be installed directly by a fresh air inlet
(e.g. air conditioning vents). In the case of air being supplied through a
perforated ceiling, each detector must be placed so that no perforation
hole occurs within 0.6m of the detector.
Avoid installing the detector in the following locations:
places with poor air circulation (niches, corners, apexes of A-
shaped roofs, etc.)
places exposed to dust, cigarette smoke or steam
places with over-intense air circulation (close to ventilators, heat
sources, air conditioning outlets, etc.)
in kitchens and other cooking places (because steam, smoke or oily
fumes can reduce detector sensitivity).
beside fluorescent lights (electrical interference can cause a false
alarm)
in areas with lots of small insects
Please note: Most false alarms are caused by improper
detector location.
See CEN/TS 54-14 standards for detailed installation guidelines.
Installation
The detector should be installed by a trained technician with a valid
certificate issued by an authorized distributor. Abide by the procedures
recommended in the previous paragraphs.
1 2
3
1400- 00- 0000- 00 01
5
4
6
INS
MEM
SMOKE
TEMP
+ -
7
Fig 6: 1– detector cover opening; 2 – detector cover closing; 3 – optical status
signalling; 4 – arrow showing where to insert the detector; 5 – enrollment code; 6 –
configuration terminals; 7 – battery holders
1. open the detector cover, by turning it anti-clockwise (1)
2. attach the removed plastic base to the desired place with screws (not
shown above).
3. set the configuration terminals (6) according to the table below.
4. Proceed according to the control panel installation manual. Basic
procedure:
a. Switch on the enrollment mode in the control panel.
b. When you insert all batteries into the detector, the enrollment code
is sent to the system – its sending is confirmed with a short flash of
the LED indicator (3).
c. The control panel confirms the enrollment with a flashing of the “A“
LED on the system keypad at the corresponding position.
5. Insert the detector into the plastic base. The detector can be inserted in
the plastic base in one position only. It is marked with arrows (4) on both
plastic parts. Close the detector cover by turning it clockwise (2).
Note: The detector can also be enrolled into the system by entering its
enrollment code (5) in the O-Link program. (Enter the last 8 digits under
the bar code).
Detector setting
The detector properties can be set in the Detectors window in the
O-Link program and with the configuration terminals.
ON
Instant alarm
3 OFF
1
OFF
Fire alarm
4 OFF
smoke (EN 54-7) or
heat (EN 54-5)
ON
memory enabled
3 ON
2
OFF
memory disabled
4 OFF
smoke only (EN 54-7)
(not heat)
3 OFF
4 ON
heat only (EN 54-5) (not
smoke)
3 ON
1
2
3
4
INS
MEM
SMOKE
TEMP
ON
OF
F
4 ON
Both smoke and heat
(both conditions at the
same time)
1

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Jablotron JA-82ST bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Jablotron JA-82ST in de taal/talen: Engels als bijlage per email.

De handleiding is 0,08 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

loading

Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info