6.33 Only single alarm indication
If this function is enabled, then only one intruder alarm may be indicated
at a time. Once an intruder alarm has been triggered and has not ended yet,
then no more alarms can be indicated no matter how many more times
triggering occurs. When the alarm ends, the system is then ready to indicate
the next single intruder alarm.
This is to limit the number of SMS reports sent if hard-wired PIR
detectors capable of being frequently triggered are installed in the system
and the system is not unset (disarmed) properly when someone enters the
building.
6 9 1 0 multiple simultaneous intruder alarms allowed
6 9 1 1 single intruder alarm allowed only
JA-82K control panel installation manual - 11 - MKH51103
Note:
A panic alarm can always be triggered with no limits (except when in
service and maintenance modes),
Apart from this limitation the system also checks if any detector is
triggering multiple alarms during one arm period. If any detector has
caused at least three alarms in a row it is then automatically
bypassed. This bypass lasts until another detector triggers an alarm or
until the next arming of the system.
6.34 Setting (arming) by service code
Normally, it is not allowed to control the system via the service code.
Using this sequence, the installer can be authorized to set and unset the
system by means of a valid service code. This feature should only be enabled
with the explicit approval of the master code holder (system
administrator):
6 9 2 0 disabled
6 9 2 1 enabled
Factory default setting: disabled
6.35 Audible panic alarm
If enabled, panic alarms can be indicated by internal and external
warning devices (sirens on IW and EW):
6 9 3 0 silent panic alarm
6 9 3 1 audible panic alarm
Note: If the sequence 370 is used, panic alarms are silent if any section of
the system is unset.
Factory default setting: silent panic alarm
6.36 Higher control-panel receiver-sensitivity
If enabled, this feature can extend the communication range between the
control panel and its wireless devices if there is no radio frequency
interference in the premises.
6 9 4 0 standard control panel sensitivity
6 9 4 1 higher control panel sensitivity
Note: The sensitivity of the control panel receiver should only be increased if
there is no RF interference as the radio range would only be reduced if
interference was present.
Factory default setting: standard control panel sensitivity
6.37 Access by code plus card
This feature increases security against unauthorised setting/unsetting
(arming/disarming):
6 9 5 0 system access by code or card
6 9 5 1 system only accessed by code and card if both are
assigned to the same user position
Notes:
The system has up to 50 user positions (01 to 50) each capable of
having an access code and an access card assigned to it. If both a
code and a card are assigned to a user then the above sequences
(6950 and 6951) determine whether the user can use a code or a card
or whether he must present both a card and a code to gain control over
the system. If both, a card and a code have to be presented, the order
in which they are done is unimportant.
If only a card or only a code is assigned to a user, then the above
settings have no effect on users like this.
Factory default setting: system operated by code or card
6.38 Audible 24 hour intruder alarm
The 24-hour intruder alarm which can be triggered whether the system is
set or not, and can also be silent or audible (IW and EW) according to the
following sequences:
6 9 6 0 silent 24-hour intruder alarm
6 9 6 1 audible 24-hour intruder alarm
Note: If sequence 370 is programmed, the intruder alarm will be silent if any
section in the system is unset.
Factory default setting: audible 24 hour intruder alarm
6.39 Service mode only with service and user code
To prevent the installer from accessing Service Mode without a user’s
permission, this feature (if enabled) makes it compulsory for the any user
code (or master code) to be entered directly after entering the service code to
access Service mode. Service Mode can then be entered by keying in 0
service-code user-code (or master-code).
6 9 7 0 Only service code needed.
6 9 7 1 Service code and user-code (or master-code) needed.
Factory default setting: Only service code needed.
6.40 Device reactions and section assignment
The following sequence programs the characteristics of system devices:
6 1 nn r s
where nn is the device address from 01 to 50 (01 to 04 … 14
can either be the hard-wired input terminals in the control
panel or enrolled wireless devices)
r is the reaction index from 0 to 9 – see table
s is the section 1 = A, 2 = B, 3 = C (only has an effect if
partial setting or system splitting is used – except for PG
output control – See 6.23)
R Reaction Notes
0 Disabled
(none)
For temporarily disabling codes or devices
including tamper sensors
1 Natural For detectors = instant, delayed or fire (selectable
in detectors by DIP switch)
For hard-wired inputs of the control panel or
keypad = delayed
Keyfobs (or ) =set, (or ) =unset, both
buttons = panic
Code = set/unset (see reaction r=9)
2 Panic
Triggers a panic alarm (audible or silent, see 6.35)
3 Fire
Triggers a fire alarm
4 24 hours
Triggers an intruder alarm even if the system is
unset (audible or silent – see 6.38)
5 Next delay
Always provides an exit delay. An entrance delay
is only provided if it is triggered shortly after a
delayed detector.
6 Instant
If activated in a set (armed) section, it triggers an
intruder alarm instantly
7 Set
Sets its own section of the system
8 PG
output control
The value of the s parameter determines which
PG output is controlled: s= 1= PGX, s=2=PGY or
s=3=PGX & PGY. To use this function the PG
output involved has to be programmed to the
ON/OFF or pulse functions.
If the reaction is triggered by:
a code (card) – the PG output changes its state
(ON,OFF,ON,OFF……) or a pulsed switching
event is generated after a valid code or card is
used. If a code or card is programmed this way, it
cannot be used for setting (arming) control. One or
more (up to 50) different codes can be
programmed to operate PG outputs, if desired.
a keyfob – one button in a pair is used to switch a
PG output ON, the second one to switch it off or
each of them generates a pulsed switching event.
If a keyfob is programmed this way, it cannot be
used for setting (arming) control. Each PG output
can have as many associated keyfobs as desired.
a detector the PG output copies the status of
the detector or it generates a pulsed switching
event when the detector is triggered. Only one
detector should be programmed to a PG output
ON/OFF reaction and should not be combined with
keyfob or keypad control as the detector repeats
its status every 9 minutes and it would override the
signal from the keypad or keyfob.
9 Set/unset
Toggles the system status
SET,UNSET,SET,UNSET etc
fig. 11 Device reactions
11

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Jablotron JA-82K OASIS bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Jablotron JA-82K OASIS in de taal/talen: Engels als bijlage per email.

De handleiding is 0,66 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

loading

Andere handleiding(en) van Jablotron JA-82K OASIS

Jablotron JA-82K OASIS Installatiehandleiding - Deutsch - 23 pagina's

Jablotron JA-82K OASIS Gebruiksaanwijzing - English - 23 pagina's

Jablotron JA-82K OASIS Aanvulling / aanpassing - English - 1 pagina's


Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info