554808
1
Verklein
Vergroot
Pagina terug
1/1
Pagina verder
The JA-63S-80 wireless optical smoke and heat detector for Oasis system
This device is designed to detect the presence of fire inside residential or commercial
buildings. It should not be installed in industrial premises. The battery-powered detector
has a built-in local warning siren combined with a transparent LED indicator. The alarm
information can also be transferred via a wireless connection to the JA-80 OASIS
system.
The JA-63S80 detector combines an optical smoke sensor with a heat sensor. Both
sensors have their outgoing signals processed digitally, resulting in higher false alarm
immunity. The optical sensor works using a light diffusion principle and is very sensitive to
the presence of large-sized particles which are characteristic of dense smokes. By
contrast, the sensor is less sensitive to small-sized particles which are typical of cleanly
burning fires. In particular, the smoke sensor is not capable of detecting the by-products of
cleanly-burning fluids such as alcohols, for instance. This deficiency is compensated for
by the built-in heat sensor. This sensor provides a slower reaction when compared to the
smoke sensor, but is much better at reacting to fires with rapidly rising heat producing only
a little smoke.
Smoke/heat sensor participation is configurable by DIP switches.
Detection range, detector positioning
Exposing fire conditions to the smoke and heat sensors requires some level of air
circulation. It is therefore necessary to install the JA-63S80 detectors in such a place on
the ceiling that (in the case of fire) smoke masses are forced to go in the direction of the
detector’s position. This can usually be achieved in most buildings. However, the
JA-63S80 is not suitable for installation in outdoor spaces or interiors with an extremely
high ceiling where fire by-products would not reach the detector position.
The following table shows the detector’s working range in relation to the height of the
ceiling on which the detector is installed. The range is expressed as the radius of the
circular fire detection area for a detector installed on a ceiling directly above:
Ceiling height (m)
< 4,5
4,5÷6
6÷8
8÷11
11÷25
> 25
Smoke
detection
7,5* m 7,5* m 7,5* m 7,5* m
Not
suitable
Not applicable
Heat
detection
5* m 5* m 5* m Not suitable
Not
applicable
Not applicable
Not suitable –not usually used in such cases
Installation on a horizontal level ceiling
Due to the possible occurrence of a cold air layer right under the ceiling, the detectors
must not be imbedded into the ceiling. The distance between any point to be
protected and an imaginary vertical line from the nearest JA-63S80 detector down to the
floor must not exceed the radius indicated in the table.
Installation on a sloping ceiling
If the JA-63S80 is installed just under an apex formed by the joining of two sloping
ceilings the values indicated in the table can be increased by 1% for every degree of
slope up to a maximum of 25%. If the space to be protected is under a saw-tooth type
of roof, JA-63S80 detectors should be installed under each apex. However, a roof with
a shallow saw-tooth form can be acceptable if the height difference between the highest
and lowest parts of the ceiling does not exceed 5% of the total ceiling height.
Walls, partitions, obstacles, and trussed ceilings
The JA-63S-80 must not be installed closer than 0.5 m from any wall or partition.
A narrow room with a width of less than 1.2m requires the detector(s) to be placed at a
distance of at least one third of the room’s width away. In the case of separating walls
(partitions, warehouse objects) which do not reach the ceiling, the space is considered to
be fully separated if the gap between the top of the separating wall and the ceiling
does not exceed 0.3 m A free space of at least 0.5m is required under the detector.
Irregularities in ceiling shape which do not exceed 5% of ceiling height are considered
insignificant the ceiling can be regarded as being even and limits from the table are
applicable. However, any irregularity (including beams) exceeding 5% of the ceiling
height is considered to be a wall with the consequences stated above.
Ventilation and air circulation
The detectors must not be installed directly by a fresh air inlet, e.g. air conditioning
vents. In the case of air being supplied through a perforated ceiling, each detector must
be placed so that no perforation hole occurs within 0.6m of the detector.
Avoid installing the detector in the following locations:
Places with poor air circulation (niches, corners, apexes of A-shaped roofs).
Places exposed to dust, cigarette smoke or steam.
Places with over-intense air circulation (close to ventilators, heat sources or air
conditioning outlets).
Kitchens and other cooking places (because steam, smoke or oily fumes can reduce
detector sensitivity).
Caution: The most common reason for the detector to be accidentally
triggered is improper detector location.
See CEN/TS 54-14 standards for detailed installation guidelines
.
Installation
1. Open the detector by turning the rear cover to the left and remove the battery
2. Screw the rear cover onto the desired location
3. Set the required function via the jumpers see the table below
4. Please read the receiving device (control panel) installation manual before you
connect the battery (remove the insulation tape) and set the control panel in learning
mode
5. When the battery is connected, the detector sends a signal to connect into the
system
6. After installing the detector, allow approx. 20 seconds for stabilisation. This period is
indicated by the LED being continuously lit and is followed by an auto-test.
Successful performance of the auto-test is confirmed acoustically.
O
p
e
n
C
l
o
s
e
TEST
+
1.
5 V
A
A
1
1
ON INSTANT alarm mode 3 OFF
Smoke (EN 14064) or heat (EN
54-5)
OFF
FIRE alarm mode
4 OFF
2
ON
Memory ON
3
ON
Only smoke (EN 14604) (heat
indifferent)
OFF
Memory OFF
4
OFF
1
1 2 3 4
ON
OFF
3
OFF
Only heat (EN 54-5) (smoke
indifferent)
4
ON
3
ON
Smoke and heat (both
simultaneously)
4 ON
Closing the detector is disabled if no battery has been installed!
Testing the detector is automatically performed up to 10 secs after
battery insertion. New settings are saved directly afterwards.
Fire alarm
Optical smoke sensor: Smoke entry into the detector is indicated as a pre-alarm state
by the LED flashing. If the smoke threshold density is exceeded, a siren sound is
generated, gradually increasing in volume.
Heat sensor: indication logic is equal to that of the smoke sensor.
Alarm memory: It is switched ON/OFF via DIP 2 as shown in the table. If the event
memory is armed at the time of alarm, alarm LED indication continues even if normal
conditions are restored. The indication can be stopped by pressing the button.
Silencing the siren during an alarm: During a fire alarm, the detector LED flashes 2
times briefly and the built-in siren sounds (at a higher intensity than during a test). Under
these conditions the siren can be silenced by pressing the test button for approx. 3sec.
However, if normal conditions are not restored within approx. 10 minutes (the smoke
does not clear from the room or the temperature does not drop), the siren re-activates.
Testing the detector
Testing the detector is automatically performed up to 10 secs after battery
insertion or after changing the settings on the jumpers. The functioning of the detector
can be tested by pressing and holding the test button for approx. 3 seconds. A properly
functioning detector responds with one beep and a short flash. The alarm information is
transferred to the system. A fault is indicated by 4 beeps and the LED permanently
flashing. In this case, remove the battery and re-insert it after 1 minute. If the fault
indication occurs again (the LED starts permanently flashing after about 1 minute), consult
the installer company.
The detector should be tested this way at least once in every 30 days.
Warning: Never start a fire in a building to test the detector. Instead, use smoke-
simulating aerosols for realistic testing. The information for the control panel is seen as a
FIRE zone.
Battery replacement
The detector monitors its battery voltage and if too low, a report is sent to the control
panel and a short acoustic warning signal is emitted every 45 seconds. Battery
replacement should not be delayed by more than two weeks. As mentioned above, the
detector is automatically tested after each battery insertion. Expired batteries should
not be thrown into the garbage, but disposed according to local regulations.
Specification
Voltage 1x AA 1.5 V alkaline battery
Battery lifetime typically 2 years
Communication frequency 868,5 MHz, OASiS protocol
Wireless communication range 100m (in open space)
Smoke detection optical, light dispersion
Smoke sensor sensitivity m = 0.11 - 0.13 dB/m pursuant to EN 14 604
Temperature detection class A2 pursuant to EN 54-5
Fire-alarm temperature +60 °C to +70 °C
Acoustic power of the built-in siren min. 85 dB/3m A
Operational temperature range -10 to +70 °C
Dimensions diameter 126 mm, height 65 mm
Complies with EN 14 604, A2 EN 54-5, EN 50130-4,
EN 55022, ETSI EN 300220, EN 60950-1
Terms of use ERC REC 70-03
1293-CPD-0261
JABLOTRON ALARMS a.s. hereby declares that the JA-63S80 is in
compliance with the essential requirements and other relevant
provisions of Directive 1989/106/EC and 1999/5/EC. The original of the
conformity assessment can be found on the web site
www.jablotron.com, Technical Support section.
Note: Dispose of batteries safely depending on battery type and local regulations.
Although this product does not contain any harmful materials we suggest you return the
product to the dealer or directly to the manufacturer after use.
The JA-63S-80 wireless optical smoke and heat detector for Oasis system 2 / 2 MKY53100

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Jablotron JA-63S-80 bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Jablotron JA-63S-80 in de taal/talen: Engels als bijlage per email.

De handleiding is 0,07 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

loading

Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info