4.5 Installer Parameters Table
4.5.1 Category 1 - Room Thermostat Settings
Note
1) Remember to always press the green button to confirm that you want to store your new Installer Set-
Up setting. To exit the Installer Mode press the AUTO or MAN button.
Parameter Parameter
No.
Factory Default Setting Optional Setting
Category 1 Parameters – Room Thermostat Settings
Display Description Display Description
AM-PM / 24hr
Display
1:CL 12 12 hr – AM/PM clock
display format
24 24 hr clock display format
Reset Time/ Temp
Program
2:rP 1 Time / Temp profile
set to factory default
Changes to 0 when
one of the time/temp
profiles are changed
0 Time / Temperature are as
programmed
To restore the factory profile set to 1
Auto Summer/
Winter Time
Change
3:tC 1 Auto Summer/Winter
Time Change
Enabled
0 Auto Summer/Winter Time Change
Disabled
LCD Backlighting 5:bL 1 Backlighting Enable 0 Backlighting Disabled
Upper Temp Limit 6:uL 35 35°C Upper Temp.
Limit
21 to
34
21°C to 34°C adjustment in 1°C
steps
Lower Temp Limit 7:LL 5 5°C Lower Temp.
Limit
5 to 21 6°C to 21°C adjustment in 1°C steps
Optimisation 8:OP 0 Optimisation
Disabled
1 Optimisation Enabled
Temperature
Offset
12:tO 0 No temperature
offset
-3 to
+3
-3°C to +3°C adjustment in 0.1°C
steps
Proportional Band
Width
13:Pb 1.5 Proportional band of
1.5 degrees
1.6 to
3.0
1.6°C to 3.0°C adjustment in 0.1°C
steps
Scheduled
Maintenance Alert
Period (months)
19:SP 0 Scheduled
Maintenance Alert
Period disabled
0 to 48 0 to 48 months adjustment in 1
month steps
Reset Parameters
to Factory
Defaults
20:FS 1 All settings at factory
defaults
Changes to 0 when
one of the parameter
is changed
0 Settings are as modified above
To restore the factory profile set to 1