GMC-I Messtechnik GmbH 19
1) Measuring Contact Current Without Tripping the RCD
Measuring Method
The instrument uses a measuring current of only 1/3 nominal
residual current for the determination of contact voltage U
IN
which occurs at nominal residual current. This prevents tripping of
the RCCB.
This measuring method is especially advantageous, because
contact voltage can be measured quickly and easily at any electri-
cal outlet without tripping the RCCB.
The usual, complex measuring method involving testing for the
proper functioning of the RCD at a given point, and subsequent
substantiation that all other systems components requiring pro-
tection are reliably connected at low resistance values to the
selected measuring point via the PE conductor, is made unneces-
sary.
N-PE Reversal Test
Additional testing is conducted in order to
determine whether or not N and PE are
reversed. The pop-up window shown at
the right appears in the event of reversal.
Attention!
!
Execute a data backup before starting measurement and
switch off all consumers in order to prevent the loss of
data in data processing systems.
Start Measurement
Amongst other values, contact voltage U
IN
and calculated earth-
ing resistance R
E
appear at the display panel.
Note
The measured earthing resistance value R
E
is acquired
with very little current. More accurate results can be
obtained with the selector switch in the R
E
position.
The DC + function can be selected here for sys-
tems with RCCBs.
Unintentional Tripping of the RCD due to Bias Current within the System
If bias currents should occur, they can be measured with the help
of a current clamp transformer as described in section 13.1 on
page 50. The RCCB may be tripped during the contact voltage
test if extremely large bias currents are present within the system,
or if a test current was selected which is too great for the RCCB.
After contact voltage has been measured, testing can be per-
formed to determine whether or not the RCCB is tripped within
the selected time limits at nominal residual current.
Unintentional Tripping of the RCD due to Leakage Current in the Measur-
ing Circuit
Measurement of contact voltage with 30% nominal residual cur-
rent does not normally trip an RCCB. However, the trip limit may
be exceeded as a result of leakage current in the measuring cir-
cuit, e.g. due to interconnected power consumers with EMC cir-
cuit, e.g. frequency converters and PCs.
2) Tripping Test after the Measurement of Contact Voltage
Press the
I
N
key.
The tripping test need
only be performed at
one measuring point for
each RCCB.
If the RCCB is tripped at nominal residual current,
the MAINS/NETZ LED blinks red (line voltage disconnected) and
time to trip t
a
and earthing resistance R
E
appear at the display
panel.
If the RCCB is not tripped at nominal residual current,
the RCD/FI LED lights up red.
Contact Voltage Too High
If contact voltage U
IN
, which has been measured with 1/3 nomi-
nal residual current I
N
and extrapolated to I
N
, is > 50 V (> 25 V),
the U
L
/R
L
LED lights up red.
If contact voltage U
IN
exceeds 50 V (25 V) during the measuring
sequence, safety shut-down occurs.
Note
Safety Shut-down: At up to 70 V, a safety shut-down is
tripped within 3 seconds in accordance with IEC 61010.
Contact voltages of up to 70 V are displayed. If contact voltage is
greater than 70 V, U
IN
> 70 V is displayed.
Limit Values for Allowable, Continuous Contact Voltage
The limit for allowable, continuous contact voltage is U
L
=50V for
alternating voltages (international agreement). Lower values have
been established for special applications (e.g. medical applica-
tions: U
L
=25V).
Attention!
!
If contact voltage is too high, or if the RCCB is not
tripped, the system must be repaired (e.g. earthing resis-
tance is too high, defective RCCB etc.)!
3-Phase Connections
For proper RCD testing at three-phase connections, the tripping
test must be conducted for one of the three phase conductors
(L1, L2 and L3).
Inductive Power Consumers
Voltage peaks may occur within the measuring circuit if inductive
consumers are shut down during an RCCB trip test. If this is the
case, the test instrument may display the following message: No
measured value (– – – ). If this message appears, switch all power
consumers off before performing the trip test. In extreme cases,
one of the fuses in the test instrument may blow, and/or the test
instrument may be damaged.
19

Hulp nodig? Stel uw vraag in het forum

Spelregels
1

Forum

Gossen-Metrawatt-PROFITEST--MXTRA

Zoeken resetten

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Gossen Metrawatt PROFITEST MXTRA bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Gossen Metrawatt PROFITEST MXTRA in de taal/talen: Engels als bijlage per email.

De handleiding is 2,28 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

loading

Andere handleiding(en) van Gossen Metrawatt PROFITEST MXTRA

Gossen Metrawatt PROFITEST MXTRA Gebruiksaanwijzing - Nederlands - 92 pagina's


Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info