IMPORT ANT! PLEASE READ CAREFULL Y AND SA VE.
This user’ s manual contains important information about your Smoke
Alarm’ s operation. If you ar e installing this Smoke Alarm for use by others,
you must leave this manual—or a copy of it—with the end user .
User’s ManUal
Printed in Mexico
M08-0194-005 Q 09/14
Fire saFeTY Tips
Follow safety rules and prevent hazar dous situations:
1) Use smoking materials properly . Never smoke in bed. 2) Keep matches or
lighters away from childr en; 3) Store flammable materials in proper containers;
4) Keep electrical appliances in good condition and don’t overload electrical
circuits; 5) Keep stoves, barbecue grills, fir eplaces and chimneys grease-
and debris-free; 6) Never leave anything cooking on the stove unattended;
7) Keep portable heaters and open flames, like candles, away from flammable
materials; 8) Don’t let rubbish accumulate.
Keep alarms clean, and test them weekly . Replace alarms immediately if they
are not working pr operly . Smoke Alarms that do not work cannot alert you to a
fire. Keep at least one working fir e extinguisher on every floor , and an additional
one in the kitchen. Have fire escape ladders or other r eliable means of escape
from an upper floor in case stairs ar e blocked.
BeFore YoU insT all This sMoke alarM
Important! Read “Recommended Locations for Smoke Alarms” and
“Locations to Avoid for Smoke Alarms” befor e beginning. This unit monitors
the air , and when smoke reaches its sensing chamber , it alarms. It can give
you more time to escape befor e fire spreads. This unit can ONL Y give an
early warning of developing fires if it is installed, maintained and located
where smoke can r each it, and where all residents can hear it, as described
in this manual. This unit will not sense gas, heat, or flame. It cannot prevent
or extinguish fires.
Understand The Differ ent T ype of Smoke Alarms
Battery powered or electrical? Dif ferent Smoke Alarms provide dif ferent
types of protection. See “About Smoke Alarms” for details.
Know Where T o Install Y our Smoke Alarms
Fire Safety Professionals recommend at least one Smoke Alarm on every
level of your home, in every bedroom, and in every bedr oom hallway or
separate sleeping area. See “Recommended Locations For Smoke Alarms”
and “Locations T o Avoid For Smoke Alarms” for details.
Know What Smoke Alarms Can and Can’t Do
A Smoke Alarm can help alert you to fire, giving you pr ecious time to
escape. It can only sound an alarm once smoke reaches the sensor .
See “Limitations of Smoke Alarms” for details.
Check Y our Local Building Codes
This Smoke Alarm is designed to be used in a typical single-family home.
It alone will not meet requir ements for boarding houses, apartment buildings,
hotels or motels. See “Special Compliance Considerations” for details.
T aBle oF ConTenTs
Introduction .................................................. 1
Fire Safety Tips ............................................... 1
Before Y ou Install This Smoke Alarm ............................. 1
Step By Step Guide T o Programming This Alarm ................... 2
Adding and Linking Additional WIRELESS INTERCONNECT Alarms .. 2
What Y ou Will See and Hear With This Alarm .................... 2
Wireless Operation ............................................ 2
How T o Install This Smoke Alarm .............................. 3-4
Optional Locking Features .................................... 3-4
W eekly T esting .............................................. 3-4
Regular Maintenance ........................................ 3-4
If This Smoke Alarm Sounds .................................... 5
What T o Do In Case Of Fire .................................. 5
Using the Silence Feature ................................... 5
Silencing the Low Battery W arning ............................ 5
Latching Features ......................................... 5
If Y ou Suspect A Problem ....................................... 5
Recommended Locations For Smoke Alarms .................... 5-6
Agency Placement Recommendations ......................... 6
Locations T o Avoid For Smoke Alarms ............................ 6
About Smoke Alarms .......................................... 6
Special Compliance Considerations ............................ 6-7
Limitations Of Smoke Alarms ................................... 7
Limited W arranty .............................................. 7
*All First Alert® Smoke Alarms conform to regulatory requirements,
including UL217 and are designed to detect particles of combustion.
Smoke particles of varying number and size are produced in all fires.
Ionization technology is generally more sensitive than photoelectric
technology at detecting small particles, which tend to be produced in
greater amounts by flaming fir es, which consume combustible materials
rapidly and spread quickly . Sources of these fires may include paper burning
in a wastebasket, or a grease fir e in the kitchen.
Photoelectric technology is generally more sensitive than ionization
technology at detecting large particles, which tend to be pr oduced
in greater amounts by smoldering fir es, which may smolder for hours
before bursting into flame. Sour ces of these fires may include cigarettes
burning in couches or bedding.
For maximum protection, use both types of Smoke Alarms on each
level and in every bedroom of your home.
• Thisunit willnot alerthearing impair ed r esidents.It isrecommended
that you install special units which use devices like flashing strobe
lights to alert hearing impaired r esidents.
• Unitwill notoperate withoutbattery power .The SmokeAlarm
cannot work until you install the batteries in the correct position
(Match “+” to “+” and “-” to “-”).
• ThisSmoke Alarmhas abattery drawerwhich r esistsclosing
unless batteries are installed.
• Donot installthis unitover anelectrical junctionbox.Air currents
aroundjunction boxescanprevent smokefromreachingthe
sensing chamber and prevent the unit fr om alarming. Only AC
power edunitsareintended forinstallation overjunction boxes.
• Donot standtoo closeto theunit whenthealarm issounding.
It is loud to wake you in an emergency . Exposure to the horn at
close range may harm your hearing.
• Donot paintover theunit. Paintmay clogtheopenings tothe
sensing chamber and prevent the unit fr om operating properly .
123
iF This sMoke alarM soUnds
responding To an alarM
During an alarm, you will hear a loud, repeating horn pattern:
3 beeps, pause, 3 beeps, pause. The red LED will flash rapidly .
• Ifthe unitalarms andyou ar e nottestingthe unit,it iswar ningyou
of a potentially dangerous situation that r equires your immediate
attention. NEVER ignore any alarm. Ignoring the alarm may r esult in
injuryor death.
• Neverremove thebatteriesfrom abatteryoperated SmokeAlarm to
stop an unwanted alarm (caused by cooking smoke, etc.). Removing
batteries disables the alarm so it cannot sense smoke, and removes
your protection. Instead open a window or fan the smoke away fr om
the unit. The alarm will reset automatically .
• Ifthe unitalarms geteveryone outof thehouseimmediately.
Wireless inTerConneCT
Ba TTer Y opera Ted
sMoke alarM
liMiTed WarranTY
BRK Brands, Inc., (“BRK”) the maker of First Alert® brand products warrants
that for a period of ten years from the date of pur chase, this product will be
free fr om defects in material and workmanship. BRK, at its option, will repair
or replace this pr oduct or any component of the product found to be defective
during the warranty period. Replacement will be made with a new or re-
manufactured pr oduct or component. If the product is no longer available,
replacement may be made with a similar pr oduct of equal or greater value.
This is your exclusive warranty .
This warranty is valid for the original retail pur chaser from the date of initial
retail pur chase and is not transferable. Keep the original sales receipt. Proof
of purchase is r equired to obtain warranty performance. BRK dealers, service
centers, or retail stor es selling BRK products do not have the right to alter ,
modify or any way change the terms and conditions of this warranty .
This warranty does not cover normal wear of parts or damage resulting fr om
any of the following: negligent use or misuse of the product, use on impr oper
voltage or current, use contrary to the operating instructions, disassembly ,
repair or alteration by anyone other than BRK or an authorized service center .
Further , the warranty does not cover Acts of God, such as fire, flood,
hurricanes and tornadoes or any batteries that are included with this unit.
BRK shall not be liable for any incidental or consequential damages caused by
the breach of any expr ess or implied warranty . Except to the extent prohibited
by applicable law , any implied warranty of merchantability or fitness for a
particular purpose is limited in duration to the duration of the above warranty .
Some states, provinces or jurisdictions do not allow the exclusion or limitation
of incidental or consequential damages or limitations on how long an implied
warranty lasts, so the above limitations or exclusion may not apply to you.
This warranty gives you specific legal rights, and you may also have other
rights that vary from state to state or pr ovince to province.
How to Obtain W arranty Service
Service: If service is requir ed, do not return the product to your retailer .
In order to obtain warranty service, contact the Consumer Af fairs Division at
1-800-323-9005, 7:30 AM - 5:00 PM Central Standard Time, Monday thr ough
Friday . T o assist us in serving you, please have the model number and date
of purchase available when calling.
For Warranty Service return to:
BRK Brands, Inc., 25 Spur Drive, El Paso, TX 79906
Battery: BRK Brands, Inc. make no warranty , expr ess or implied, written or
oral, including that of merchantability or fitness for any particular purpose
with respect to battery .
loCa Tions To aVoid For sMoke alarMs
For best performance, it is recommended you A VOID installing Smoke
Alarms in these areas:
• Where combustion particles ar e produced. Combustion particles form
when something burns. Areas to avoid include poorly ventilated kitchens,
garages, and furnace rooms. Keep units at least 20 feet (6 meters) from
the sources of combustion particles (stove, furnace, water heater , space
heater) if possible. In areas wher e a 20-foot (6-meter) distance is not
possible – in modular , mobile, or smaller homes, for example – it is
recommended the Smoke Alarm be placed as far fr om these fuel-burning
sources as possible. The placement r ecommendations are intended to
keep these Alarms at a reasonable distance fr om a fuel-burning source,
and thus reduce “unwanted” alarms. Unwanted alarms can occur if a
Smoke Alarm is placed directly next to a fuel-burning source. V entilate
these areas as much as possible.
• In air streams near kitchens. Air curr ents can draw cooking smoke into
the sensing chamber of a Smoke Alarm near the kitchen.
• In very damp, humid or steamy areas, or dir ectly near bathrooms with
showers. Keep units at least 10 feet (3 meters) away from showers,
saunas, dishwashers, etc.
• Where the temperatur es are regularly below 40˚ F (4.4˚ C) or above 100˚ F
(37.8˚ C), including unheated buildings, outdoor rooms, por ches, or
unfinished attics or basements.
• In very dusty , dirty , or greasy areas. Do not install a Smoke Alarm dir ectly
over the stove or range. Keep laundry room Smoke Alarms fr ee of dust or
lint.
• Near fresh air vents, ceiling fans, or in very drafty ar eas. Drafts can blow
smoke away from the unit, pr eventing it from reaching the sensing
chamber .
• In insect infested areas. Insects can clog openings to the sensing
chamber and cause unwanted alarms.
• Less than 12 inches (305mm) away from fluor escent lights.
Electrical “noise” can interfere with the sensor .
• In “dead air” spaces. “Dead air” spaces may prevent smoke fr om
reaching the Smoke Alarm.
Avoiding Dead Air Spaces
“Dead air” spaces may prevent smoke fr om reaching the Smoke Alarm.
T o avoid dead air spaces, follow the installation recommendations below .
On ceilings, install Smoke Alarms as close to the center of the ceiling as
possible. If this is not possible, install the Smoke Alarm at least 4 inches
(102 mm) from the wall or corner .
For wall mounting (if allowed by building codes), the top edge of Smoke
Alarms should be placed between 4 and 12 inches (102 and 305 mm) from
the wall/ceiling line, below typical “dead air” spaces.
On a peaked, gabled, or cathedral ceiling, install the first Smoke Alarm
within 3 feet (0.9 meters) of the peak of the ceiling, measured horizontally .
Additional Smoke Alarms may be requir ed depending on the length, angle,
etc. of the ceiling’ s slope. Refer to NFP A 72 for details on requirements for
sloped or peaked ceilings.
liMiT a Tions oF sMoke alarMs
Smoke Alarms have played a key role in r educing deaths resulting from home
fires worldwide. However , like any warning device, Smoke Alarms can only
work if they are pr operly located, installed, and maintained, and if smoke
reaches them. They ar e not foolproof.
Smoke alarms may not waken all individuals. Practice the escape plan
at least twice a year , making sure that everyone is involved – from kids to
grandparents. Allow childr en to master fire escape planning and practice
before holding a fir e drill at night when they are sleeping. If children or others
do not readily waken to the sound of the smoke alarm, or if ther e are infants
or family members with mobility limitations, make sure that someone is
assigned to assist them in fire drill and in the event of an emer gency . It is
recommended that you hold a fir e drill while family members are sleeping
in order to determine their r esponse to the sound of the smoke alarm while
sleeping and to determine whether they may need assistance in the event
of an emergency .
Smoke Alarms cannot work without power. Battery operated units cannot
work if the batteries are missing, disconnected or dead, if the wr ong type of
batteries are used, or if the batteries ar e not installed correctly . AC units
cannot work if the AC power is cut off for any r eason (open fuse or circuit
breaker , failure along a power line or at a power station, electrical fir e that
burns the electrical wires, etc.). If you are concerned about the limitations
of battery or AC power , install both types of units.
Smoke Alarms cannot detect fires if the smoke does not reach them.
Smoke from fir es in chimneys or walls, on roofs, or on the other side of
closed doors may not reach the sensing chamber and set of f the alarm.
That is why one unit should be installed inside each bedroom or sleeping
area—especially if bedr oom or sleeping area doors are closed at night—and
in the hallway between them.
Smoke Alarms may not detect fire on another floor or area of the home.
For example, a stand-alone unit on the second floor may not detect smoke
from a basement fir e until the fire spreads. This may not give you enough
time to escape safely . That is why r ecommended minimum protection is at
least one unit in every sleeping area, and every bedr oom on every level of
your home. Even with a unit on every floor , stand-alone units may not provide
as much protection as inter connected units, especially if the fire starts in a
remote ar ea. Some safety experts recommend installing interconnected
AC powered units with battery back-up (see “About Smoke Alarms”) or
professional fir e detection systems, so if one unit senses smoke, all units
alarm. Interconnected units may pr ovide earlier warning than stand-alone
units since all units alarm when one detects smoke.
Smoke Alarms may not be heard. Though the alarm horn in this unit meets
or exceeds current standar ds, it may not be heard if: 1) the unit is located
outside
a closed or partially closed door , 2) residents recently consumed
alcohol or drugs, 3) the alarm is drowned out by noise fr om stereo, TV , traf fic,
air conditioner or other appliances, 4) residents ar e hearing impaired or sound
sleepers. Special purpose units, like those with visual and audible alarms,
should be installed for hearing impaired r esidents.
Smoke Alarms may not have time to alarm before the fir e itself causes
damage,injury ,or death,since smokefromsome firesmaynot reach
the unit immediately . Examples of this include persons smoking in bed,
children playing with matches, or fir es caused by violent explosions
resulting fr om escaping gas.
Smoke Alarms are not foolproof. Like any electronic device, Smoke Alarms
are made of components that can wear out or fail at any time. Y ou must test
the unit weekly to ensure your continued pr otection. Smoke Alarms cannot
prevent or extinguish fir es. They are not a substitute for property or life
insurance.
Smoke Alarms have a limited life. The unit should be replaced immediately
if it is not operating properly . Y ou should always replace a Smoke Alarm
after 10 years from date of pur chase. Write the purchase date on the space
provided on back of unit.
speCial CoMplianCe Considera Tions
This Smoke Alarm is suitable for use in apartments, condominiums,
townhouses, hospitals, day care facilities, health car e facilities, boarding
houses, group homes and dormitories pr ovided a primary fire detection
system already exists to meet fir e detection requirements in common ar eas
like
lobbies, hallways, or porches. Using this Smoke Alarm in common ar eas
may not provide suf ficient warning to all residents or meet local fire
protection or dinances/regulations.
This Smoke Alarm alone is not a suitable substitute for complete fire
detection systems in places housing many people—like apartment buildings,
condominiums, hotels, motels, dormitories, hospitals, health care facilities,
nursing homes, day care facilities, or gr oup homes of any kind. It is not a
suitable substitute for complete fire detection systems in war ehouses,
industrial facilities, commercial buildings, and special-purpose non-r esidential
buildings which requir e special fire detection and alarm systems. Depending
on the building codes in your area, this Smoke Alarm may be used to pr ovide
additional protection in these facilities.
In new construction, most building codes requir e the use of AC or AC/DC
powered Smoke Alarms only . In existing construction, AC, AC/DC, or DC
powered Smoke Alarms can be used as specified by local building codes.
Refer to NFP A 72 (National Fir e Alarm and Signaling Code) and NFP A 101
(Life Safety Code), local building codes, or consult your Fire Department for
detailed fire pr otection requirements in buildings not defined as “households”.
HUD MAP Program
Certain HUD battery powered Smoke Alarm applications, especially those
that fall under HUD 223(f) MAP (Multi-family Accelerated Processing), may
requir e a 10 Y ear sealed tamper resistant battery . This alarm does not meet
that requir ement. Substitute First Alert SA340B.
Continued...
First Alert® is a register ed trademark of the First Alert T rust used under license.
4567
aBoUT sMoke alarMs
Battery (DC) operated Smoke Alarms: Provide pr otection even when
electricity fails, provided the batteries ar e fresh and correctly installed. Units
are easy to install, and do not r equire professional installation.
AC powered Smoke Alarms: Can be interconnected so if one unit senses
smoke, all units alarm. They do not operate if electricity fails.
AC with battery (DC) back-up: will operate if electricity fails, provided the
batteries are fr esh and correctly installed. AC and AC/DC units must be
installed by a qualified electrician.
WIRELESS INTERCONNECT Smoke Alarms with battery (DC) back-up:
Interconnects with
all WIRELESS INTERCONNECT enabled Smoke and Smoke/CO Alarms
without wires or connectors, so when one alarm sounds, they all sound.
Will operate if electricity fails, provided the batteries ar e fresh and correctly
installed. Units are easy to install, and do not r equire professional installation.
Smoke Alarms for Solar or Wind Energy users and battery backup power
systems: AC powered Smoke Alarms should only be operated with true or
pure sine wave inverters. Operating this Smoke Alarm with most battery-
powered UPS (uninterruptible power supply) pr oducts or square wave or
“quasi sine wave” inverters will damage the Alarm . If you are not sur e about
your inverter or UPS type, please consult with the manufacturer to verify .
Smoke Alarms for the hearing impaired: Special purpose Smoke Alarms
should be installed for the hearing impaired. They include a visual alarm and
an audible alarm horn, and meet the requirements of the Americans With
Disabilities Act. Can be interconnected so if one unit senses smoke, all units
alarm.
Smoke alarms are not to be used with detector guards unless the
combination has been evaluated and found suitable for that purpose.
All these Smoke Alarms are designed to pr ovide early warning of fires if located,
installed and cared for as described in the user’ s manual, and if smoke reaches
them. If you are unsur e which type of Smoke Alarm to install, refer to Chapter
2 of the National Fire Pr otection Association (NFP A) Standard 72 (National
Fire Alarm and Signaling Code) and NFP A 101 (Life Safety Code). National
Fire Pr otection Association, One Batterymarch Park, Quincy , MA 02269-9101.
Local building codes may also requir e specific units in new construction or in
differ ent areas of the home.
Printed in Mexico M08-0194-005 Q 09/14
Wha T To do in Case oF Fire
• Don’t panic; stay calm. Follow your family escape plan.
• Get out of the house as quickly as possible. Don’t stop to get dr essed or
collect anything.
• Feel doors with the back of your hand before opening them. If a door
is cool, open it slowly . Don’ t open a hot door . Keep doors and windows
closed, unless you must escape through them.
• Cover your nose and mouth with a cloth (preferably damp). T ake short,
shallow breaths.
• Meet at your planned meeting place outside your home, and do a head
count to make sure everybody got out safely .
• Call the Fire Department as soon as possible fr om outside. Give your
address, then your name.
• Never go back inside a burning building for any reason.
• Contact your Fire Department for ideas on making your home safer .
Alarms have various limitations. See “Limitations of Smoke Alarms” for
details.
Using The silenCe Fea TUre
The Silence Feature can temporarily quiet an unwanted alarm for up to
15 minutes. T o use this feature, pr ess the “Push to T est/Silence” button on
the cover . If the unit will not silence and no heavy smoke is present, or if
it stays in silence mode continuously, it should be replaced immediately.
The LED will continue to flash rapidly while in silence.
The Silence Feature does not disable the unit—it makes it temporarily
less sensitive to smoke. For your safety , if smoke ar ound the unit is
dense enough to suggest a potentially dangerous situation, the unit will
stay in alarm or may re-alarm quickly . If you do not know the source of
the smoke, do not assume it is an unwanted alarm. Not responding to
analarm canresultin propertyloss, injury , ordeath.
silenCing The loW Ba TTerY W arning
This silence feature can temporarily quiet the low battery warning “chirp” for
up to 8 hours. Y ou can silence the low battery warning “chirp” by pressing
the T est/Silence button on the alarm cover .
Once the low battery warning “chirp” silence feature is activated, the unit
continues to flash the Green light twice a minute for 8 hours. After 8 hours, the
low battery “chirp” will resume. Replace the batteries as soon as possible;
this unit will not operate without battery power!
T o deactivate this feature: Pr ess the T est/Silence button again. The unit will
go into T est Mode and the low battery warning will resume (LED flashes and
unit sounds “chirp” once a minute).
To loCk The Ba TTerY CoMp arTMenT
Do not lock the battery compartment until you install the batteries and
test the Smoke Alarm.
If the unit does not alarm during testing,
DO NOT lock the battery compartment!
Install new batteries and test again. If the
Smoke Alarm still does not alarm, replace it
immediately .
1. Using needle-nose pliers, detach one
locking pin from the mounting bracket.
2. After batteries are inserted, then push
the locking pin through the hole near
the battery door latch on the back of the
Smoke Alarm.
opTional loCking Fea TUres
To loCk The MoUnTing BraCkeT
1. Using needle-nose pliers, detach one
locking pin from the mounting bracket.
2. Insert the locking pin through the hole on
the back of the Smoke Alarm as shown
in the diagram.
3. When you attach the Smoke Alarm to the
mounting bracket, the locking pin’ s head
will fit into a notch on the bracket.
The optional locking features ar e designed to prevent unauthorized removal of the battery or alarm. It is not necessary to activate the locks in
single-family households where unauthorized battery or alarm r emoval is not a concern.
These Smoke Alarms have two separate locking features: one to lock the battery compartment, and the other to lock the
Smoke Alarm to the mounting bracket. Y ou can choose to use either feature independently , or use them both.
T oolsyou willneed: • Needle-nosepliers •Standard flatheadscrewdriver .
Both locking features use locking pins, which ar e molded into the mounting bracket. Depending on which locking features you
use, remove one or both pins fr om the mounting bracket using needle-nose pliers.
T o permanently remove either locking pin, insert a flathead scr ewdriver between the locking pin and the lock, and pry
the pin out of the lock.
To UnloCk The Ba TTerY CoMp arTMenT
1. Remove the Smoke Alarm from the
mounting bracket. If the unit is locked to
the bracket, see the section “T o Unlock
the Mounting Bracket.”
2. Insert a flathead screwdriver under the
head of the locking pin, and gently pry
it out of the battery compartment lock.
(If you plan to relock the battery
compartment, save the locking pin.)
3. T o relock the battery compartment,
close the battery door and reinsert
locking pin in lock.
4. Reattach the Smoke Alarm to the
mounting bracket.
When replacing the batteries, always test
the Smoke Alarm before r elocking the
battery compartment.
To UnloCk The MoUnTing BraCkeT
1. Insert a flathead screwdriver into the
rectangular cut-out on the mounting
bracket nearest to the locking pin.
2. Pry the Smoke Alarm away from
the bracket by pushing up on the
screwdriver and turning the Smoke
Alarm counterclockwise (left) at the
same time.
regUlar MainTenanCe
This unit has been designed to be as maintenance free as possible, but ther e
are a few simple things you must do to keep it working pr operly .
• T est it at least once a week.
• Clean the Smoke Alarm at least once a month; gently vacuum off any
dust using your household vacuum’ s soft brush attachment, and test the
Smoke Alarm after cleaning. Never use water , cleaners or solvents since
they may damage the unit.
• If the Smoke Alarm becomes contaminated by excessive dirt, dust and/or
grime, and cannot be cleaned to avoid unwanted alarms, replace the unit
immediately .
• Relocate the unit if it sounds frequent unwanted alarms. See “Locations
to Avoid For Smoke Alarms” for details.
• When the battery becomes weak, the Smoke Alarm unit will “chirp”
approximately once a minute (the low battery warning). This low battery
warning should last for up to 7 days, but you should replace the battery
immediately to continue your protection.
Choosing a replacement battery:
Y our Smoke Alarm requir es 2 “AA” batteries: Energizer E91 or Duracell MN1500.
These batteries are available at many local retail stores.
• Alwaysuse theexact batteriesspecified bythis User’ s Manual.
DO NOT use rechar geable batteries. Clean the battery contacts and
also those of the device prior to battery installation. Install batteries
correctly with r egard to polarity (+ and -).
• Pleasedispose ofor recycleusedbatteries properly , followingany
local regulations. Consult your local waste management authority
or recycling or ganization to find an electronics recycling facility in
your area. DO NOT DISPOSE OF BA TTERIES IN FIRE. BA TTERIES
MA Y EXPLODE OR LEAK.
• Keepbattery outof reachofchildren.In theevent abattery is
swallowed, immediately contact your poison control center , your
physician, or the National Battery Ingestion hotline at 202-625-3333
asserious injurymay occur .
Actual service life depends on the Smoke Alarm and the environment in
which it is installed. All the batteries specified above are acceptable
replacement batteries for this unit. Regar dless of the manufacturer’ s
suggested
battery life, you MUST replace the battery immediately once the unit starts
“chirping” (the “low battery warning”).
T o replace the batteries (without
removing Alarm fr om the ceiling
or wall):
1. Open the battery compartment.
2. Press tabs A and B as shown in the
diagram and remove each battery .
3. Insert the new batteries, making sure
they snap completely into the battery
compartment. Match the terminals
on the ends of the batteries with the
terminals on the unit.
4. Close the battery compartment, and
then test the unit by pressing the T est/
Silence button.
adding and linking addiTional Wireless
inTerConneCT alarMs
• NEVERuse anopen flameof anykind totestthis unit.Y ou might
accidentally damage or set fire to the unit or to your home. The
built-in test switch accurately tests the unit’ s operation as r equired
by Underwriters Laboratories, Inc. (UL).
• Ifthe Alarmever failsto testproperly , replaceitimmediately .
Products under warranty may be r eturned to the manufacturer for
replacement. See “Limited W arranty” for details.
• DONOT standclose tothe alarmwhen thehorn issounding.
Exposure at close range may be harmful to your hearing. When
testing, step away when horn starts sounding.
It is important to test this unit every week to make sure it is working
properly. Using the test button is the recommended way to test this Smoke
Alarm. Press and hold the test button on the cover of the unit until the alarm
sounds (the unit may continue to alarm for a few seconds after you release
the button). If it does not alarm, make sure the unit is r eceiving power (LED
will flash approximately once a minute indicating it has power); and test it
again. If it still does not alarm, replace it immediately . During testing you will
hear a loud, repeating horn pattern: 3 beeps, pause, 3 beeps, pause.
NOTE: Steps 1 through 3 below need to be completed within two
minutes. If more than two minutes pass, the Gr een power LED will
stop blinking. Simply open the battery drawer of the second Alarm
and repeat steps 1 thr ough 3.
1. Insert the batteries into the battery
drawer of the next Alarm.
DO NOT CLOSE THE DRAWER.
2. Press and hold the test button and
then close the battery drawer .
3. Once you hear the unit chirp, release
the test button. The Green power
LED will start to blink indicating the
WIRELESS INTERCONNECT Alarm is waiting for
program data fr om one of the other setup WIRELESS INTERCONNECT
Alarms.
4. Press and hold the test button on the first Alarm, until the second Alarm
chirps and its Green power LED stops blinking. Then r elease the test
button.
5. If you purchased a T alking Smoke Alarm, you will now be pr ompted to
set the Alarm’ s location. Follow the dir ections given by the Alarm.
6. If you have purchased the har dwired battery back-up WIRELESS
INTERCONNECT Alarm, you can now connect the hardwir ed Alarm by
installing the three-wir e connector on the ceiling to the Alarm.
7. Repeat steps 1-6 for additional WIRELESS INTERCONNECT Alarms.
Y ou have now successfully linked your new WIRELESS INTERCONNECT
Alarms. T o add additional Alarms at a later time, follow steps 1 through 6.
Wireless opera Tion
First Alert® WIRELESS INTERCONNECT T echnology is the easy , cost-
effective way to pr ovide your family with whole-home safety . All WIRELESS
INTERCONNECT Alarms communicate with each other without wires or
connectors. When one Alarm sounds, they all sound. This provides your family
with an earlier warning of potential danger , and gives you mor e time to react.
The communication distance (range) between any two WIRELESS
INTERCONNECT Alarms is typically 50 feet (15 meters) inside of a home.
Some features of a home, such as the number of floors, number/size of
rooms, furniture and types of building materials used may r educe the range
of the Alarms. Examples include: suspended ceilings, ductwork, large
metallic appliances (refrigerators) and metal studs. A featur e of WIRELESS
INTERCONNECT Alarms is that they operate as a mesh network. All
Alarms will repeat any alarm signal that is r eceived to all other WIRELESS
INTERCONNECT Alarms. Interference fr om structural conditions can be
overcome by adding additional Alarms to r oute the wireless signal around
obstructions.
• Therange andproperoperation ofany wirelessdevicewill vary
depending on its surroundings. It is very important that each Alarm is
tested individually before and after installation to make sur e that all
Alarms respond pr operly .
• TheWIRELESS INTERCONNECT Alarms are not to be used outdoors
or to transmit between buildings. The Alarms will not communicate
properly under these conditions.
• Metalobjects andmetallic wallpapermay interferewith signalsfrom
wireless Alarms. Alarms should be tested after changes to your
home such as remodeling, moving furniture, and with metal doors
opened and closed.
Y our First Alert® WIRELESS INTERCONNECT Smoke Alarm will automatically
communicate potential fires with all other First Alert® WIRELESS
INTERCONNECT Smoke Alarms.
Changes or modifications not expressly appr oved by BRK Brands, Inc.
could void the user’ s authority to operate the equipment.
Model SA511
iF YoU sUspeCT a proBleM
Smoke Alarms may not operate properly because of dead, missing or weak
batteries, a build-up of dirt, dust or grease on the Smoke Alarm cover , or
installation in an improper location. Clean the Smoke Alarm as described
in “Regular Maintenance,” and install a fresh battery , then test the Smoke
Alarm again. If it fails to test properly when you use the test button, or if
the problem persists, r eplace the Smoke Alarm immediately .
• Ifyou heara “chirp”about oncea minute,replacethe battery .
• Ifyou experiencefrequentnon-emergencyalarms (likethose caused
by cooking smoke), try relocating the Smoke Alarm.
• Ifthe alarmsounds whenno smokeis visible,trycleaning or
relocating the Smoke Alarm. The cover may be dirty .
• Ifthe alarmdoes notsound duringtesting, tryinstallinga new
battery , and make sur e it is snapped in securely .
• Ifthe alarmsounds 3rapid “chirps”every minute;LEDflashes
approximately once a minute. MALFUNCTION: the device is not
working properly and needs to be r eplaced.
Do not try fixing the alarm yourself – this will void your warranty!
If the Smoke Alarm is still not operating properly , and it is still under warranty ,
please see “How to Obtain W arranty Service” in the Limited Warranty .
reCoMMended loCa Tions For
sMoke alarMs
Installing Smoke Alarms in Single-Family Residences
The National Fire Pr otection Association (NFP A), recommends one Smoke
Alarm on every floor , in every sleeping area, and in every bedroom. In new
construction, the Smoke Alarms must be AC powered and inter connected.
See “Agency Placement Recommendations” for details. For additional
coverage, it is recommended that you install a Smoke Alarm in all r ooms,
halls,
storage areas, finished attics, and basements, wher e temperatures normally
remain between 40˚ F (4.4˚ C) and 100˚ F (37.8˚ C). Make sur e no door or
other obstruction could keep smoke from r eaching the Smoke Alarms.
More specifically , install Smoke Alarms:
• On every level of your home, including finished attics and basements.
• Inside every bedroom, especially if people sleep with doors closed.
• In the hall near every sleeping area. If your home has multiple sleeping
areas, install a unit in each. If a hall is over 40 feet (12 meters) long, install
an alarm at each end.
• At the top of the first-to-second floor stairway , and at bottom of basement
stairway .
Specific requir ements for Smoke Alarm installation vary from state to state
and from r egion to region. Check with your local Fire Department for curr ent
requir ements in your area. It is recommended AC or AC/DC units be
interconnected for added protection.
WIRELESS
INTERCONNECT
ALARMS
agenCY plaCeMenT reCoMMenda Tions
NFP A 72 Chapter 29
“For your information, the National Fire Alarm and Signaling Code , NFP A 72,
reads as follows:”
29.5.1* Required Detection.
29.5.1.1* Where r equired by other governing laws, codes, or standards for
a specific type of occupancy , appr oved single and multiple-station smoke
alarms shall be installed as follows:
(1)*In all sleeping rooms and guest r ooms
(2)* Outside of each separate dwelling unit sleeping area, within 21 ft (6.4 m)
of any door to a sleeping room, with the distance measur ed along a path
of travel
(3) On every level of a dwelling unit, including basements
(4) On every level of a residential boar d and care occupancy (small facility),
including basements and excluding crawl spaces and unfinished attics
(5)*In the living area(s) of a guest suite
(6) In the living area(s) of a r esidential board and care occupancy
(small facility)
(Reprinted with permission from NFP A 72® , National Fire Alarm and Signaling
Code Copyright © 2010 National Fire Pr otection Association, Quincy , MA
02269. This reprinted material is not the complete and of ficial position of
the National Fire Pr otection Association, on the referenced subject which
is repr esented only by the standard in its entirety), (National Fir e Alarm and
Signaling Code® and NFP A 72® ar e registered trademarks of the National Fir e
Protection Association, Inc., Quincy , MA 02269).
Features:
WIRELESS INTERCONNECT
Enabled
V oice with Programmable Location
T wo Latching Features
Optipath 360 T echnologyTM
T wo Silence Features
inTrodUCTion
Thank you for choosing First Alert® for your Smoke Alarm needs. Y ou have
purchased a state-of-the-art Smoke Alarm designed to pr ovide you with
early warning of a fire. Key features include:
WIRELESS INTERCONNECT Enabled. Alarm automatically communicates
with other WIRELESS INTERCONNECT enabled alarms when installed.
Exclusive Voice Warning with Location will tell you the prepr ogrammed
location of the initiating unit and danger detected. Programmable up to
11 locations (ex. “basement”). When alarms sounds, if programmed for
basement it will say “W arning, evacuate, smoke in basement” along with
all other installed WIRELESS INTERCONNECT V oice alarms.
Spread Spectrum Horn Tone. Lower and varying horn frequency makes it
easier for elderly with normal age related hearing loss to hear horn. Sweeps
through the 2200 – 3400 Hz range.
RF Interconnect. Reliable and secure radio fr equency communication
between alarms. 915MHz frequency with 65,000 security codes and 3
channel frequency hopping.
Optipath 360 TechnologyTM provides 360 degr ees of direct access to the
smoke sensor .
Single Button Test/Silence eliminates confusion. Depending on what mode
the alarm is in, pushing the button provides dif ferent functions such as
testing the alarm, silencing the alarm, r e-testing the alarm when in silence and
clearing the Latching features.
Two Silence Features. T emporarily silence low battery chirp for up to eight
hours before r eplacing low battery or silence an unwanted alarm for several
minutes.
Two Latching Features. Alarm Latch: Easily identifies initiating alarm even
after alarm condition has subsided. Low Battery Latch: Identifies which unit
is in low battery condition.
Perfect Mount System includes a gasketless base for easy installation and
a mounting bracket that keeps the alarm secure over a wide r otation range
to allow for perfect alignment.
© 2014 BRK Brands, Inc. All rights reserved.
Distributed by BRK Brands, Inc.
3901 Liberty Street Road, Aur ora, IL 60504-8122
Consumer Affairs: (800) 323-9005 • www .firstalert.com
la TChing Fea TUres
Alarm Latch is activated after an Alarm is exposed to alarm levels of smoke.
After smoke levels drop below alarm levels, the “Smoke” Red LED will begin to
flash On for 2 seconds/Off for 2 seconds. It will continue to flash or “latch” for
about 15 minutes, to give you time to determine which unit initiated the alarm.
Low Battery Latch is activated when the Alarm is in the “low battery condition”.
When this occurs, the Power LED flashes Green On for 2 seconds/Of f for 2
seconds for about 15 minutes. This feature is designed to help you identify
which Alarm needs to have the battery replaced. Although, the Alarm will
sound the low battery chirp approximately once every minute, sometimes
during the initial stages of “low battery”, the Alarm will chirp in greater
intervals than one minute, sometimes up to several hours, until the battery
reaches a steady low battery level. This innovative featur e eliminates the
frustration of waiting for and/or identifying which unit is chirping.
sTep BY sTep gUide To prograMMing
This alarM
FOR FIRST TIME AND WHEN CHANGING BA TTERIES
Action:
1. Insert batteries (2, AA batteries).
Alarm Will Say:
“W elcome, First Alert Smoke Alarm.”
“No location programmed” if
first time or “[Location, example:
“Basement”] location programmed”
when changing batteries.
“T o select location, press and hold
test button now .”
2. Press & Hold T est Button if
you would like to program the
location or change the location of
the Alarm. Release button after
Alarm responds.
“T o save location, press and hold
test button after location is heard.”
Alarm will speak list of locations
(see below).
3. After you hear the location of
where you ar e placing the Alarm,
Press & Hold the T est Button.
“[Location, example: “Basement”]
location saved.”
If no location is chosen:
“No location saved.”
Y our Alarm has now been programmed for the location of your choice.
Available locations:
Basement Kitchen Child’ s Bedr oom
Living Room Dining Room Master Bedroom
Family Room No Location Guest Bedroom
Office Hallway Utility Room
WHA T YOU WILL SEE AND HEAR WITH THIS ALARM
Under Normal Operations
Voice: Silent
Horn: Silent
Power LED: Flashes Green once/minute
When Y ou T est the Alarm
Voice: “T esting.” Horn: 3 beeps, pause, 3 beeps; Voice: “W arning,
evacuate smoke in [Location, example: “Basement”]. Evacuate.”
Smoke LED: Flashes Red in sync with the horn patter n
If Battery Becomes Low
Voice: “Replace battery in [Location, example “Basement”].”
Repeated every 5 hours
Horn: chirps once a minute
Power LED: Flashes Green On for 2 seconds/Of f for 2 seconds.
Low Battery Latch is now engaged.
If Alarm is Not Operating Properly (MALFUNCTION SIGNAL)
Voice: “Detector error in [Location, example “Basement”], please see
manual.” Repeated every 5 hours
Horn: Three rapid chirps every minute
Smoke LED: Flashes approximately once a minute
Smoke is Detected
Horn: 3 beeps, pause, repeating 3 times
Voice: “W arning, evacuate smoke in [Location, example: “Basement”].
Evacuate.”
Smoke LED:
During Alarm: Flashes Red in sync with the horn patter n.
After Alarm: Flashes Red On for 2 seconds/Off for 2 seconds.
Smoke Alarm Latch is now engaged.
Smoke Alarm is Silenced
Horn: Off
Smoke LED: Flashes Red
hoW To insT all This sMoke alarM
The p arTs oF This sMoke alarM
1. T est/Silence button
2. Battery drawer
3. Power indicator LED
4. Smoke Alarm LED
Tools YoU Will need:
This unit is designed to be mounted
on the ceiling, or on the wall if necessary .
• Pencil
• Drill with 3/16” (5 mm) drill bit
• Phillips screwdriver
• Hammer
• Pliers to activate optional
“tamper -resistant” locking
features
FolloW These siMple sTeps!
1. Hold base firmly and twist the mounting bracket counterclockwise to
separate it from the base.
2. Hold the mounting bracket against the ceiling (or wall) so the vertical
mounting slot is aligned in the 12 o’clock position and trace around the
inside of the mounting slots (vertical and horizontal mounting).
3. Put the unit where it won’ t get covered with dust when you drill the
mounting holes.
4. Using a 3/16” (5 mm) drill bit, drill a hole through the center of the oval
outlines you traced.
5. Insert the plastic screw anchors (in the plastic bag with scr ews) into the
holes. T ap the screw anchors gently with a hammer , if necessary , until
they are flush with the ceiling or wall.
6. Line the mounting bracket up
over the plastic screw anchors.
7. Screw the mounting bracket to
the ceiling or wall through the
mounting slots using the two
screws pr ovided.
8. Attach the Smoke Alarm to the
mounting bracket. Line up the guides on the alarm’ s base with the
guides on the mounting bracket. When guides are lined up, turn the
base clockwise (right) until it snaps into place.
NOTE: Once the Smoke Alarm is snapped onto the mounting
bracket,you canrotatethe SmokeAlarm toadjust thealignment.
9. T est the Smoke Alarm. See “W eekly T esting.”
If you want to lock the battery drawer , or lock the Smoke Alarm to the
mounting bracket, please read the “Optional Locking Featur es” section
before you begin installation.
CONFORMS TO
UL STD 217
Weekl Y TesTing
FCC Compliance
This equipment has been tested and found to comply with the limits for a
Class B digital device, pursuant to Part 15 of the FCC rules. These limits are
designed to provide r easonable protection against harmful interference in
a residential installation. This equipment generates, uses and can radiate
radio frequency ener gy and, if not installed and used in accordance with
the instructions, may cause harmful interference to radio communications.
However , there is no guarantee that the interference will not occur in a
particular installation. If this equipment does cause harmful interference
to radio or television reception, which can be determined by turning
the equipment off and on, the user is encouraged to try to corr ect the
interference by one or mor e of the following measures:
• Reorient or relocate the r eceiving antenna.
• Increase the separation between the equipment and r eceiver .
• Connect the equipment into an outlet on a circuit dif ferent from that of
the receiver .
• Consult the dealer or an experienced radio or TV technician for help.
W arning: Changes or modifications to the product, not expressly approved
by First Alert / BRK Brands, Inc., could void the user’ s authority to operate
the equipment.
This device complies with Part 15 of the FCC Rules. Operation is subject
to the following two conditions: (1) this device may not cause harmful
interference, and (2) this device must accept any interfer ence received,
including interference that may cause undesir ed operation.
FCC ID: M7U5001L
SPECIAL COMPLIANCE CONSIDERA TIONS, Continued