Alarm ModelsHD6135F and HD6135FB; BRK®Auxiliary Devices Models
RM3 and RM4 (Relay Modules), SL177 (Strobe Light).
See www.brkelectronics.com for most current interconnect list.
Interconnected units must meet ALL of the following requirements:
•Amaximum of 18 compatible units may be interconnected
(Maximum of 12 Smoke Alarms).
•The same fuse or circuit breaker must power all interconnected units.
•The total length of wire interconnecting the units should be less than
1000 feet (300 meters). This type of wire is commonly available at
Hardware and Electrical Supply stores.
•
All wiring must conform to all local electrical codes and NFPA 70 (NEC).
Refer to NFPA72, NFPA101, and/or your local building code for further
connection requirements.
HOW TO INSTALL THIS SMOKE ALARM
THE PARTS OF THIS SMOKE ALARM
This Smoke Alarm is designed to be mounted on any standard wiring junction box up to a 4-inch (10 cm) size, on either the ceiling or wall (if allowed by local codes).
Read “Recommended Locations For Smoke Alarms” and “Locations to Avoid For Smoke Alarms” before you begin installation.
Tools you will need: • Needle-nose pliers or utility knife•Standard Flathead screwdriver.
FOLLOWTHESEINSTALLATION STEPS
STAND-ALONE ALARM ONLY:
•Connect the white wire on the power connector to the neutral wire in
the junction box.
•Connect the black wire on the power connector to the hot wire in the
junction box.
•Tuck the orange wire inside the junction box. It is used for interconnect
only.
INTERCONNECTED UNITS ONLY:
Strip off about 1/2” (12 mm) of the plastic coating on the orange wire
onthe power connector.
•Connect the white wire on the power connector to the neutral wire in
the junction box.
•Connect the black wire on the power connector to the hot wire in the
junction box.
•
Connect the orange wireon the power connector to the interconnect
wirein the junction box. Repeat for each unit you areinterconnecting.
Never connect the hot or neutral wires in the junction box to the orange
interconnect wire. Never cross hot and neutral wires between Alarms.
STAND-ALONE ALARM ONLY:
•If you are only installing one Smoke Alarm, restore power to the
junction box.
INTERCONNECTED UNITS ONLY:
•If you areinterconnecting multiple Smoke Alarms, repeat steps
1-5 for each Smoke Alarm in the series. When you are finished,
restore power to the junction box.
#
}
)
}
*
&
%
$
!
!
""#
A.Unswitched 120VAC
60Hz source
B.Toadditional units; Maximum = 18 total
(Maximum 12 Smoke Alarms)
1. Smoke Alarm
2. Ceiling or Wall
3.Power Connector
4. Wire Nut
5. Junction Box
6.Neutral Wire (Wht)
7. Interconnect Wire
(Orange)
8.Hot Wire(Blk)
4
OPTIONAL LOCKING FEATURES
The locking features are designed to discourage unauthorized removal of the batteries or Alarm. It is not necessary to activate the locks in single-family
households where unauthorized battery or Alarm removal is not a concern.
These Smoke Alarms have two separate locking features: one to lock the battery compartment, and the other to lock the Smoke Alarm
to the mounting bracket. You can choose to use either feature independently, or use them both.
Tools you will need:•Needle-nose pliers or utility knife • Standard Flathead screwdriver.
Both locking features use locking pins, which are molded into the mounting bracket. Using needle-nose pliers or a utility knife, remove
one or both pins from the mounting bracket, depending on how many locking features you want to use.
To permanently remove either lock, insert a flathead screwdriver between the locking pin and the lock, and pry the pin out of the lock.
TO LOCK THE BATTERY COMPARTMENT
Do not lock the battery compartment until you have installed the
batteries and tested the battery back-up.
1.Push and hold Test button until the alarm sounds: 3 beeps, pause,
3beeps, pause. LED flashes once every second.
If the unit does not alarm during testing, DO NOT lock the battery
compartment! Install new batteries and test again. If the Smoke
Alarm still does not alarm, replace it immediately.
2.Using needle-nose pliers or a utility knife, detach one locking pin
from the mounting bracket.
3.Push the locking pin through the hole near the battery drawer on the
back of the Smoke Alarm.
TO UNLOCK THE BATTERY COMPARTMENT
Once the Smoke Alarm is installed, you must disconnect it from the AC power
beforeunlocking the battery compartment.
ELECTRICAL SHOCK HAZARD. Turnoffthe power to the area wherethe
Smoke Alarm is installed before removing it from the mounting bracket.
Failure to turn off the power first may result in serious electrical shock,
injury or death.
Always discharge the branch circuit before servicing an AC or AC/DC
Smoke Alarm. First, turn off the AC power at the circuit breaker or fuse box.
Next, remove the batteries from Smoke Alarms with battery back-up.
Finally,press and hold the Test/Silence button for 5-10 seconds to
discharge the branch circuit.
1.Remove the Smoke Alarm from the mounting
bracket. If the unit is locked to the bracket, see
the section “To Unlock the Mounting Bracket.”
2.Disconnect the power connector by gently prying
it away from the back of the Smoke Alarm.
3.Insert a flathead screwdriver under the head
of the locking pin, and gently pry it out of the
battery compartment lock. (If you plan to relock
the battery compartment, save the locking pin.)
4.To relock the battery compartment, close the
battery door and reinsert locking pin in lock.
5.Reconnect the power connector to the back of the Smoke Alarm, reattach
the Smoke Alarm to the mounting bracket, and restore the power.
When replacing the batteries, always test the Smoke Alarm before relocking
the battery compartment.
TO UNLOCK THE MOUNTING BRACKET
ELECTRICAL SHOCK HAZARD. Turn off the power to the area where the
Smoke Alarm is installed beforeremoving it from the mounting bracket.
Failure to turn off the power first may result in serious electrical shock,
injury or death.
Always discharge the branch circuit before servicing an AC or AC/DC
Smoke Alarm. First, turnoffthe AC power at the circuit breaker or fuse
box. Next, remove the batteries from Smoke Alarms with battery back-up.
Finally, press and hold the Test/Silence button for 5-10 seconds to
discharge the branch circuit.
1.Insert a flathead screwdriver between the
mounting bracket pin and the mounting bracket.
2.Pry the Smoke Alarm away from the bracket by
turning both the screwdriver and the Smoke
Alarm counterclockwise (left) at the same time.
TO LOCK THE MOUNTING BRACKET
1.Using needle-nose pliers, detach one locking pin from mounting bracket.
2.Insert the locking pin into the lock located
opposite from the battery drawer as shown
in the diagram.
3.When you attach the Smoke Alarm to the mounting bracket, the locking
pin’s head will fit into a notch on the bracket.
Locking Features (Continued)
Printed in Mexico M08-0224-000 Q11/10
First Alert®is a registered trademark of the First Alert Trust.
BRK®is a registered trademark of BRK Brands, Inc.
WEEKLY TESTING
•NEVER use an open flame of any kind to test this unit. You might
accidentally damage or set fire to the unit or to your home. The built-
in test switch accurately tests the unit’s operation as required by
Underwriters Laboratories, Inc. (UL).
•If the Alarm ever fails to test properly, replace it immediately.
Products under warranty may be returned to the manufacturer
for replacement. See “Limited Warranty” at the end of this manual.
DONOT stand close to the Alarm when the horn is sounding. Exposure
atclose range may be harmful to your hearing. When testing, step away
when hornstarts sounding.
Itis important to test this unit every week to make
sure it is working properly. Using the test button is the
recommended way to test this Smoke Alarm.
Press and holdthe Test/Silence button on the cover of the
unit until the alarm sounds (the unit may continue to alarm
for a few seconds after you release the button). If it does
not alarm, make surethe unit is receiving power and test
it again. If it still does not alarm, replace it immediately.
During testing, you will hear a loud, repeating horn pattern: 3 beeps,
pause, 3 beeps, pause. LED flashes once every second.
When testing a series of interconnected units you must test each unit
individually.Make sure all units alarm when each one is tested.
REGULAR MAINTENANCE
Use only the replacement batteries listed below. The unit may not
operate properly with other batteries. Never use rechargeable batteries
since they may not provide a constant charge.
This unit has been designed to be as maintenance-free as possible, but there
areafew simple things you must do to keep it working properly:
•Test it at least once a week.
•Clean the Smoke Alarm at least once a month; gently vacuum the
outside of the Smoke Alarm using your household vacuum’s soft brush
attachment. Test the Smoke Alarm. Never use water, cleaners or solvents
since they may damage the unit.
•If the Smoke Alarm becomes contaminated by excessive dirt, dust and/or
grime, and cannot be cleaned to avoid unwanted alarms, replace the
unit immediately.
•Relocate the unit if it sounds frequent unwanted alarms. See “Locations
ToAvoid For Smoke Alarms” for details.
•When the battery back-up becomes weak, the Smoke Alarm will “chirp”
about once a minute (the low battery warning). This warning should last 7
days, but you should replace the batteries immediately to continue your
protection.
UNDERSTANDING THE INDICATOR LIGHTS
AND ALARM HORN PATTERNS
NOTE: When power is applied, unit(s) may alarm momentarily.
*When any Smoke Alarm in an interconnected series triggers an alarm, its
red LED will flash rapidly. The red LEDs will remain OFF on any remaining
alarms in the series. This feature helps responders identify which unit(s)
triggered the alarm.
Latching AlarmRed LED flashing 2
seconds on,
2seconds off
Not available
AC Power
DC Power
Normal OperationConstant Green LED
No Audible Alarm
Flashing Green LED
once/minute
NoAudible Alarm
Test ConditionRapidly Flashing
Red LED
Audible Alarm
Rapidly Flashing
Red LED
Audible Alarm
Silence ModeRapidly Flashing
Red LED
Audible Alarm Off
Rapidly Flashing
Red LED
Audible Alarm Off
Alarm Condition*
(Initiating Unit)
Rapidly Flashing
Red LED
Audible Alarm
Rapidly Flashing
Red LED
Audible Alarm
Alarm Condition*
(Remote Units)
Constant Green LED
Audible Alarm
Green LED Off
Audible Alarm
IFTHIS SMOKE ALARM SOUNDS
RESPONDING TO AN ALARM
During an alarm, you will hear a loud, repeating horn pattern: 3 beeps,
pause, 3 beeps, pause.
•Ifthe unit alarms and you are not testing the unit, it is warning you of a
potentially dangerous situation that requires your immediate attention.
NEVER ignore any alarm. Ignoring the alarm may result in injury or
death.
•Never disconnect the AC power to quiet an unwanted alarm.
Disconnecting the power disables the Alarm so it cannot sense
smoke. This will remove your protection. Instead, open a window or
fan the smoke away from the unit. The Alarm will reset automatically.
•If the unit alarms get everyone out of the house immediately.
•
ELECTRICAL SHOCK HAZARD: Attempting to disconnect the power
connector from the unit when the power is on may result in electrical
shock, serious injury or death.
When an interconnected system of AC powered units is in alarm, the alarm
indicator light on the unit(s) that initiated the alarm will blink rapidly. It will
remain OFF on any remaining units.
If the unit alarms, get everyone out of the dwelling immediately.
Ifthe unit alarms and you are certain that the source of smoke is not a fire—
cooking smoke or an extremely dusty furnace, for example—open a nearby
window or door and fan the smoke away from the unit (Use the Silence Feature
tosilence the Alarm). This will silence the alarm, and once the smoke clears the
unit will reset itself automatically.
WHAT TO DO IN CASE OF FIRE
•Don’t panic; stay calm. Follow your family escape plan.
•Get out of the house as quickly as possible. Don’t stop to
get dressed or collect anything.
•Feel doors with the back of your hand before opening them.
Ifadoor is cool, open it slowly. Don’t open a hot door. Keep doors
and windows closed, unless you must escape through them.
•Cover your nose and mouth with a cloth (preferably damp).
Take short, shallow breaths.
•Meet at your planned meeting place outside your home,
and do a head count to make sure everybody got out safely.
•Call the Fire Department as soon as possible from outside.
Give your address, then your name.
•Never go back inside a burning building for any reason.
•Contact your Fire Department for ideas on making your home safer.
Alarms have various limitations. See "Limitations of Smoke Alarms" for
details.
IF YOU SUSPECT A PROBLEM
Smoke Alarms may not operate properly because of dead, missing or weak
batteries, a build-up of dirt, dust or grease on the Smoke Alarm cover, or
installation in an improper location. Clean the Smoke Alarm as described in
“Regular Maintenance,” and install fresh batteries, then test the Smoke Alarm
again. If it fails to test properly when you use the test button, or if the problem
persists, replace the Smoke Alarm immediately.
•If you hear a “chirp” approximately once a minute, replace the
batteries.
•If you experience frequent non-emergency alarms (like those caused
by cooking smoke), try relocating the Smoke Alarm.
•If the alarm sounds when no smoke is visible, try cleaning or
relocating the Smoke Alarm. The cover may be dirty.
•If the alarm does not sound during testing, make sure it is receiving
ACpower from the household current.
Always discharge the branch circuit before servicing an AC or AC/DC
Smoke Alarm. First, turnoffthe AC power at the circuit breaker or fuse
box. Next, remove the batteries from Smoke Alarms with battery back-up.
Finally, press and hold the test button for 5-10 seconds to discharge the
branch circuit.
If the Smoke Alarm is still not operating properly, and it is still under warranty,
please see “How to Obtain Warranty Service” in the Limited Warranty.
Do not try fixing the alarm yourself – this will void your warranty!
LIMITED WARRANTY
BRK Brands, Inc., ("BRK") the maker of First Alert®brand and BRK®brand
products, warrants that for a period of ten years from the date of purchase,
this product will be free from defects in material and workmanship.
BRK, at its option, will repair or replace this product or any component of
the product found to be defective during the warranty period. Replacement
will be made with a new or remanufactured product or component. If the
product is no longer available, replacement may be made with a similar
product of equal or greater value. This is your exclusive warranty.
This warranty is valid for the original retail purchaser from the date of initial
retail purchase and is not transferable. Keep the original sales receipt.
Proof of purchase is required to obtain warranty performance.
BRK dealers, service centers, or retail stores selling BRK products do not
have the right to alter, modify or any way change the terms and conditions
of this warranty.
This warranty does not cover normal wear of parts or damage resulting
from any of the following: negligent use or misuse of the product, use on
improper voltage or current, use contrary to the operating instructions,
disassembly,repair or alteration by anyone other than BRK or an authorized
service center. Further, the warranty does not cover Acts of God, such as
fire, flood, hurricanes and tornadoes or any batteries that are included with
this unit.
BRK shall not be liable for any incidental or consequential damages
caused by the breach of any express or implied warranty.Except to the
extent prohibited by applicable law, any implied warranty of merchantability
or fitness for a particular purpose is limited in duration to the duration of
the above warranty.Some states, provinces or jurisdictions do not allow
the exclusion or limitation of incidental or consequential damages or
limitations on how long an implied warranty lasts, so the above limitations
or exclusion may not apply to you. This warranty gives you specific legal
rights, and you may also have other rights that vary from state to state or
province to province.
How to Obtain Warranty Service
Service: If service is required, do not return the product to your retailer.
In order to obtain warranty service, contact the Consumer Affairs Division
at 1-800-323-9005, 7:30 AM - 5:00 PM Central Standard Time, Monday
through Friday. To assist us in serving you, please have the model number
and date of purchase available when calling.
For Warranty Service return to:
BRK Brands, Inc., 25 Spur Drive, El Paso, TX 79906
Battery:BRK Brands, Inc. make no warranty,express or implied, written or
oral, including that of merchantability or fitness for any particular purpose
with respect to battery.
RECOMMENDED LOCATIONS FOR
SMOKE ALARMS
Installing Smoke Alarms in Single-Family Residences
The National Fire Protection Association (NFPA), recommends one Smoke
Alarm on every floor, in every sleeping area, and in every bedroom. In new
construction, the Smoke Alarms must be AC powered and interconnected.
See “Agency Placement Recommendations” for details. For additional cover-
age, it is recommended that you install a Smoke Alarm in all rooms, halls,
storage areas, finished attics, and basements, where temperatures normally
remain between 40˚ F (4.4˚ C) and 100˚ F (37.8˚ C). Make sure no door or
other obstruction could keep smoke from reaching the Smoke Alarms.
More specifically, install Smoke Alarms:
•On every level of your home, including finished attics and basements.
•Inside every bedroom, especially if people sleep with the door partly or
completely closed.
•In the hall near every sleeping area. If your home has multiple sleeping
areas, install a unit in each. If a hall is more than 40 feet long (12 meters),
install a unit at each end.
•At the top of the first-to-second floor stairway, and at the bottom
of the basement stairway.
Specific requirements for Smoke Alarm installation vary from state to state
and from region to region. Check with your local Fire Department for current
requirements in your area. Itis recommended AC or AC/DC units be inter-
connected for added protection.
INSTALLING SMOKE ALARMS IN MOBILE HOMES & RVS
For minimum security install one Smoke Alarm as close to each sleeping area
as possible. For more security, put one unit in each room. Many older mobile
homes (especially those built before 1978) have little or no insulation. If your
mobile home is not well insulated, or if you are unsure of the amount of
insulation, it is important to install units on inside walls only. Smoke Alarms
should be installed where temperatures normally remain between 40˚ F (4.4˚ C)
and 100˚ F (37.8˚ C).
WARNING: Test units used in RVs after the vehicle has been in storage,
before every trip, and once a week while in use. Failure to test units
used in RVs as described may remove your protection.
LIMITATIONS OF SMOKE ALARMS
Smoke Alarms have played a key role in reducing deaths resulting from home
fires worldwide. However, like any warning device, Smoke Alarms can only
work if they are properly located, installed, and maintained, and if smoke
reaches the Alarms. They arenot foolproof.
Smoke alarms may not waken all individuals.Practice the escape plan
atleast twice a year, making sure that everyone is involved – from kids to
grandparents. Allow childrento master fireescape planning and practice
before holding a fire drill at night when they are sleeping. If children or others
donot readily waken to the sound of the smoke alarm, or if there are infants
or family members with mobility limitations, make sure that someone is
assigned to assist them in fire drill and in the event of an emergency. It is
recommended that you hold a firedrill while family members aresleeping in
order to determine their response to the sound of the smoke alarm while
sleeping and to determine whether they may need assistance in the event
ofan emergency.
Smoke Alarms cannot work without power.Battery operated units cannot
work if the batteries are missing, disconnected or dead, if the wrong type
ofbatteries are used, or if the batteries are not installed correctly. AC units
cannot work if the AC power is cut offfor any reason (open fuse or circuit
breaker,failurealong a power line or at a power station, electrical firethat
burns the electrical wires, etc.). If you are concerned about the limitations
ofbattery or AC power, install both types of units.
Smoke Alarms cannot detect firesif the smoke does not reach the
Alarms.Smoke from firesin chimneys or walls, on roofs, or on the other side
ofclosed doors may not reach the sensing chamber and set off the Alarm.
That is why one unit should be installed inside each bedroom or sleeping
area—especially if bedroom or sleeping area doors are closed at night—and
inthe hallway between them.
Smoke Alarms may not detect fireon another floor or areaof the
dwelling.For example, a stand-alone unit on the second floor may not detect
smoke from a basement fire until the fire spreads. This may not give you
enough time to escape safely.That is why recommended minimum protection
isat least one unit in every sleeping area, and every bedroom on every level
ofyour dwelling. Even with a unit on every floor, stand-alone units may not
provide as much protection as interconnected units, especially if the fire starts
inaremote area. Some safety experts recommend installing interconnected
ACpowered units with battery back-up (see “About Smoke Alarms”) or
professional fire detection systems, so if one unit senses smoke, all units
alarm. Interconnected units may provide earlier warning than stand-alone
units since all units alarm when one detects smoke.
Smoke Alarms may not be heard.Though the alarm horn in this unit meets
orexceeds current standards, it may not be heard if: 1) the unit is located
outside a closed or partially closed door, 2) residents recently consumed
alcohol or drugs, 3) the Alarm is drowned out by noise from stereo, TV, traffic,
air conditioner or other appliances, 4) residents are hearing impaired or sound
sleepers. Special purpose units, like those with visual and audible alarms,
should be installed for hearing impaired residents.
Smoke Alarms may not have time to alarm beforethe fireitself causes
damage, injury, or death, since smoke from some fires may not reach
the unit immediately.Examples of this include persons smoking in bed,
children playing with matches, or fires caused by violent explosions
resulting from escaping gas.
Smoke Alarms are not foolproof.Like any electronic device, Smoke Alarms
are made of components that can wear out or fail at any time. You must test
the unit weekly to ensureyour continued protection. Smoke Alarms cannot
prevent or extinguish fires. They are not a substitute for property or life
insurance.
Smoke Alarms have a limited life.The unit should be replaced immediately
if it is not operating properly. You should always replace a Smoke Alarm after
10 years from date of purchase. Write the purchase date on the space provided
on back of unit.
USING THE SILENCE FEATURE
TheSilence Featurecan temporarily quiet an unwanted alarm for up to 15
minutes.
The Silence Feature does not disable the unit—it makes it temporarily
less sensitive to smoke. For your safety, if smoke aroundtheunitisdense
enough to suggest a potentially dangerous situation, the unit will stay in
alarm or may re-alarm quickly. If you do not know the source of the
smoke, do not assume it is an unwanted alarm. Not responding to an
alarm can result in property loss, injury, or death.
Tosilence Smoke Alarms in an interconnected series:
1.To silence multiple alarms in an interconnected series, you must press the
Test/Silence button on the unit(s) that triggered the alarm.
2.Once you activate the Silence feature,the Red LED will flash approximately
once every 10 seconds.
3.Pressing the Test/Silence button when in silence will restart the silence
timer.
TheSilence Feature on these units can temporarily quiet an unwanted alarm for
up to 15 minutes. Touse this feature, press the Test/Silence button on the cover.
Ifthe unit will not silence and no heavy smoke is present, or if it stays in
silence mode continuously,it should be replaced immediately.
Model 3120B
with Battery Back-Up and Silence
ACPowered
Photo & Ion Smoke Alarm
Input: 120V AC ~,60Hz, 0.07A
Make sure the Alarm is not receiving excessively noisy power. Examples of noisy power could be major appliances on the same circuit, power from a
generator or solar power, light dimmer on the same circuit or mounted near fluorescent lighting. Excessively noisy power may cause damage to your
Alarm.
Low BatteryAlarm “chirp’’ approx.
once/minute
Alarm “chirp’’ approx.
once/minute
Low Battery LatchGreen LED flashing 2
seconds on,
2seconds off
Not available
LISTEDTO
UL 217
STANDARD
AGENCY PLACEMENT RECOMMENDATIONS
NFPA 72 (National Fire Code) Chapter 11
“For your information, the National Fire Protection Association's Standard 72,
reads as follows:”
“11.5.1 One- and Two-Family Dwelling Units.”
“11.5.1.1 Smoke Detection.Where required by applicable laws, codes, or
standards for the specified occupancy, approved single- and multiple-station
Smoke Alarms shall be installed as follows: (1) In all sleeping rooms.
Exception: Smoke Alarms shall not be requiredin sleeping rooms in existing
one- and two-family dwelling units. (2) Outside of each separate sleeping area,
inimmediate vicinity of the sleeping rooms. (3) On each level of the dwelling
unit, including basements. Exception: In existing one- and two family dwelling
units, approved Smoke Alarms powered by batteries are permitted.”
“A.11.8.3 Are More Smoke Alarms Desirable? The required number of
Smoke Alarms might not provide reliable early warning protection for those
areas separated by a door fromthe areas protected by the required Smoke
Alarms. For this reason, it is recommended that the householder consider
the use of additional Smoke Alarms for those areas for increased protection.
The additional areas include the basement, bedrooms, dining room, furnace
room, utility room, and hallways not protected by the required Smoke Alarms.
The installation of Smoke Alarms in kitchens, unfinished attics, or garages
is not normally recommended, as these locations occasionally experience
conditions that can result in improper operation.”
California State Fire Marshal (CSFM)
Early warning detection is best achieved by the installation of firedetection
equipment in all rooms and areas of the household as follows: A Smoke Alarm
installed in each separate sleeping area (in the vicinity, but outside bedrooms),
andHeat or Smoke Alarms in the living rooms, dining rooms, bedrooms,
kitchens, hallways, finished attics, furnace rooms, closets, utility and storage
rooms, basements, and attached garages.
LOCATIONS TO AVOID FOR SMOKE ALARMS
For best performance, AVOID installing Smoke Alarms in these areas:
•Wherecombustion particles are produced. Combustion particles form
when something burns. Areas to avoid include poorly ventilated kitchens,
garages, and furnace rooms. Keep units at least 20 feet (6 meters) from
the sources of combustion particles (stove, furnace, water heater,space
heater) if possible. In areas where a 20-foot distance is not possible – in
modular, mobile, or smaller homes, for example – it is recommended
the Smoke Alarm be placed as far from these fuel-burning sources as
possible. The placement recommendations areintended to keep these
Alarms at a reasonable distance from a fuel-burning source, and thus
reduce “unwanted” alarms. Unwanted alarms can occur if a Smoke
Alarm is placed directly next to a fuel-burning source. Ventilate these
areas as much as possible.
•In air streams near kitchens. Air currents can draw cooking smoke into
the sensing chamber of a Smoke Alarm near the kitchen.
•In very damp, humid or steamy areas, or directly near bathrooms with
showers. Keep units at least 10 feet (3 meters) away from showers,
saunas, dishwashers, etc.
•Where the temperatures are regularly below 40˚ F (4.4˚ C) or above
100˚ F (37.8˚ C) including unheated buildings, outdoor rooms, porches,
or unfinished attics or basements.
•In very dusty, dirty, or greasy areas. Do not install a Smoke Alarm directly
over the stove or range. Clean a laundry room unit frequently to keep it
free of dust or lint.
•Near fresh air vents, ceiling fans, or in very drafty areas. Drafts can blow
smoke away from the unit, preventing it from reaching sensing chamber.
•In insect infested areas. Insects can clog openings to the sensing chamber
and cause unwanted alarms.
•Less than 12 inches (305 mm) away from fluorescent lights. Electrical
“noise” can interferewith the sensor.
•In “dead air” spaces. “Dead air” spaces may prevent smoke from reaching
the Smoke Alarm.
AVOIDING DEAD AIR SPACES
“Dead air” spaces may prevent smoke from reaching the Smoke Alarm. To
avoid dead air spaces, follow the installation recommendations below.
On ceilings,install Smoke Alarms as close to the center of the ceiling as
possible. If this is not possible, install the Smoke Alarm at least 4 inches
(102 mm) from the wall or corner.
For wall mounting(if allowed by building codes), the top edge of Smoke
Alarms should be placed between 4 inches (102 mm) and 12 inches (305 mm)
from the wall/ceiling line, below typical “dead air” spaces.
On a peaked, gabled, or cathedral ceiling,install the first Smoke Alarm
within 3 feet (0.9 meters) of the peak of the ceiling, measured horizontally.
Additional Smoke Alarms may be required depending on the length, angle,
etc. of the ceiling's slope. Refer to NFPA 72 for details on requirements for
sloped or peaked ceilings.
SPECIAL COMPLIANCE CONSIDERATIONS
This Smoke Alarm alone is not a suitable substitute for complete fire
detection systems in places housing many people—like apartment
Alarm ModelsHD6135F and HD6135FB; BRK®Auxiliary Devices Models
RM3 and RM4 (Relay Modules), SL177 (Strobe Light).
See www.brkelectronics.com for most current interconnect list.
Interconnected units must meet ALL of the following requirements:
•Amaximum of 18 compatible units may be interconnected
(Maximum of 12 Smoke Alarms).
•The same fuse or circuit breaker must power all interconnected units.
•The total length of wire interconnecting the units should be less than
1000 feet (300 meters). This type of wire is commonly available at
Hardware and Electrical Supply stores.
•
All wiring must conform to all local electrical codes and NFPA 70 (NEC).
Refer to NFPA72, NFPA101, and/or your local building code for further
connection requirements.
HOW TO INSTALL THIS SMOKE ALARM
THE PARTS OF THIS SMOKE ALARM
This Smoke Alarm is designed to be mounted on any standard wiring junction box up to a 4-inch (10 cm) size, on either the ceiling or wall (if allowed by local codes).
Read “Recommended Locations For Smoke Alarms” and “Locations to Avoid For Smoke Alarms” before you begin installation.
Tools you will need: • Needle-nose pliers or utility knife•Standard Flathead screwdriver.
FOLLOWTHESEINSTALLATION STEPS
STAND-ALONE ALARM ONLY:
•Connect the white wire on the power connector to the neutral wire in
the junction box.
•Connect the black wire on the power connector to the hot wire in the
junction box.
•Tuck the orange wire inside the junction box. It is used for interconnect
only.
INTERCONNECTED UNITS ONLY:
Strip off about 1/2” (12 mm) of the plastic coating on the orange wire
onthe power connector.
•Connect the white wire on the power connector to the neutral wire in
the junction box.
•Connect the black wire on the power connector to the hot wire in the
junction box.
•
Connect the orange wireon the power connector to the interconnect
wirein the junction box. Repeat for each unit you areinterconnecting.
Never connect the hot or neutral wires in the junction box to the orange
interconnect wire. Never cross hot and neutral wires between Alarms.
STAND-ALONE ALARM ONLY:
•If you are only installing one Smoke Alarm, restore power to the
junction box.
INTERCONNECTED UNITS ONLY:
•If you areinterconnecting multiple Smoke Alarms, repeat steps
1-5 for each Smoke Alarm in the series. When you are finished,
restore power to the junction box.
#
}
)
}
*
&
%
$
!
!
""#
A.Unswitched 120VAC
60Hz source
B.Toadditional units; Maximum = 18 total
(Maximum 12 Smoke Alarms)
1. Smoke Alarm
2. Ceiling or Wall
3.Power Connector
4. Wire Nut
5. Junction Box
6.Neutral Wire (Wht)
7. Interconnect Wire
(Orange)
8.Hot Wire(Blk)
4
OPTIONAL LOCKING FEATURES
The locking features are designed to discourage unauthorized removal of the batteries or Alarm. It is not necessary to activate the locks in single-family
households where unauthorized battery or Alarm removal is not a concern.
These Smoke Alarms have two separate locking features: one to lock the battery compartment, and the other to lock the Smoke Alarm
to the mounting bracket. You can choose to use either feature independently, or use them both.
Tools you will need:•Needle-nose pliers or utility knife • Standard Flathead screwdriver.
Both locking features use locking pins, which are molded into the mounting bracket. Using needle-nose pliers or a utility knife, remove
one or both pins from the mounting bracket, depending on how many locking features you want to use.
To permanently remove either lock, insert a flathead screwdriver between the locking pin and the lock, and pry the pin out of the lock.
TO LOCK THE BATTERY COMPARTMENT
Do not lock the battery compartment until you have installed the
batteries and tested the battery back-up.
1.Push and hold Test button until the alarm sounds: 3 beeps, pause,
3beeps, pause. LED flashes once every second.
If the unit does not alarm during testing, DO NOT lock the battery
compartment! Install new batteries and test again. If the Smoke
Alarm still does not alarm, replace it immediately.
2.Using needle-nose pliers or a utility knife, detach one locking pin
from the mounting bracket.
3.Push the locking pin through the hole near the battery drawer on the
back of the Smoke Alarm.
TO UNLOCK THE BATTERY COMPARTMENT
Once the Smoke Alarm is installed, you must disconnect it from the AC power
beforeunlocking the battery compartment.
ELECTRICAL SHOCK HAZARD. Turnoffthe power to the area wherethe
Smoke Alarm is installed before removing it from the mounting bracket.
Failure to turn off the power first may result in serious electrical shock,
injury or death.
Always discharge the branch circuit before servicing an AC or AC/DC
Smoke Alarm. First, turn off the AC power at the circuit breaker or fuse box.
Next, remove the batteries from Smoke Alarms with battery back-up.
Finally,press and hold the Test/Silence button for 5-10 seconds to
discharge the branch circuit.
1.Remove the Smoke Alarm from the mounting
bracket. If the unit is locked to the bracket, see
the section “To Unlock the Mounting Bracket.”
2.Disconnect the power connector by gently prying
it away from the back of the Smoke Alarm.
3.Insert a flathead screwdriver under the head
of the locking pin, and gently pry it out of the
battery compartment lock. (If you plan to relock
the battery compartment, save the locking pin.)
4.To relock the battery compartment, close the
battery door and reinsert locking pin in lock.
5.Reconnect the power connector to the back of the Smoke Alarm, reattach
the Smoke Alarm to the mounting bracket, and restore the power.
When replacing the batteries, always test the Smoke Alarm before relocking
the battery compartment.
TO UNLOCK THE MOUNTING BRACKET
ELECTRICAL SHOCK HAZARD. Turn off the power to the area where the
Smoke Alarm is installed beforeremoving it from the mounting bracket.
Failure to turn off the power first may result in serious electrical shock,
injury or death.
Always discharge the branch circuit before servicing an AC or AC/DC
Smoke Alarm. First, turnoffthe AC power at the circuit breaker or fuse
box. Next, remove the batteries from Smoke Alarms with battery back-up.
Finally, press and hold the Test/Silence button for 5-10 seconds to
discharge the branch circuit.
1.Insert a flathead screwdriver between the
mounting bracket pin and the mounting bracket.
2.Pry the Smoke Alarm away from the bracket by
turning both the screwdriver and the Smoke
Alarm counterclockwise (left) at the same time.
TO LOCK THE MOUNTING BRACKET
1.Using needle-nose pliers, detach one locking pin from mounting bracket.
2.Insert the locking pin into the lock located
opposite from the battery drawer as shown
in the diagram.
3.When you attach the Smoke Alarm to the mounting bracket, the locking
pin’s head will fit into a notch on the bracket.
Locking Features (Continued)
Printed in Mexico M08-0224-000 Q11/10
First Alert®is a registered trademark of the First Alert Trust.
BRK®is a registered trademark of BRK Brands, Inc.
WEEKLY TESTING
•NEVER use an open flame of any kind to test this unit. You might
accidentally damage or set fire to the unit or to your home. The built-
in test switch accurately tests the unit’s operation as required by
Underwriters Laboratories, Inc. (UL).
•If the Alarm ever fails to test properly, replace it immediately.
Products under warranty may be returned to the manufacturer
for replacement. See “Limited Warranty” at the end of this manual.
DONOT stand close to the Alarm when the horn is sounding. Exposure
atclose range may be harmful to your hearing. When testing, step away
when hornstarts sounding.
Itis important to test this unit every week to make
sure it is working properly. Using the test button is the
recommended way to test this Smoke Alarm.
Press and holdthe Test/Silence button on the cover of the
unit until the alarm sounds (the unit may continue to alarm
for a few seconds after you release the button). If it does
not alarm, make surethe unit is receiving power and test
it again. If it still does not alarm, replace it immediately.
During testing, you will hear a loud, repeating horn pattern: 3 beeps,
pause, 3 beeps, pause. LED flashes once every second.
When testing a series of interconnected units you must test each unit
individually.Make sure all units alarm when each one is tested.
REGULAR MAINTENANCE
Use only the replacement batteries listed below. The unit may not
operate properly with other batteries. Never use rechargeable batteries
since they may not provide a constant charge.
This unit has been designed to be as maintenance-free as possible, but there
areafew simple things you must do to keep it working properly:
•Test it at least once a week.
•Clean the Smoke Alarm at least once a month; gently vacuum the
outside of the Smoke Alarm using your household vacuum’s soft brush
attachment. Test the Smoke Alarm. Never use water, cleaners or solvents
since they may damage the unit.
•If the Smoke Alarm becomes contaminated by excessive dirt, dust and/or
grime, and cannot be cleaned to avoid unwanted alarms, replace the
unit immediately.
•Relocate the unit if it sounds frequent unwanted alarms. See “Locations
ToAvoid For Smoke Alarms” for details.
•When the battery back-up becomes weak, the Smoke Alarm will “chirp”
about once a minute (the low battery warning). This warning should last 7
days, but you should replace the batteries immediately to continue your
protection.
UNDERSTANDING THE INDICATOR LIGHTS
AND ALARM HORN PATTERNS
NOTE: When power is applied, unit(s) may alarm momentarily.
*When any Smoke Alarm in an interconnected series triggers an alarm, its
red LED will flash rapidly. The red LEDs will remain OFF on any remaining
alarms in the series. This feature helps responders identify which unit(s)
triggered the alarm.
Latching AlarmRed LED flashing 2
seconds on,
2seconds off
Not available
AC Power
DC Power
Normal OperationConstant Green LED
No Audible Alarm
Flashing Green LED
once/minute
NoAudible Alarm
Test ConditionRapidly Flashing
Red LED
Audible Alarm
Rapidly Flashing
Red LED
Audible Alarm
Silence ModeRapidly Flashing
Red LED
Audible Alarm Off
Rapidly Flashing
Red LED
Audible Alarm Off
Alarm Condition*
(Initiating Unit)
Rapidly Flashing
Red LED
Audible Alarm
Rapidly Flashing
Red LED
Audible Alarm
Alarm Condition*
(Remote Units)
Constant Green LED
Audible Alarm
Green LED Off
Audible Alarm
IFTHIS SMOKE ALARM SOUNDS
RESPONDING TO AN ALARM
During an alarm, you will hear a loud, repeating horn pattern: 3 beeps,
pause, 3 beeps, pause.
•Ifthe unit alarms and you are not testing the unit, it is warning you of a
potentially dangerous situation that requires your immediate attention.
NEVER ignore any alarm. Ignoring the alarm may result in injury or
death.
•Never disconnect the AC power to quiet an unwanted alarm.
Disconnecting the power disables the Alarm so it cannot sense
smoke. This will remove your protection. Instead, open a window or
fan the smoke away from the unit. The Alarm will reset automatically.
•If the unit alarms get everyone out of the house immediately.
•
ELECTRICAL SHOCK HAZARD: Attempting to disconnect the power
connector from the unit when the power is on may result in electrical
shock, serious injury or death.
When an interconnected system of AC powered units is in alarm, the alarm
indicator light on the unit(s) that initiated the alarm will blink rapidly. It will
remain OFF on any remaining units.
If the unit alarms, get everyone out of the dwelling immediately.
Ifthe unit alarms and you are certain that the source of smoke is not a fire—
cooking smoke or an extremely dusty furnace, for example—open a nearby
window or door and fan the smoke away from the unit (Use the Silence Feature
tosilence the Alarm). This will silence the alarm, and once the smoke clears the
unit will reset itself automatically.
WHAT TO DO IN CASE OF FIRE
•Don’t panic; stay calm. Follow your family escape plan.
•Get out of the house as quickly as possible. Don’t stop to
get dressed or collect anything.
•Feel doors with the back of your hand before opening them.
Ifadoor is cool, open it slowly. Don’t open a hot door. Keep doors
and windows closed, unless you must escape through them.
•Cover your nose and mouth with a cloth (preferably damp).
Take short, shallow breaths.
•Meet at your planned meeting place outside your home,
and do a head count to make sure everybody got out safely.
•Call the Fire Department as soon as possible from outside.
Give your address, then your name.
•Never go back inside a burning building for any reason.
•Contact your Fire Department for ideas on making your home safer.
Alarms have various limitations. See "Limitations of Smoke Alarms" for
details.
IF YOU SUSPECT A PROBLEM
Smoke Alarms may not operate properly because of dead, missing or weak
batteries, a build-up of dirt, dust or grease on the Smoke Alarm cover, or
installation in an improper location. Clean the Smoke Alarm as described in
“Regular Maintenance,” and install fresh batteries, then test the Smoke Alarm
again. If it fails to test properly when you use the test button, or if the problem
persists, replace the Smoke Alarm immediately.
•If you hear a “chirp” approximately once a minute, replace the
batteries.
•If you experience frequent non-emergency alarms (like those caused
by cooking smoke), try relocating the Smoke Alarm.
•If the alarm sounds when no smoke is visible, try cleaning or
relocating the Smoke Alarm. The cover may be dirty.
•If the alarm does not sound during testing, make sure it is receiving
ACpower from the household current.
Always discharge the branch circuit before servicing an AC or AC/DC
Smoke Alarm. First, turnoffthe AC power at the circuit breaker or fuse
box. Next, remove the batteries from Smoke Alarms with battery back-up.
Finally, press and hold the test button for 5-10 seconds to discharge the
branch circuit.
If the Smoke Alarm is still not operating properly, and it is still under warranty,
please see “How to Obtain Warranty Service” in the Limited Warranty.
Do not try fixing the alarm yourself – this will void your warranty!
LIMITED WARRANTY
BRK Brands, Inc., ("BRK") the maker of First Alert®brand and BRK®brand
products, warrants that for a period of ten years from the date of purchase,
this product will be free from defects in material and workmanship.
BRK, at its option, will repair or replace this product or any component of
the product found to be defective during the warranty period. Replacement
will be made with a new or remanufactured product or component. If the
product is no longer available, replacement may be made with a similar
product of equal or greater value. This is your exclusive warranty.
This warranty is valid for the original retail purchaser from the date of initial
retail purchase and is not transferable. Keep the original sales receipt.
Proof of purchase is required to obtain warranty performance.
BRK dealers, service centers, or retail stores selling BRK products do not
have the right to alter, modify or any way change the terms and conditions
of this warranty.
This warranty does not cover normal wear of parts or damage resulting
from any of the following: negligent use or misuse of the product, use on
improper voltage or current, use contrary to the operating instructions,
disassembly,repair or alteration by anyone other than BRK or an authorized
service center. Further, the warranty does not cover Acts of God, such as
fire, flood, hurricanes and tornadoes or any batteries that are included with
this unit.
BRK shall not be liable for any incidental or consequential damages
caused by the breach of any express or implied warranty.Except to the
extent prohibited by applicable law, any implied warranty of merchantability
or fitness for a particular purpose is limited in duration to the duration of
the above warranty.Some states, provinces or jurisdictions do not allow
the exclusion or limitation of incidental or consequential damages or
limitations on how long an implied warranty lasts, so the above limitations
or exclusion may not apply to you. This warranty gives you specific legal
rights, and you may also have other rights that vary from state to state or
province to province.
How to Obtain Warranty Service
Service: If service is required, do not return the product to your retailer.
In order to obtain warranty service, contact the Consumer Affairs Division
at 1-800-323-9005, 7:30 AM - 5:00 PM Central Standard Time, Monday
through Friday. To assist us in serving you, please have the model number
and date of purchase available when calling.
For Warranty Service return to:
BRK Brands, Inc., 25 Spur Drive, El Paso, TX 79906
Battery:BRK Brands, Inc. make no warranty,express or implied, written or
oral, including that of merchantability or fitness for any particular purpose
with respect to battery.
RECOMMENDED LOCATIONS FOR
SMOKE ALARMS
Installing Smoke Alarms in Single-Family Residences
The National Fire Protection Association (NFPA), recommends one Smoke
Alarm on every floor, in every sleeping area, and in every bedroom. In new
construction, the Smoke Alarms must be AC powered and interconnected.
See “Agency Placement Recommendations” for details. For additional cover-
age, it is recommended that you install a Smoke Alarm in all rooms, halls,
storage areas, finished attics, and basements, where temperatures normally
remain between 40˚ F (4.4˚ C) and 100˚ F (37.8˚ C). Make sure no door or
other obstruction could keep smoke from reaching the Smoke Alarms.
More specifically, install Smoke Alarms:
•On every level of your home, including finished attics and basements.
•Inside every bedroom, especially if people sleep with the door partly or
completely closed.
•In the hall near every sleeping area. If your home has multiple sleeping
areas, install a unit in each. If a hall is more than 40 feet long (12 meters),
install a unit at each end.
•At the top of the first-to-second floor stairway, and at the bottom
of the basement stairway.
Specific requirements for Smoke Alarm installation vary from state to state
and from region to region. Check with your local Fire Department for current
requirements in your area. Itis recommended AC or AC/DC units be inter-
connected for added protection.
INSTALLING SMOKE ALARMS IN MOBILE HOMES & RVS
For minimum security install one Smoke Alarm as close to each sleeping area
as possible. For more security, put one unit in each room. Many older mobile
homes (especially those built before 1978) have little or no insulation. If your
mobile home is not well insulated, or if you are unsure of the amount of
insulation, it is important to install units on inside walls only. Smoke Alarms
should be installed where temperatures normally remain between 40˚ F (4.4˚ C)
and 100˚ F (37.8˚ C).
WARNING: Test units used in RVs after the vehicle has been in storage,
before every trip, and once a week while in use. Failure to test units
used in RVs as described may remove your protection.
LIMITATIONS OF SMOKE ALARMS
Smoke Alarms have played a key role in reducing deaths resulting from home
fires worldwide. However, like any warning device, Smoke Alarms can only
work if they are properly located, installed, and maintained, and if smoke
reaches the Alarms. They arenot foolproof.
Smoke alarms may not waken all individuals.Practice the escape plan
atleast twice a year, making sure that everyone is involved – from kids to
grandparents. Allow childrento master fireescape planning and practice
before holding a fire drill at night when they are sleeping. If children or others
donot readily waken to the sound of the smoke alarm, or if there are infants
or family members with mobility limitations, make sure that someone is
assigned to assist them in fire drill and in the event of an emergency. It is
recommended that you hold a firedrill while family members aresleeping in
order to determine their response to the sound of the smoke alarm while
sleeping and to determine whether they may need assistance in the event
ofan emergency.
Smoke Alarms cannot work without power.Battery operated units cannot
work if the batteries are missing, disconnected or dead, if the wrong type
ofbatteries are used, or if the batteries are not installed correctly. AC units
cannot work if the AC power is cut offfor any reason (open fuse or circuit
breaker,failurealong a power line or at a power station, electrical firethat
burns the electrical wires, etc.). If you are concerned about the limitations
ofbattery or AC power, install both types of units.
Smoke Alarms cannot detect firesif the smoke does not reach the
Alarms.Smoke from firesin chimneys or walls, on roofs, or on the other side
ofclosed doors may not reach the sensing chamber and set off the Alarm.
That is why one unit should be installed inside each bedroom or sleeping
area—especially if bedroom or sleeping area doors are closed at night—and
inthe hallway between them.
Smoke Alarms may not detect fireon another floor or areaof the
dwelling.For example, a stand-alone unit on the second floor may not detect
smoke from a basement fire until the fire spreads. This may not give you
enough time to escape safely.That is why recommended minimum protection
isat least one unit in every sleeping area, and every bedroom on every level
ofyour dwelling. Even with a unit on every floor, stand-alone units may not
provide as much protection as interconnected units, especially if the fire starts
inaremote area. Some safety experts recommend installing interconnected
ACpowered units with battery back-up (see “About Smoke Alarms”) or
professional fire detection systems, so if one unit senses smoke, all units
alarm. Interconnected units may provide earlier warning than stand-alone
units since all units alarm when one detects smoke.
Smoke Alarms may not be heard.Though the alarm horn in this unit meets
orexceeds current standards, it may not be heard if: 1) the unit is located
outside a closed or partially closed door, 2) residents recently consumed
alcohol or drugs, 3) the Alarm is drowned out by noise from stereo, TV, traffic,
air conditioner or other appliances, 4) residents are hearing impaired or sound
sleepers. Special purpose units, like those with visual and audible alarms,
should be installed for hearing impaired residents.
Smoke Alarms may not have time to alarm beforethe fireitself causes
damage, injury, or death, since smoke from some fires may not reach
the unit immediately.Examples of this include persons smoking in bed,
children playing with matches, or fires caused by violent explosions
resulting from escaping gas.
Smoke Alarms are not foolproof.Like any electronic device, Smoke Alarms
are made of components that can wear out or fail at any time. You must test
the unit weekly to ensureyour continued protection. Smoke Alarms cannot
prevent or extinguish fires. They are not a substitute for property or life
insurance.
Smoke Alarms have a limited life.The unit should be replaced immediately
if it is not operating properly. You should always replace a Smoke Alarm after
10 years from date of purchase. Write the purchase date on the space provided
on back of unit.
USING THE SILENCE FEATURE
TheSilence Featurecan temporarily quiet an unwanted alarm for up to 15
minutes.
The Silence Feature does not disable the unit—it makes it temporarily
less sensitive to smoke. For your safety, if smoke aroundtheunitisdense
enough to suggest a potentially dangerous situation, the unit will stay in
alarm or may re-alarm quickly. If you do not know the source of the
smoke, do not assume it is an unwanted alarm. Not responding to an
alarm can result in property loss, injury, or death.
Tosilence Smoke Alarms in an interconnected series:
1.To silence multiple alarms in an interconnected series, you must press the
Test/Silence button on the unit(s) that triggered the alarm.
2.Once you activate the Silence feature,the Red LED will flash approximately
once every 10 seconds.
3.Pressing the Test/Silence button when in silence will restart the silence
timer.
TheSilence Feature on these units can temporarily quiet an unwanted alarm for
up to 15 minutes. Touse this feature, press the Test/Silence button on the cover.
Ifthe unit will not silence and no heavy smoke is present, or if it stays in
silence mode continuously,it should be replaced immediately.
Model 3120B
with Battery Back-Up and Silence
ACPowered
Photo & Ion Smoke Alarm
Input: 120V AC ~,60Hz, 0.07A
Make sure the Alarm is not receiving excessively noisy power. Examples of noisy power could be major appliances on the same circuit, power from a
generator or solar power, light dimmer on the same circuit or mounted near fluorescent lighting. Excessively noisy power may cause damage to your
Alarm.
Low BatteryAlarm “chirp’’ approx.
once/minute
Alarm “chirp’’ approx.
once/minute
Low Battery LatchGreen LED flashing 2
seconds on,
2seconds off
Not available
LISTEDTO
UL 217
STANDARD
AGENCY PLACEMENT RECOMMENDATIONS
NFPA 72 (National Fire Code) Chapter 11
“For your information, the National Fire Protection Association's Standard 72,
reads as follows:”
“11.5.1 One- and Two-Family Dwelling Units.”
“11.5.1.1 Smoke Detection.Where required by applicable laws, codes, or
standards for the specified occupancy, approved single- and multiple-station
Smoke Alarms shall be installed as follows: (1) In all sleeping rooms.
Exception: Smoke Alarms shall not be requiredin sleeping rooms in existing
one- and two-family dwelling units. (2) Outside of each separate sleeping area,
inimmediate vicinity of the sleeping rooms. (3) On each level of the dwelling
unit, including basements. Exception: In existing one- and two family dwelling
units, approved Smoke Alarms powered by batteries are permitted.”
“A.11.8.3 Are More Smoke Alarms Desirable? The required number of
Smoke Alarms might not provide reliable early warning protection for those
areas separated by a door fromthe areas protected by the required Smoke
Alarms. For this reason, it is recommended that the householder consider
the use of additional Smoke Alarms for those areas for increased protection.
The additional areas include the basement, bedrooms, dining room, furnace
room, utility room, and hallways not protected by the required Smoke Alarms.
The installation of Smoke Alarms in kitchens, unfinished attics, or garages
is not normally recommended, as these locations occasionally experience
conditions that can result in improper operation.”
California State Fire Marshal (CSFM)
Early warning detection is best achieved by the installation of firedetection
equipment in all rooms and areas of the household as follows: A Smoke Alarm
installed in each separate sleeping area (in the vicinity, but outside bedrooms),
andHeat or Smoke Alarms in the living rooms, dining rooms, bedrooms,
kitchens, hallways, finished attics, furnace rooms, closets, utility and storage
rooms, basements, and attached garages.
LOCATIONS TO AVOID FOR SMOKE ALARMS
For best performance, AVOID installing Smoke Alarms in these areas:
•Wherecombustion particles are produced. Combustion particles form
when something burns. Areas to avoid include poorly ventilated kitchens,
garages, and furnace rooms. Keep units at least 20 feet (6 meters) from
the sources of combustion particles (stove, furnace, water heater,space
heater) if possible. In areas where a 20-foot distance is not possible – in
modular, mobile, or smaller homes, for example – it is recommended
the Smoke Alarm be placed as far from these fuel-burning sources as
possible. The placement recommendations areintended to keep these
Alarms at a reasonable distance from a fuel-burning source, and thus
reduce “unwanted” alarms. Unwanted alarms can occur if a Smoke
Alarm is placed directly next to a fuel-burning source. Ventilate these
areas as much as possible.
•In air streams near kitchens. Air currents can draw cooking smoke into
the sensing chamber of a Smoke Alarm near the kitchen.
•In very damp, humid or steamy areas, or directly near bathrooms with
showers. Keep units at least 10 feet (3 meters) away from showers,
saunas, dishwashers, etc.
•Where the temperatures are regularly below 40˚ F (4.4˚ C) or above
100˚ F (37.8˚ C) including unheated buildings, outdoor rooms, porches,
or unfinished attics or basements.
•In very dusty, dirty, or greasy areas. Do not install a Smoke Alarm directly
over the stove or range. Clean a laundry room unit frequently to keep it
free of dust or lint.
•Near fresh air vents, ceiling fans, or in very drafty areas. Drafts can blow
smoke away from the unit, preventing it from reaching sensing chamber.
•In insect infested areas. Insects can clog openings to the sensing chamber
and cause unwanted alarms.
•Less than 12 inches (305 mm) away from fluorescent lights. Electrical
“noise” can interferewith the sensor.
•In “dead air” spaces. “Dead air” spaces may prevent smoke from reaching
the Smoke Alarm.
AVOIDING DEAD AIR SPACES
“Dead air” spaces may prevent smoke from reaching the Smoke Alarm. To
avoid dead air spaces, follow the installation recommendations below.
On ceilings,install Smoke Alarms as close to the center of the ceiling as
possible. If this is not possible, install the Smoke Alarm at least 4 inches
(102 mm) from the wall or corner.
For wall mounting(if allowed by building codes), the top edge of Smoke
Alarms should be placed between 4 inches (102 mm) and 12 inches (305 mm)
from the wall/ceiling line, below typical “dead air” spaces.
On a peaked, gabled, or cathedral ceiling,install the first Smoke Alarm
within 3 feet (0.9 meters) of the peak of the ceiling, measured horizontally.
Additional Smoke Alarms may be required depending on the length, angle,
etc. of the ceiling's slope. Refer to NFPA 72 for details on requirements for
sloped or peaked ceilings.
SPECIAL COMPLIANCE CONSIDERATIONS
This Smoke Alarm alone is not a suitable substitute for complete fire
detection systems in places housing many people—like apartment
Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.
Product:
Spelregels forum
Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:
lees eerst de handleiding door;
controleer of uw vraag al eerder door iemand anders is gesteld;
probeer uw vraag zo duidelijk mogelijk te stellen;
heeft u een probleem en al geprobeerd om dit op te lossen, vermeld dit erbij aub;
heeft u een oplossing gekregen van een bezoeker dan horen wij dat graag in dit forum;
wilt u een reactie geven op een vraag of antwoord, gebruik dan niet dit formulier maar klik op de knop 'reageer op deze vraag';
uw vraag wordt direct op de website gezet; vermijd daarom persoonlijke gegevens in te vullen;
Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.
Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.
Abonneren
Abonneer u voor het ontvangen van emails voor uw First Alert 3120B bij:
nieuwe vragen en antwoorden
nieuwe handleidingen
U ontvangt een email met instructies om u voor één of beide opties in te schrijven.
Ontvang uw handleiding per email
Vul uw emailadres in en ontvang de handleiding van First Alert 3120B in de taal/talen: Engels als bijlage per email.
De handleiding is 1.4 mb groot.
U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.
Stel vragen via chat aan uw handleiding
Stel uw vraag over deze PDF
Uw handleiding is per email verstuurd. Controleer uw email
Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.
Er is een email naar u verstuurd om uw inschrijving definitief te maken.
Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken
U heeft geen emailadres opgegeven
Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.
Uw vraag is op deze pagina toegevoegd
Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.