10.3.6 External thermostat/programmable thermostat
If you want to use an external programmable thermostat, connect it to the TERM clamps (connector CN7 pin 7-8).
•
external thermostat: set the stove SET temperature to 7°C.
•
external programmable thermostat: set the stove SET temperature to 7°C and disable the chrono functions from 03-
01 menu.
The stove external thermostat is enabled when the contact is closed with stove on.
10.3.7 Room temperature reaches set value (SET temperature)
When the set room temperature value is reached or the fume temperature has reached the Pr13 value, the stove heat
output is set automatically to the minimum value (MODULATION mode). See figure 20
fig. 20
If the stove is in the STAND-BY mode, it switches off after the period of time set by Pr44 and after reaching the SET
temperature. If the following condition occurs -
T
ambiente >
(T
SET
+ Pr43), it is then possible to switch the stove back
on.
10.3.8 Burn pot cleaning
When the stove is in the working mode, the “BURN POT CLEANING” mode is activated for the period set by Pr12
parameter at the intervals set by Pr03 parameter.
fig. 21
10.3.9 Stove switching off
Hold down P4 button for approx. 2 seconds to switch off the stove. The Auger tube stops immediately and
the exhaust blower reaches its maximum speed value. The FINAL CLEANING phase is performed.
At the end of the period of time set by Pr39, when the fume temperature has reached a value below Pr13 parameter, the
exhaust blower stops.
fig. 22