The display shows “GO-STBY”. At the end of a preset time, the display shows the message “UAITCOOLING”. When the fume temperature reaches the threshold
set by the Pr13 parameter, the stove goes into STAND-BY mode and the message “STOP ECO TEMP GOOD” scrolls on the display. If the boiler temperature falls
below the set temperature minus the threshold given by the preset delta, the stove will restart.
Stove switch off
Hold P3 button down to switch off the stove. The display shows the message “CLEANINGFINAL”.
After a time given by the PR39parameter, if the fume temperature is below the threshold given by the parameter Pr10, the stove switches off, displaying the
message “OFF”.
External thermostat/chrono-thermostat use
If an external room thermostat is to be used, make the connection to the TERM terminals. Set MODE 2 using technical parameters. An external thermostat or an
external chrono-thermostatcan be used. Disable (OFF) the chrono functionality in the stove.
The stove external thermostat is enabled when the contact is closed with stove on.
Summary schematic of the OPERATIONAL MODES
SETTABLE
HEAT
OUTPUT
SETTABLE
TEMPERATURE
H20
SETTABLE ROOM
TEMPERATURE
SETTABLE EXT
THERMOSTATSTAND-BY CONDITIONS FOR
STAND BY
MODE 1
Thermo-stove,
heating water control
YESYESNOYESSettable
Heating water
temperature
reached
MODE 2
Thermo-stove,
heating water control
and external
thermostat
YESYESNOYESSettable
External
thermostat temp
reached
MODE 3
Storage water heater,
domestic water
control
NOYESNONOAlways active
Domestic hot
water temp
satisfied
08.4 ALARMS
In the event that an operating fault occurs, the board intervenes and signals the occurrence of an irregularity, switching onthe alarm LED (alarm LED on) and
emitting acoustic signals.
In case of alarm, the stove is always immediately switched off
EXCEPT FOR THE POWER OUTAGE ALARM, alarm status is reached at the end of the period of time set by the Pr11 parameter and can be cleared by holding
theP3 button down. Whenever an alarm is cleared, the stove starts a switching-off phase for safety reasons. The alarm LED (alarm LED on) will remain on and
the buzzer, if enabled, will sound intermittently during the entire alarm phase. Should the alarm not be cleared, the stove will in any case be switched off and the
alarm message will remain on the display.
AL1 BLAC-OUT – Power outage alarm
Power outage may occur with the stove in working mode. When restarting, if the outage period is less than 20 seconds, the stove restarts in UORKmode, otherwise
an alarm will sound. The display shows the message “AL1 BLAC-OUT” and the stove switches off.
AL2 SMOKE PROBE ADJUST – Fume temperature probe alarm
The alarm is triggered in case of faulty fume probe. The stove goes into alarm status and the alarm LED illuminates (LED alarm on). The stove will show the wording
“AL2 SMOKE PROBE ADJUST” on the display and will switch off.
AL3 HOT EXHAUST – Fume over-temperature alarm
This occurs if the fume probe detects a temperature greater than a fixed set value that cannot be changed using a parameter. The display shows the message
“AL3 HOT EXHAUST” and the stove switches off.
AL4 FAN FAILURE – Fume encoder fault alarm
The alarm is triggered in the event of an exhaust blower fault. The stove will go into alarm status and the message “AL4 FAN FAILURE” will appear on the display.
AL5 NO LIGHTIN- – Ignition fault alarm
The alarm is triggered in the event of ignition phase fault. This occurs if, after a time given by parameter Pr11, the fume temperature does not exceed parameter
Pr13. The display shows “AL5 NO LIGHTIN-” and the stove goes into alarm status.
AL6 NO PELLET – No pellets alarm
This occurs when the fume temperature falls below parameter Pr13 during operation. The display shows “AL6 NO PELLET” and the stove goes into alarm status.
The alarm is triggered whenever the general safety thermostat detects a temperature exceeding the trigger threshold. The thermostat trips and switches off the
auger as it is placed in series with its power supply, and the controller trips by signalling alarm status (alarm LED on), showing “AL7 SAFETY THERMAL” on the
display, and the stove switches off.
AL8 FAILURE DEPRESS – No negative pressure alarm
This occurs when the external component (pressure switch) detects a pressure above the trigger threshold. The pressure switchintervenes by switching off the
auger, being electrically connected in series, and the controller signals alarm status (alarm LED on) showing “AL8 FAILURE DEPRESS” on the display. The stove
Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.
Product:
Spelregels forum
Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:
lees eerst de handleiding door;
controleer of uw vraag al eerder door iemand anders is gesteld;
probeer uw vraag zo duidelijk mogelijk te stellen;
heeft u een probleem en al geprobeerd om dit op te lossen, vermeld dit erbij aub;
heeft u een oplossing gekregen van een bezoeker dan horen wij dat graag in dit forum;
wilt u een reactie geven op een vraag of antwoord, gebruik dan niet dit formulier maar klik op de knop 'reageer op deze vraag';
uw vraag wordt direct op de website gezet; vermijd daarom persoonlijke gegevens in te vullen;
Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.
Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.
Abonneren
Abonneer u voor het ontvangen van emails voor uw Eva Calor SB 80 bij:
nieuwe vragen en antwoorden
nieuwe handleidingen
U ontvangt een email met instructies om u voor één of beide opties in te schrijven.
Ontvang uw handleiding per email
Vul uw emailadres in en ontvang de handleiding van Eva Calor SB 80 in de taal/talen: Engels als bijlage per email.
De handleiding is 2.55 mb groot.
U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.
Uw handleiding is per email verstuurd. Controleer uw email
Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.
Er is een email naar u verstuurd om uw inschrijving definitief te maken.
Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken
U heeft geen emailadres opgegeven
Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.
Uw vraag is op deze pagina toegevoegd
Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.