INSTALLATION INSTRUCTIONS
Important warnings
As well as that indicated in the pre-
sent document, bear in mind the UNI
rules:
- n. 10683 - wood heat generators:
installation requirements
- n. 9615/90 - calculation of the
chimney internal dimensions.
In particular:
- before starting any mounting opera-
tion, it is important to verify the
compatibility of the plant as establi-
shed by the UNI 10683 rule in para-
graphs 4.1/ 4.1.1 / 4.1.2.
- once mounted, once mounted, the
installer must “start up” the plant and
issue the documentation requested in
the UNI 10683 rule, respectively in
paragraphs 4.6 and 5.
Before installing the cover, verify the
correct functioning of the connections,
the controls and all moving parts.
The verification must be carried out
with the chimney having been on for a
few hours, before covering the hearth,
in order to eventually intervene.
Therefore, the finishing operations
such as for example:
- manufacture of the false hood
- mounting of covering
- carrying out stripping, painting, etc.
must be carried out once tested with
positive result.
Therefore, Edilkamin does not
answer for burdens deriving from
both demolition and reconstruction
interventions, even if subsequent to
replacing hearth pieces which resul-
ted faulty.
Calibration and start up to be carried
out by the dealer.
Vorwort
The FORTE UP2 hearths must be
installed keeping to the following
instructions, as the safety and plant
efficiency depend on the correct
installation.
Carefully read the present instruc-
tions before mounting.
EDILKAMIN declines any responsi-
bility for eventual damages deriving
from the non compliance with the pre-
sent instructions and, in case, any war-
ranty right will be void.
The FORTE UP2 hearth is supplied
already assembled on non returnable
pallet. The inside covering of the
hearth is supplied already installed.
A model identification label is
applied under the hearth hatch; the
label can be seen until the hearth is
covered. The model identification
number is indicated in the documenta-
tion supplied with the product.
Building protection
All the building surfaces near the
hearth must be protected against over-
heating. The insulating measures to be
adopted depend on the type of surfaces
present and how they are made.
Hot air outlets / Grillsr
The hot air outlets must be placed at a
minimum distance of 50 cm from the
ceiling and 30 cm from the furniture.
Position the grills or the air outlets at
the highest point of the covering, in
order to avoid heat accumulating insi-
de the same covering. Position the
grills or the air outlets so that they can
be easily accessed for cleaning.
Heating insulation
The insulating layers must not have
joints and have to be overlapped. The
thickness of the insulating material
must be of at least 3 cm.
Ornamental beams
The realisation of eventual wood orna-
mental beams in front of the hearth
covering is allowed only if they are
outside the radiation field, at a distan-
ce of at least 1 cm from the same cove-
ring. The air space which isolates the
ornamental elements and the covering
must be such not to accumulate heat.
The wood ornamental beams cannot
be integrating parts of the building.
Floor opposite the hearth
Floors made with fuelling materials
must be protected by a sufficiently
thick, non fuelling cover.
The floor protection must be equal to:
frontally:
- the corresponding height of the fire
surface from the floor plus 30 cm and,
in any case, min. 50 cm
laterally:
- the corresponding height of the fire
surface from the floor plus 20 cm and,
in any case, min. 30 cm.
In the radiation field of the hearth
The structural elements built with
fuelling material or which present
fuelling components and the furniture
must be positioned at a minimum
distance of 80 cm from the hearths
mouth, in all three directions: front,
upper and side.
Should such elements or furniture be
screened by a ventilated anti-radiation
protection, it will be sufficient to
respect a distance of 40 cm.
Outside the radiation field
The structural elements built with
fuelling materials or which present
fuelling components and furniture,
must be positioned at a minimum
distance of 5 cm from the hearths
covering.
In such air space, the air present in the
room must be able to circulate freely.
No heat accumulation must be created.
Electric lines
There must be no electric lines in the
walls and the ceilings, including the
hearth embedding area.
NOTE: The product is supplied with
two anti-corrosion discs (one on the
outside and one on the inside of the
combustion chamber). They must be
removed during unpacking and
disposed of as normal waste.
5

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Edilkamin Forte 2 Up bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Edilkamin Forte 2 Up in de taal/talen: Engels als bijlage per email.

De handleiding is 2.2 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

loading

Andere handleiding(en) van Edilkamin Forte 2 Up

Edilkamin Forte 2 Up Gebruiksaanwijzing en installatiehandleiding - Italiano - 16 pagina's


Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info