Elite Control Operations Manual Programming
L-2230 ENGLISH 9
delay, the system will be restarted. As with all faults, system lockout (sustained shutdown) will occur after the fourth consecutive
LAC fault. See “Failsafe and Fault-Handling Codes” on page 13 for further details on system lockout.
P-7: De-Icing Cycle
The de-icing cycle prevents ice build up on the evaporator coil during extended periods of cooling operation. Installation
variables such as grille sizes, length of ducting, insulation, and ambient temperatures determine the run time required to
achieve set point. Factors that substantially increase run time include operating the system with hatches and doors open and
programming an unrealistic set point (e.g. 65°F/18.3°C). Such situations can cause the evaporator to form ice on warm humid
days.
For software revision A13 and older, de-icing is accomplished by switching the reversing valve into Heat Mode while
the system is cooling. The valve remains energized for the programmed cycle time. The cycle is programmable to
“OFF” or to a period of 1, 2, or 3 minutes.
For software revision A15 and newer, de-icing is accomplished by closely monitoring the room air temperature in 10-
minute intervals during a cooling cycle. Depending on the parameter value and the change in room temperature during
these monitoring intervals, the control performs various actions to prevent ice from forming or to melt ice that has
already formed. This is accomplished by short compressor shutdown periods combined with a one-speed increase in
fan speed and by periodic Heat Mode cycles with the fan turned off.
The parameter setting for the de-icing feature depends on whether you are using the optional alternate air-temperature sensor
or the display’s built-in room air-temperature sensor. Installation of an optional alternate air temperature sensor (located in the
return air path) greatly increases the effectiveness of the de-icing feature, and this option should be considered whenever the
display sensor cannot read the room temperature accurately.
If using an optional alternate air temperature sensor, set this parameter to “1” to turn the de-icing feature on, or to
OFF to disable.
If using the display’s built-in room air temperature sensor, this feature has two selectable behavior modes. Both
modes attempt to compensate for any temperature discrepancy the display sensor experiences. (Although
discrepancy is not typical, installation variables such as where the display is placed inside the room—near an open
door or in direct sunlight—can affect how accurately it reads the actual room temperature.) Set this parameter to “1” to
assume the display sensor may be reading the room temperature as much as 5°F (2.8°C) greater than the actual
evaporator temperature (standard). For more extreme installations, set this parameter to “2” to assume the display
sensor may be reading the room temperature as much as 7°F (3.9°C) greater than the actual evaporator temperature.
The setting of “2” should only be used if a setting of “1” does not prevent evaporator ice from forming.
P-8: Optional Pump Sentry
Elite can be equipped with an optional temperature sensor that is used to monitor the condenser coil temperature. The sensor is
plugged into the “SERVICE/H20” sensor jack and parameter P-8 programmed for a temperature between 100 and 150°F (37.8
and 65.6°C), depending on seawater temperature and the system type. (Note that setting increments are in °F even when the
control is set to display °C.) Connect the water sensor to the condenser coil outlet and insulate it. When the coil temperature
rises above the programmed value, the pump and compressor are shut down and “PLF” flashes in the display.
P-9: Display Brightness Control
The display brightness can be adjusted from 4 to 18, with 4 being the dimmest and 18 the brightest. Typically a dark cabin will
require a setting of 4 or 5. A very bright cabin will require a setting of 12 to 18.
P-10: Fahrenheit or Celsius Selection
The default setting is °F. Select °C for Celsius. (Celsius readings are displayed in tenths, for example 22.2°).
P-11: Cycle Pump With Compressor
To increase pump life and conserve electricity the pump can be programmed to cycle on and off with the compressor. The pump
can also be programmed to operate continuously whenever the system is on. To program the pump for continuous operation,
set P-11 to “con”.
P-12: Reverse Automatic Fan Speeds During Heating
The automatic fan speeds can be reversed during Heat Mode to improve heat output in cooler climates. The fan will speed up
as the set point is approached. Lowering the fan speed when the cabin is cold increases head pressure and helps raise supply
temperature. Increasing the fan speed as the set point is approached also reduces unnecessary high-pressure faults. The fan
switches to low speed when the set point is satisfied and the compressor cycles off. The fan can be programmed to operate the
same as in cooling by programming P-12 “nor” which represents normal fan operation during reverse-cycle heating.
P-13: Reverse-Cycle or Electric Heat
Units not equipped with reverse-cycle heat may have an electric heater added. Set to “ELE” for the electric heat option or “nor
to disable.
11

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Dometic Elite Control DX systems bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Dometic Elite Control DX systems in de taal/talen: Engels als bijlage per email.

De handleiding is 0,32 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

loading

Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info