WI 35TU - WI 45TU English
7.4.4 Hydraulic distribution system
The compact manifold and the dual differential pressureless
manifold function as an interface between the heat pump, the
heating distribution system, the buffer tank and, in some cases,
even the domestic hot water cylinder. A compact system is
used to simplify the installation process, so that a lot of different
components do not have to be installed individually. Further in-
formation can be found in the relevant installation instructions.
Compact manifold
The return sensor can remain in the heat pump, or should be in-
stalled in the immersion sleeve. The remaining empty space be-
tween the sensor and the immersion sleeve must be filled com-
pletely with heat transfer compound.
Dual differential pressureless manifold
In order for the heating circuit pumps of the generator and con-
sumer circuits to supply the flow to the return sensor, this must
be installed in the immersion sleeve of the dual differential
pressureless manifold.
7.5 Electrical connection
7.5.1 General
All electrical installation work must be carried out by a trained
electrician or a specialist for the specified tasks in accordance
with the
installation and operating instructions,
country-specific installation regulations (e.g. VDE 0100),
technical connection conditions of the energy suppliers
and supply grid operators (e.g. TAB) and
local conditions.
To ensure that the frost protection function of the heat pump
works properly, the heat pump manager must remain con-
nected to the power supply and the flow must be maintained
through the heat pump at all times.
The switching contacts of the output relay are interference-
suppressed. Therefore, depending on the internal resistance of
the measuring instrument, a voltage can also be measured
when the contacts are open. However, this will be much lower
than the line voltage.
Extra-low voltage is connected to controller terminals N1-J1 to
N1-J11; N1-J19 to N1-J20; N1-J23 to N1-J26 and the terminal
strips X3. If, due to a wiring error, the line voltage is mistakenly
connected to these terminals, the heat pump manager will be
destroyed.
NOTE
º
ºººº
For installation work on the switch box, ensure that the mains
cable and signal cables are inserted separately into the switch
box. The specially arranged switch box inlets must be used for
this purpose (see Fig. 7.4 on page 7).
The mains cables and signal cables must also always be laid
separately in the switch box during wiring work.
Fig. 7.4:Cable inlet switch box
7.5.2 Electrical installation work
1) The four-core electrical supply cable for the heat pump
power part is fed from the heat pump electricity meter into
the heat pump via the utility company blocking contactor
(if required) (for supply voltage, see heat pump manual).
The mains cable is connected to the heat pump contact
plate via terminals X1: L1/L2/L3/PE.
CAUTION!
!!
Ensure that there is a clockwise rotating field: With incorrect
wiring the starting of the heat pump is prevented. A
corresponding warning is indicated on the display of the heat
pump manager (adjust wiring).
An all-pole disconnecting device with a contact gap of at least
3 mm (e.g. utility company blocking contactor or power contac-
tor) and an all-pole circuit breaker with common tripping for all
external conductors must be installed in the power supply for
the heat pump (tripping current and characteristic in compli-
ance with the device information).
2) The three-core supply cable for the heat pump manager
(heating controller N1) is fed into the heat pump. Connec-
tion of the control cable to the contact plate of the heat
pump via terminal X2: L/N/PE.
The (L/N/PE~230 V, 50 Hz) supply cable for the heat pump
manager must have a continuous voltage. For this reason,
it should be tapped upstream from the utility company
blocking contactor or be connected to the household cur-
rent, as important protection functions could otherwise be
lost during a utility block.
3) The utility company blocking contactor (K22) with main
contacts and an auxiliary contact must be designed and
provided by the customer in accordance with the heat
pump output.
The NO contact of the utility company blocking contactor
is looped from the terminal strip X3/G to the plug-in termi-
nal X3/A3. CAUTION! Extra-low voltage!
4) The contactor (K20) for the immersion heater (E10) of
mono energy systems (HG2) should be dimensioned ac-
cording to the radiator output and must be supplied by the
customer. It is controlled (230 V AC) by the heat pump
manager via terminals X2/N and X2/K20.
5) The contactor (K21) for the flange heater (E9) in the do-
mestic hot water cylinder should be dimensioned accord-
ing to the radiator output and must be supplied by the cus-
tomer. It is controlled (230 V AC) by the heat pump
manager via terminals X2/N and X2/K21.
6) The contactors mentioned above in points 3, 4 and 5 are
installed in the electrical distribution system.
7) All installed electric cables must have permanent wiring.
Supply signal cable
Supply mains cable
25

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Dimplex WI 35TU bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Dimplex WI 35TU in de taal/talen: Duits, Engels, Frans als bijlage per email.

De handleiding is 2.76 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

loading

Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info