798439
15
Verklein
Vergroot
Pagina terug
1/44
Pagina verder
www.dimplex.de E-5
English
7.3
6.4 Electrical Connection
The following electrical connections need to be established on
the heat pump.
Connection of the control line to the control panel of the heat
pump via terminal X1: L/N/PE.
Connection of the mains cable to the control panel of the
heat pump via terminal X5: L1/L2/L3/PE.
Connection of the mains cable of the well pump to the con-
trol panel of the heat pump via terminal X5: L11/L21/L31/PE.
Connection of the well pump (to be provided by the cus-
tomer) to the control panel of the heat pump via terminal X1:
PE and pump contactor K2: 2/4/6.
Ensure that the supply voltage for these terminals cannot be
switched off by the tariff contactor when connecting the mains
cable of the well pump, in order to enable the turn-off delay of the
well pump.
All electrical components required for the operation of the heat
pump are located on the control panel.
For detailed instructions concerning the connection and function-
ing of the heat pump controller, refer to the operating manual
supplied with the controller.
An all-pole disconnecting device with a contact gap of at least
3 mm (e.g. utility blocking contactor or power contactor) as well
as a 3-pole circuit breaker with common tripping for all external
conductors have to be provided by the customer. The required
conductor cross-section is to be selected according to the power
consumption of the heat pump, the technical connection require-
ments of the respective utility company as well as all applicable
regulations. Details on the power consumption of the heat pump
are listed on both the product information sheet and the type
plate. The connection terminals are designed for a max. conduc-
tor cross section of 10 mm2.
ATTENTION!
Observe the clockwise rotating field when connecting the mains cable (if
rotating field is not clockwise, the heat pump will not work properly and
will be very noisy).
7 Commissioning
7.1 General Information
To ensure that start-up is performed correctly, it should only be
carried out by an after-sales service technician authorised by the
manufacturer. This may be a condition for extending the guaran-
tee (see Warranty Service).
7.2 Preparation
The following items need to be checked prior to start-up:
The heat pump must be fully connected, as described in
Chapter 6.
The heat source system and the heating circuit must have
been filled and checked.
All valves that could impair proper flow in the well and heat-
ing circuits must be open.
The heat pump controller must be adapted to the heating
system in accordance with the controller’s operating instruc-
tions.
7.3 Start-up Procedure
The heat pump is started up via the heat pump controller.
ATTENTION!
The heat pump must be started up in accordance with the installation and
operating instructions of the heat pump controller.
If an overflow valve is fitted to assure the minimum heating water
flow rate, the valve must be set in accordance with the require-
ments of the respective heating system. Incorrect adjustment
can lead to faulty operation and increased energy consumption.
We recommend carrying out the following procedure to correctly
adjust the overflow valve:
Close all of the heating circuits that may also be closed during
operation (depending on the type of heat pump usage) so that
the most unfavourable operating state - with respect to the water
flow rate - is achieved. This normally means the heating circuits
of the rooms on the south and west sides of the building. At least
one heating circuit must remain open (e.g. bathroom).
The overflow valve should be opened far enough to produce the
maximum temperature spread between the heating flow and re-
turn flow listed in the table below for the current heat source tem-
perature. The temperature spread should be measured as close
as possible to the heat pump. The heating element of mono en-
ergy systems should be disconnected.
Any faults occurring during operation are displayed on the heat
pump controller and can be corrected as described in the operat-
ing manual of the heat pump controller.
Heat source
temperature Max. temperature spread
between heating flow and return
flow
From To
7° C 12° C 10 K
13° C 18° C 11 K
19° C 25° C 12 K
15

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Dimplex WI 18CS bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Dimplex WI 18CS in de taal/talen: Duits, Engels, Frans als bijlage per email.

De handleiding is 2.95 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

loading

Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info