1 Please Read
Immediately
1.1 Important Information
ATTENTION!
The heat pump is not secured to the wooden pallet.
ATTENTION!
The heat pump must not be tilted more than 45° (in any direction).
ATTENTION!
Do not use the holes in the panel assemblies for lifting the device!
ATTENTION!
Flush the heating system prior to connecting the heat pump.
ATTENTION!
The supplied dirt trap must be inserted in the heat source inlet of the heat
pump to protect the evaporator against the ingress of impurities.
ATTENTION!
The brine solution must contain at least a 25% concentration of a
monoethylene glycol or propylene glycol-based antifreeze, which must
be mixed before filling.
ATTENTION!
Observe the clockwise rotating field when connecting the mains cable (if
rotating field is not clockwise, the heat pump will not work properly and
will be very noisy).
ATTENTION!
The heat pump must be started up in accordance with the installation and
operating instructions of the heat pump controller.
ATTENTION!
We recommend the installation of a suitable corrosion protection system
to prevent the formation of deposits (e.g. rust) in the condenser of the
heat pump.
ATTENTION!
Any work on the heat pump may only be performed by authorised and
qualified after-sales service technicians.
ATTENTION!
Disconnect all electrical circuits from the power source prior to opening
the device.
1.2 Legal Regulations and
Directives
This heat pump conforms to all relevant DIN/VDE regulations
and EU directives. Refer to the EC Declaration of Conformity in
the appendix for details.
The heat pump must be connected to the power supply in com-
pliance with all relevant VDE, EN and IEC standards. Any further
connection requirements stipulated by local utility companies
must also be observed.
The heat pump is to be connected to the heat source system or
the heating system in accordance with all applicable regulations.
1.3 Energy-Efficient Use of the
Heat Pump
By operating this heat pump you are helping to protect our envi-
ronment. The heating or cooling system and the heat source
must be properly designed and dimensioned to ensure efficient
operation. It is particularly important to keep water flow tempera-
tures as low as possible in heating operation. All connected en-
ergy consumers should therefore be suitable for low flow temper-
atures. Raising the heating water temperature by 1 K
corresponds to an increase in energy consumption of approx.
2.5%. Low-temperature heating systems with flow temperatures
between 30 °C and 50 °C are particularly well-suited for energy-
efficient operation.
2 Purpose of the Heat
Pump
2.1 Application
The brine-to-water heat pump is designed for use in existing or
newly built heating systems. Brine is used as the heat carrier in
the heat source system. Borehole heat exchangers, ground heat
collectors or similar systems can be used as the heat source.
2.2 Operating Principle
Heating
The heat generated by the sun, wind and rain is stored in the
ground. This heat stored in the ground is collected at a low tem-
perature by the brine circulating in the ground collector, ground
coil or similar device. A circulating pump then conveys the
“heated” brine to the evaporator of the heat pump. There the heat
is given off to the refrigerant in the refrigerating cycle. This cools
the brine so that it can absorb thermal energy in the brine circuit.
The refrigerant is drawn in by the electrically driven compressor,
compressed and “pumped” to a higher temperature level. The
electrical power needed to run the compressor is not lost in this
process. Most of it is absorbed by the refrigerant.
Subsequently, the refrigerant is passed through the condenser
where it transfers its heat energy to the heating water. Depend-
ing on the set operating point (thermostat setting), the heating
water is thus heated up to a max. of 60 °C.
Cooling
The functions of the evaporator and the liquifier are reversed in
the “Cooling” operating mode.
The heating water transfers its heat to the refrigerant via the liq-
uifier which is now functioning as an evaporator. The refrigerant
is pumped to a higher temperature level using the compressor.
Heat passes into the brine via the liquifier (evaporator in heating
operation) and consequently into the ground.
12

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Dimplex SI 11USR bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Dimplex SI 11USR in de taal/talen: Duits, Engels, Frans als bijlage per email.

De handleiding is 4.69 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

loading

Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info