English LI 20TES - LI 28TES
7.5 Electrical connection
7.5.1 General
All electrical connection work must be carried out by a trained
electrician or a specialist for the specified tasks in accordance
with the
installation and operating instructions,
country-specific installation regulations (e.g. VDE 0100),
technical connection conditions of the energy suppliers
and supply grid operators (e.g. TAB) and
local conditions.
To ensure that the frost protection function of the heat pump
works properly, the heat pump manager must remain con-
nected to the power supply and the flow must be maintained
through the heat pump at all times.
The switching contacts of the output relay are interference-
suppressed. Therefore, depending on the internal resistance of
the measuring instrument, a voltage can also be measured
when the contacts are open. However, this will be much lower
than the line voltage.
Extra-low voltage is connected to controller terminals N1-J1 to
N1-J11, N1-J24 to N1-J26 and terminal strip X3. If, due to a
wiring error, the line voltage is mistakenly connected to these
terminals, the heat pump manager will be destroyed.
7.5.2 Electrical installation
1) The electric supply cable for the output section of the heat
pump (up to 4-core) is fed from the electricity meter of the
heat pump via the utility blocking contactor (if required)
into the heat pump (see heat pump operating instructions
for supply voltage).
An all-pole disconnecting device with a contact gap of at
least 3 mm (e.g. utility blocking contactor or power contac-
tor) and an all-pole circuit breaker with common tripping
for all external conductors must be installed in the power
supply for the heat pump (tripping current and characteris-
tic in compliance with the device information).
When connecting the device, ensure that the incoming
supply has a clockwise rotating field L1; L2; L3.
ATTENTION!
!
!
Ensure that there is a clockwise rotating field: With incorrect
wiring the starting of the heat pump is prevented. A
corresponding warning is indicated on the display of the heat
pump manager (adjust wiring).
For detailed information, refer to the circuit diagrams in the
appendix.
2) The three-core electic supply cable for the heat pump
manager (heating controller N1) is fed into the heat pump.
The correct control voltage must be ensured according to
the type plate. The (L/N/PE~230 V, 50 Hz) supply cable for
the heat pump manager must have a constant voltage. For
this reason, it should be tapped upstream from the utility
blocking contactor or be connected to the household
current, as important protection functions may otherwise
be lost during a utility block.
3) The utility blocking contactor (K22) with 3 main contacts
(1/3/5 // 2/4/6) and an auxiliary contact (NO contact 13/
14) should be dimensioned according to the heat pump
output and must be supplied by the customer.
The NO contact of the utility blocking contactor (13/14) is
looped from terminal strip X3/G to connector terminal N1-
J5/ID3. CAUTION! Extra-low voltage!
4) The contactor (K21) for the flange heater (E9) in the hot
water cylinder should be dimensioned according to the
radiator output and must be supplied by the customer. It is
controlled (230 V AC) by the heat pump manager via
terminals X2/N and N1-J16/NO10.
5) The contactors mentioned above in points 3 and 4 are
installed in the electrical distribution system. Mains cables
for the installed heaters must be laid and secured in
accordance with the valid standards and regulations.
6) All installed electric cables must have permanent wiring.
7) The heat circulating pump (M13) is activated via the con-
tact N1-J13/NO5. The connection points for the pump are
X2/M13 and X2/N. When using pumps where the switch-
ing capacity exceeds the output, a coupling relay must be
interposed.
8) The auxiliary circulating pump (M16) is activated via the
contact N1-J16/NO9. The connection points for the pump
are X2/M16 and X2/N. A coupling relay is already
integrated in this output.
9) The domestic hot water circulating pump (M18) is acti-
vated via the contact N1-J18/NO6. The connection points
for the pump are X2/M18 and X2/N. When using pumps
where the switching capacity exceeds the output, a cou-
pling relay must be interposed.
10) The return sensor (R2) is integrated into air-to-water heat
pumps for indoor installation.
The connection to the HPM is at terminals X3/GND and
N1-J2/U2.
11) The external sensor (R1) is connected to terminals X3/GND
and N1-J2/U1.
12) The domestic hot water sensor (R3) is included with the
domestic hot water cylinder and is connected to terminals
X3/ GND and N1-J2/U3.
7.5.3 Connecting an electronically
regulated circulating pump
Electronically regulated circulating pumps have high starting
currents, which may shorten the service life of the heat pump
manager. A coupling relay is therefore installed or must be in-
stalled between the output of the heat pump manager and the
electronically regulated circulating pump. This is not necessary
if the maximum permissible operating current of the heat pump
manager of 2 A and the maximum permissible starting current
of the heat pump manager of 12 A are not exceeded by the
electronically regulated circulating pump or a relevant approval
has been issued by the pump manufacturer.
ATTENTION!
!
!
It is not permitted to connect more than one electronically
regulated circulating pump via a relay output.
30

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Dimplex LI 24TES bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Dimplex LI 24TES in de taal/talen: Duits, Engels, Frans als bijlage per email.

De handleiding is 2.49 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

loading

Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info