609084
70
Verklein
Vergroot
Pagina terug
1/84
Pagina verder
70
GT 530A DDR_G30A/AE _IO_V4.0 09/2013
Gas Vent Category I - High Temperature Operation Applications:
Consult a chimney-venting specialist or professional engineer for the sizing of the breeching and main chimney in
accordance to local and national gas codes CSA B149.1-05 & ANSI Z223.1 (NFPA 54) and sized accordingly to the
appropriate tables or methods of chimney vent sizing as local jurisdiction will accept.
1. An approved type “B or L” vent may be used under these operating conditions.
a. Category I - Negative breeching pressure range from 0 to -0.09 inches water column [0 to 0.22 mbar]
b. Return water temperature is greater than 140°F [60°C]
c. The flue gas temperature is greater than 252°F [122°C] to a maximum of 473°F [245°C]
d. Double acting draft control device may be employed, but is not necessary for correct operation of the boiler.
Consult a chimney-vent specialist for the correct usage and application.
Application Note: If a barometric draft control is not used it is mandatory that a vent safety device, either equipped
on burner or venting (gas, combustion head or vent pressure switch, WMO-1 vent safety switch or FTS-6 spill
switch).
Gas Vent Category III - High Temperature Operation Applications:
The vent shall be sized by a chimney venting specialist or professional engineer using methods or vent calculations
that are acceptable to National and local codes having jurisdiction.
2. Listed Industrial Type Factory Built Chimney system. Listed Type BH Class I/II 245C maximum, or special vent
system fabricated from AL29-4C® or SS316L.
a. Category III – Positive breeching pressure range from 0 to +0.20 inches water column [0 to 0.50mbar]
b. The vent shall be sized by a chimney venting specialist or professional engineer using methods or vent
calculations that are acceptable to National and local codes having jurisdiction. A maximum 16 ft. [5m]
horizontal breeching length to the main chimney TEE fitting. The vent shall then extend vertically 5 ft.
[1.5m] minimum to a 246 ft. [75m] maximum, through the ceiling roof.
c. Return water temperature is greater than 140°F [60°C]
d. The flue gas temperature is greater than 252°F [122°C] to a maximum of 473°F [245°C]
e. Do not use any barometric draft control on positive vent pressure systems as flue gas spillage will
contaminate inside air quality.
Application Note: it is mandatory that a vent safety device be employed, either equipped on burner or venting (gas,
combustion head or vent pressure switch)
Oil or Dual Fuel Applications:
a. Listed Industrial Type Factory Built Chimneys system or special vent system fabricated from AL29-4C® or
SS316L sized in accordance to the appropriate table in the CSA B139-00 or NFPA 31.
b. Negative breeching pressure range from 0 to -0.09 inches water column [0 to 0.22 mbar]
c. A single acting draft control device may be employed as required, but is not necessary for correct operation
of the boiler. Consult a chimney-vent specialist for the correct usage and application.
Application Note: If a barometric draft control is not used it is mandatory that a vent safety device, either equipped
on burner or venting (gas, combustion head or vent pressure switch, WMO-1 vent safety switch or FTS-6 spill
switch).
Gas Vent Category II, III & IV - Low Temperature Operation Applications:
These vent systems shall be sized by a chimney venting specialist or professional engineer using methods or vent
calculations that
are acceptable to National and local codes having jurisdiction Listed Industrial Type Factory Built Chimney system.
1. Listed Type BH Class I/II 245C maximum, or special vent system fabricated from AL29-4C® or SS316L.
2. The vent shall then extend vertically 5 ft. [1.5m] minimum to a 246 ft. [75m] maximum, through the ceiling
roof.
3. Condensate drain TEE tting shall be provided on the boiler breeching as close a practical to avoid any
accumulation of ue gas condensation
4. Follow the vent manufacturers recommended and supplied instructions regarding, vent connection cleaning,
sealing, supporting.
5. Category II - Negative breeching pressure range from 0 to -0.09 inches water column [0 to 0.22mbar]
6. Category III & IV – Positive breeching pressure range from 0 to +0.20 inches water column [0 to 0.50mbar]
7. Do-not use a barometric draft control on positive vent pressure systems as ue gas spillage will contaminate the
inside air quality.
70

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw De Dietrich GT530AE Series bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van De Dietrich GT530AE Series in de taal/talen: Engels als bijlage per email.

De handleiding is 13,03 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

loading

Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info