18. These models are supplied with a factory pre-set programme which will
be active after a RESET has been performed. The pre-s e t
programme is shown in the chart with the Setting Instructions.
The chart also has spaces for users own times and temperatures a s
required by them.
19. The time and programme memory are maintained by the batteries
which should last more than two years. Every 24 months the batteries
should be renewed. Internal circuitry retains the time and programme
memory for one minute, long enough for the batteries to be changed.
If the batteries volts drop, before a change is due, a battery symbol will
blink in the display. When this occurs the TP75-RF will operate
normally for 2 weeks. After the 15th midnight all relays will switch to
OFF, the unit will shut down with just the time shown. When new
batteries are fitted the unit will start to operate normally again.
Advise the User to enter their own times and temperatures in the chart on the
Setting Instructions.
Post-commissioning
Optimum Start Control
If this has been enabled, initially set to the recommended 30 minutes start-
up duration and the event 1 temperature is not achieved by the event 1 time,
then refer to the Setting Instructions and increase the start-up duration one
stage, i.e. to 1 hour.
If the space temperature at the beginning of an Optimum Start sequence is
consistently lower than the programmed event 1 temperature by more that
2°F, then the event 1 temperature may not be achieved by the event 1 time.
In this case the event 1 time should be brought forward sufficiently to
compensate, so that the comfort temperature is achieved when actually
required.
Intelligent Anticipator
If, when the heating equipment is switched on, the room temperature is 4°F
or more lower than the programmed temperature the electronic anticipation
function measures the rate of rise in the sensed temperature and will switch
the heating plant off before the programmed temperature is reached. The
residual heat in the system after the heating plant has shut down will ensure
that the comfort temperature is achieved. This will improve the comfort
conditions and minimise fuel consumption.
Commissioning
12. Lower the front flap and remove the anti-discharge paper strip from
between the batteries and their contacts, and ensure the mains power
to the control circuit is switched on.
13. Press and release the recessed RESET button to ensure the factory
pre-set programme is active.
14. Once the programming has been completed, communication between
the thermostat and the receiver module has to be established.
a) SINGLE ZONE SYSTEM WITH RX1 RECEIVER
1 - Press and hold the LEARN button of the TP75-RF for at least 3
seconds. The thermostat will now transmit a continuous signal which
contains its unique identity for a period of 5 minutes.
2 - Within the 5 minute period go to the RX1 receiver module and
press both "PROG" and "CH1" buttons together and hold for at
least 3 seconds, then release.
During this process the RX1 receiver will have learnt the unique
transmission code of the thermostat and will in future react to all
transmissions from that thermostat.
To stop the continuous transmission on the TP75-RF unit press the
s button.
b) TWO ZONE SYSTEM WITH RX2 RECEIVER
1 - Repeat as above for zone one (CH1).
2 - Repeat steps one and two above for zone two, remembering to
press "PROG" and "CH2" on the RX2 receiver.
c) THREE ZONE SYSTEM WITH RX3 RECEIVER
1 - Repeat as above for zones 1 and 2 (CH1 and CH2).
2 - Repeat as above for zone 3, remembering to press "PROG" and "CH3"
on the RX3 receiver.
15. Establish with the customer the requirements for the operating
mode, and adjust as follows:
Clock type - 24 hour or 12 hour with AM/PM indication.
The factory pre-set is 24 hour. To convert to 12 hour, press and
hold down the NEXT and DAY buttons until the display changes,
then release. (Repeat to return to a 24 hour clock.)
Temperature display - °C or °F
The factory pre-set is °C. To convert to display all temperatures i n
°F, press and hold down the DAY and COPY buttons until the
display changes. (Repeat to return to a °C display.)
16. Check the existing space temperature by pressing and holding
down the two buttons: NEXT and COPY, until the display changes from
time to temperature.
17a. If the set temperature is below the space temperature, use the
button to raise the set temperature. The flame symbol will appear in the
display. Check that the heating plant operates correctly.
17b. If the set temperature is above the space temperature, use the
button to lower the set temperature below the space temperature. The
flame symbol will disappear. Check that the heating plant does not
operate.
3

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Danfoss TP75-RF bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Danfoss TP75-RF in de taal/talen: Engels als bijlage per email.

De handleiding is 0.26 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

loading

Andere handleiding(en) van Danfoss TP75-RF

Danfoss TP75-RF Gebruiksaanwijzing - Nederlands - 4 pagina's

Danfoss TP75-RF Gebruiksaanwijzing - Deutsch - 4 pagina's

Danfoss TP75-RF Gebruiksaanwijzing - English - 4 pagina's


Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info