DAIKIN ROOM AIR CONDITIONER
INSTALLATION MANUAL
R410A Split Series
EnglishDeutschFrançaisNederlandsEspañolItalianoEλληνικάPortuguesPyccкийTürkçe
MODELS
FTXS35K2V1B FTXS35K3V1B
FTXS42K2V1B FTXS42K3V1B
FTXS50K2V1B FTXS50K3V1B
ATXS35K2V1B ATXS35K3V1B
ATXS50K2V1B ATXS50K3V1B
English 1
English
Safety Precautions
The precautions described herein are classified as WARNING and CAUTION. They both contain important
information regarding safety. Be sure to observe all precautions without fail.
Meaning of WARNING and CAUTION notices
WARNING.....Failure to follow these instructions properly may result in personal injury or loss of life.
CAUTION......Failure to observe these instructions properly may result in property damage or personal injury, which
may be serious depending on the circumstances.
The safety marks shown in this manual have the following meanings:
After completing installation, conduct a trial operation to check for faults and explain to the customer how to operate
the air conditioner and take care of it with the aid of the operation manual.
The English text is the original instruction. Other languages are translations of the original instructions.
Be sure to follow the instructions. Be sure to establish an earth connection. Never attempt.
WARNING
Ask your dealer or qualified personnel to carry out installation work.
Do not attempt to install the air conditioner yourself. Improper installation may result in water leakage, electric shocks or fire.
Install the air conditioner in accordance with the instructions in this installation manual.
Improper installation may result in water leakage, electric shocks or fire.
Be sure to use only the specified accessories and parts for installation work.
Failure to use the specified parts may result in the unit falling, water leakage, electric shocks or fire.
Install the air conditioner on a foundation strong enough to withstand the weight of the unit.
A foundation of insufficient strength may result in the equipment falling and causing injury.
Electrical work must be performed in accordance with relevant local and national regulations and with instructions
in this installation manual. Be sure to use a dedicated power supply circuit only.
Insufficiency of power circuit capacity and improper workmanship may result in electric shocks or fire.
Use a cable of suitable length.
Do not use tapped wires or an extension lead, as this may cause overheating, electric shocks or fire.
Make sure that all wiring is secured, the specified wires are used, and that there is no strain on the terminal
connections or wires.
Improper connections or securing of wires may result in abnormal heat build-up or fire.
When wiring the power supply and connecting the wiring between the indoor and outdoor units, position the wires
so that the control box lid can be securely fastened.
Improper positioning of the control box lid may result in electric shocks, fire or over heating terminals.
If refrigerant gas leaks during installation, ventilate the area immediately.
Toxic gas may be produced if the refrigerant comes into contact with fire.
After completing installation, check for refrigerant gas leakage.
Toxic gas may be produced if the refrigerant gas leaks into the room and comes into contact with a source of fire, such as a fan heater,
stove or cooker.
When installing or relocating the air conditioner, be sure to bleed the refrigerant circuit to ensure it is free of air,
and use only the specified refrigerant (R410A).
The presence of air or other foreign matter in the refrigerant circuit causes abnormal pressure rise, which may result in equipment damage
and even injury.
During installation, attach the refrigerant piping securely before running the compressor.
If the refrigerant pipes are not attached and the stop valve is open when the compressor is run, air will be sucked in, causing abnormal
pressure in the refrigeration cycle, which may result in equipment damage and even injury.
During pump-down, stop the compressor before removing the refrigerant piping.
If the compressor is still running and the stop valve is open during pump-down, air will be sucked in when the refrigerant piping is removed,
causing abnormal pressure in the refrigeration cycle, which may result in equipment damage and even injury.
Be sure to earth the air conditioner.
Do not earth the unit to a utility pipe, lightning conductor or telephone earth lead. Imperfect earthing may result in electric shocks.
Be sure to install an earth leakage breaker.
Failure to install an earth leakage breaker may result in electric shocks or fire.
CAUTION
Do not install the air conditioner at any place where there is a danger of flammable gas leakage.
In the event of a gas leakage, build-up of gas near the air conditioner may cause a fire to break out.
While following the instructions in this installation manual, install drain piping to ensure proper drainage
and insulate piping to prevent condensation.
Improper drain piping may result in indoor water leakage and property damage.
Tighten the flare nut according to the specified method such as with a torque wrench.
If the flare nut is too tight, it may crack after prolonged use, causing refrigerant leakage.
2 English
Accessories
Choosing an Installation Site
Before choosing the installation site, obtain user approval.
1. Indoor unit
The indoor unit should be sited in a place where:
1) the restrictions on installation specified in the indoor unit installation drawings are met,
2) both air inlet and air outlet have clear paths met,
3) the unit is not in the path of direct sunlight,
4) the unit is away from the source of heat or steam,
5) there is no source of machine oil vapour (this may shorten indoor unit life),
6) cool (warm) air is circulated throughout the room,
7) the unit is away from electronic ignition type fluorescent lamps (inverter or rapid start type) as they may shorten the remote
controller range,
8) the unit is at least 1m away from any television or radio set (unit may cause interference with the picture or sound),
9) no laundry equipment is located.
2. Wireless remote controller
Turn on all the fluorescent lamps in the room, if any, and find the site where remote controller signals are properly received
by the indoor unit (within 7m).
This appliance is intended to be used by expert or trained users in shops, in light industry and on farms, or for
commercial and household use by lay persons.
Sound pressure level is less than 70 dB(A).
Mounting plate
1
Remote controller holder
1
Operation manual
1
Titanium apatite photocatalytic
air-purifying filter
2
Dry battery AAA. LR03
(alkaline)
2
Installation manual
1
Wireless remote controller
1
Indoor unit fixing screw
(M4 × 12L)
2
Indoor unit
H
A
D
G
B
E
H
C
F
English 3
English
Preparation before Installation
1. Removing and installing the front panel
Removal method
1) Place your fingers in the indentations on the main unit (one each on the
left and right sides), and open the front panel until it stops.
2) Continue to open the front panel further while sliding the panel to the
right and pulling it toward you in order to disengage the front panel shaft
on the left side. To disengage the front panel shaft on the right side, slide
the panel to the left while pulling it toward you.
Installation method
Align the tabs of the front panel with the grooves, and push all the way
in. Then close slowly. Push the centre of the lower surface panel firmly
to engage the tabs.
2. Removing and installing the front grille
Removal method
1) Remove the front panel to remove the air filter.
2) Remove the 3 screws from the front grille.
3) In front of the mark of the front grille, there are 3 upper hooks.
Lightly pull the front grille toward you with one hand, and push down on
the hooks with the fingers of your other hand.
When there is no work space because the unit is close to ceiling
CAUTION
• Be sure to wear protection gloves.
Place both hands under the centre of the front grille, and while pushing up, pull it toward you.
Installation method
1) Install the front grille and firmly engage the upper hooks (3 locations).
2) Install 3 screws of the front grille.
3) Install the air filter and then mount the front panel.
3. How to set the different addresses
When two indoor units are installed in one room, the two wireless remote controllers
can be set for different addresses.
1) Remove the metal plate electrical wiring cover.
(Refer to the Removal/attachment methods of metal plate electrical wiring
covers.)
2) Cut the address jumper (JA) on the printed circuit board.
3) Cut the address jumper (J4) in the remote controller.
Be careful not to cut jumper (J8).
Front panel shaft
Groove
Upper hook
mark area
(3 locations)
Push
down.
Upper hook
1) Push up.
2) Pull toward you.
Jumper
4 English
Indoor Unit
Installation Drawings
Screws
(M4 × 16L)
Service lid
Caulk pipe
hole gap
with putty.
Wrap the insulation pipe
with the finishing tape
from bottom to top.
Cut thermal insulation
pipe to an appropriate
length and wrap it with
tape, making sure that no
gap is left in the insulation
pipe’s cut line.
Bottom frame
Front grille
How to attach the indoor unit
Hook the claws of the bottom frame
to the mounting plate.
If the claws are difficult to hook,
remove the front grille.
How to remove the indoor unit
Push up the lower part of the front
grille to release the claws.
If they are difficult to release,
remove the front grille.
Opening the service lid
The service lid is removable.
1) Remove the service lid screw.
2) Pull out the service lid diagonally
down in the direction of the arrow.
3) Pull down.
The mounting plate
should be installed on a
wall which can support the
weight of the indoor unit.
30mm or more from ceiling
Front panel
50mm or more
from walls
(on both sides)
Air filters
Mounting plate
Mounting
plate
Mounting plate
fixing screw
(field supply: M4 × 25L)
Wireless remote controller
Fixing screw for remote
controller holder
(field supply: M3 × 20L)
Remote controller
holder
Air filter
Titanium apatite
photocatalytic
air-purifying filter
Filter frame
Ta b
Titanium apatite photocatalytic
air-purifying filter (2 pcs)
Before screwing the
remote controller holder
to the wall, make sure
that control signals are
properly received by
indoor unit.
Claw
Opening method
English 5
English
Indoor Unit Installation
1. Installing the mounting plate
The mounting plate should be installed on a wall which can support the weight of the indoor unit.
1) Temporarily secure the mounting plate to the wall, make sure that the panel is completely level, and mark the boring points
on the wall.
2) Secure the mounting plate to the wall with screws.
Recommended mounting plate retention spots and dimensions
2. Boring a wall hole and installing wall embedded pipe
For walls containing metal frame or metal board, be sure to use a wall
embedded pipe and wall cover in the feed-through hole to prevent possible
heat, electrical shock, or fire.
Be sure to caulk the gaps around the pipes with caulking material to
prevent water leakage.
1) Bore a feed-through hole of 65mm in the wall so it has a down slope
toward the outside.
2) Insert a wall pipe into the hole.
3) Insert a wall cover into wall pipe.
4) After completing refrigerant piping, wiring, and drain piping, caulk pipe hole gap with putty.
3. Installing the indoor unit
In the case of bending or curing refrigerant pipes, keep the following
precautions in mind.
Abnormal sound may be generated if improper work is conducted.
1) Do not strongly press the refrigerant pipes onto the bottom frame.
2) Do not strongly press the refrigerant pipes on the front grille, either.
209 241 191.5
66
106176
150
384
900
344
75.5
48 250
48
298
50
50
Use a tape measure
as shown.
unit: mm
Removed pipe
port cover
Recommended mounting plate
retention spots (5 spots in all)
Place a leveler
on raised tab.
Drain hose positionKeep here the piece cut out
from the unit for piping
Liquid pipe end Gas pipe end
Mounting plate
* The removed pipe port cover can be
kept in the mounting plate pocket.
Position the end of
the tape measure at .
Through-
the-wall
hole 65mm
Inside Outside
Caulking
Wall embedded pipe
(field supply)
Wall hole cover
(field supply)
Wall embedded pipe
(field supply)
65
6 English
Indoor Unit Installation
Remove the pipe port cover as shown below.
1) Cut off the pipe port cover from inside the front grille using a copping
saw.
Apply the blade of the copping saw to the notch, and cut off the pipe
port cover along the uneven inner surface.
2) After cutting off the pipe port cover, perform filing. Remove the burrs
along the cut section using a half round needle file.
CAUTION
• If the pipe port cover is cut off using nippers, the front grille will be damaged. Please do not use nippers.
• Wear gloves during the pipe port cover removal.
3-1.
Right-side, right-back, or right-bottom piping
1) Attach the drain hose to the underside of the refrigerant pipes with
adhesive vinyl tape.
2) Wrap the refrigerant pipes and drain hose together with insulation
tape.
3) Pass the drain hose and refrigerant pipes through the wall hole, then
set the indoor unit on the mounting plate hooks by using the
markings at the top of the indoor unit as a guide.
4) Open the front panel, then open the service lid.
(Refer to preparation before installation.)
5) Pass the inter-unit wire from the outdoor unit through the
feed-through wall hole and then through the back of the
indoor unit. Pull them through the front side. Bend the ends of
tie wires upward for easier work in advance. (If the inter-unit
wire ends are to be stripped first, bundle wire ends with
adhesive tape.)
6) Press the bottom frame of the indoor unit with both hands to
set it on the mounting plate hooks. Make sure the wires do
not catch on the edge of the indoor unit.
Right-bottom
piping
Right-back piping
Right-side piping
Bind refrigerant
pipe and drain
hose together with
insulating tape.
Remove pipe port cover
here for right-side piping.
Remove pipe port cover
here for right-bottom piping.
Mounting plate
Wire guide
When stripping off
the ends of inter-unit wire in
advance, cover the ends with
insulating tape to make it
easier to pass the wire.
Hang indoor unit’s hook here.
Inter-unit wire
Mounting plate
10

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Daikin FTXS42K3V1B bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Daikin FTXS42K3V1B in de taal/talen: Engels als bijlage per email.

De handleiding is 1,55 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

Andere handleiding(en) van Daikin FTXS42K3V1B

Daikin FTXS42K3V1B Gebruiksaanwijzing - Nederlands - 44 pagina's

Daikin FTXS42K3V1B Installatiehandleiding - Nederlands - 20 pagina's

Daikin FTXS42K3V1B Gebruiksaanwijzing - Deutsch - 44 pagina's

Daikin FTXS42K3V1B Installatiehandleiding - Deutsch - 20 pagina's

Daikin FTXS42K3V1B Gebruiksaanwijzing - English - 45 pagina's


Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info