Installation and operation manual
13
EUWA(*)5~24KBZW1
Packaged air-cooled water chillers
4PW61653-1 – 07.2010
Consulting actual operational information
The actual operational information that can be consulted in the list of
direct parameters consists of:
b01:Evaporator inlet water temperature,
b02:Evaporator outlet water temperature,
b03: Not used,
c10:Total running hours of the compressor 1,
c11:Total running hours of the compressor 2,
c15:Total running hours of the pump.
These are direct parameters, refer to "How to consult and modify the
direct parameters" on page 12.
Resetting alarms
When an alarm is detected, the following happens:
the alarm relay is energized,
the H LED is displayed
the display starts flashing, alternately showing the alarm code
and the inlet water temperature.
The following alarm codes may appear on the screen:
a1: indicates an anti-freeze alarm.
e1: indicates that the NTC probe used to measure the
evaporator inlet water temperature is defective.
e2: indicates that the NTC probe used to measure the
evaporator outlet water temperature is defective.
e3: indicates that the fuse for the evaporator heatertape (F4)
is blown or that there is a reverse phase error or that there
is a problem with the I/O PCB (A2P).
ehs: indicates that the supply voltage is exceedingly high. In
this case contact a licensed electrician.
el1: indicates that there is a power supply error (example:
noise). In this case contact a licensed electrician.
el2: indicates that there is a power supply error (example:
noise). In this case contact a licensed electrician.
els: indicates that the supply voltage is exceedingly low. In this
case contact a licensed electrician.
epb: indicates that the EEPROM on the controller PCB inside
the unit is defective.
epr: indicates that the EEPROM on the controller PCB inside
the unit is defective.
fl: indicates that there was no sufficient water flow either
during the period of 15 seconds after the pump was
started or for 5 seconds while the compressor is active or
that the overcurrent protection of the pump is activated.
hp1: indicates that a high pressure switch, the discharge
thermal protection or the overcurrent protection of the
compressor motor is activated or that the NTC probe used
to measure the ambient temperature is defective.
fl + hp1
: indicates that there is most likely an RPP error or that the
F4 fuse is blown.
lp1: indicates that the low pressure switch is activated.
ter: indicates that there is a remote user interface
communication error.
:
communication failure between the digital controller of the
unit and the remote user interface. Confirm the correct
selection of parameter code h23. This should be default
setting 0 and confirm the correction installation according
to the installation manual of the remote user interface
EKRUMCA.
To reset an alarm, proceed as follows:
1 Find the cause of shutdown and correct.
Refer to the chapter "Troubleshooting" on page 18.
2 If the alarm codes a1, fl, hp1 or lp1 appear on the display,
reset the alarm manually by pressing the E combination keys
C and D simultaneously for approximately 5 seconds.
In all other cases the alarm is reset automatically.
Once the alarm is reset, the error code and the H LED no longer
appears on the display. The controller continues its normal
operation, displaying the inlet water temperature.
Resetting warnings
During normal operation, the display of the controller may start
flashing, alternately showing the inlet water temperature and the
following warning code:
hc1: indicates that the compressor 1 requires maintenance:
the total running hours of the compressor 1 (direct
parameter c10) has exceeded the setting of the timer
threshold for maintenance warning (user parameter
c14).
hc2: indicates that the compressor 2 requires maintenance:
the total running hours of the compressor 2 (direct
parameter c11) has exceeded the setting of the timer
threshold for maintenance warning (user parameter
c14).
To reset the maintenance warning hc1 or hc2, proceed as follows:
1 Consult c10 running hours of compressor 1 or c11 running
hours of compressor 2.
These are direct parameters, refer to "How to consult and modify
the direct parameters" on page 12.
2 When c10 or c11 parameter value is displayed, press the
C and D key simultaneously for 5 seconds. The value of
the timer becomes 0 and the warning is reset.
NOTE
The parameters b01, b02 and b03 can also be
consulted by the "sensor readout menu". Refer to
"How to consult the "sensor readout menu"
parameters" on page 12.
To reset the timers of parameters c10, c11 and
c15 refer to "Resetting warnings" on page 13.
In case the unit is equipped with freeze protection, it is
highly recommended to install the remote indicator
lamp alarm (H3P) (see wiring diagram supplied with
the unit). By doing so, breakdown of the fuse for the
evaporator heatertape (F4) will be detected sooner
and freezing of the circuit will be avoided during cold
weather.
NOTE
If the alarm codes fl and h1 are flashing alternately,
the alarm is most probably caused by the reverse
phase protector or by the fuse for evaporator heater-
tape (F4) that was blown.
NOTE
Do not forget to carry out the required maintenance
activities after resetting the timers.
Besides resetting timer c10 and c11, it is also
possible to reset timer c15 (running hours of pump)
in the same way.
4PW61653-1_digital_EN.book Page 13 Thursday, August 26, 2010 1:49 PM
16

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Daikin EUWA water chillers bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Daikin EUWA water chillers in de taal/talen: Engels als bijlage per email.

De handleiding is 2,89 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

loading

Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info