EUWA(*)5~24KBZW1
Packaged air-cooled water chillers
4PW61653-1 – 07.2010
Installation and operation manual
8
Charging water
For all versions
1 Connect the water supply to the drain and fill valve
2 Open the pressure regulating valve (only for EUWAP and
EUWAB) and shut-off valves
3 Use the air purge valves on the unit and purge valves installed in
the highest places in the circuit to remove all air when filling the
system
Only for EUWAP, EUWAB versions
Water must be filled until the system reaches the required
pressure (Pr). The pressure can be read on the manometer.
The value of the required water pressure (Pr) is depending on the
total water volume in the system and the pressure in the expansion
vessel (see previous chapter).
Refer to figure 7 – Required water pressure in function of water
volume and pre-pressure:
1. Calculate the total water volume in the entire system.
2. Check in figure 7 where the horizontal line of the set prepressure
(Pg) cuts the vertical line of the system water volume.
3. At the cutting point, read the required water pressure (Pr) from the
lines in the figure.
Example 1
Total system water volume=130 l
Highest point of circuit above the EUWA=5 m
Pg=(5/10+0.3)=0.8 bar
Pr=±2.0 bar
Example 2
Total system water volume=190 l
Highest point of circuit above the EUWA unit=5 m
Pg=(5/10+0.3)=0.8 bar
Pr=±1.7 bar
PIPING INSULATION
The complete water circuit, inclusive all piping, must be insulated to
prevent condensation and reduction of the cooling capacity.
FIELD WIRING
Parts table
Refer to the wiring diagram supplied with the unit.
Following parts are to be connected during installation:
N ............................Neutral
P.............................Main earth terminal
F1,F2,F3 ................Main fuses (field supply, obligatory)
H3P........................Indication lamp alarm (field supply, not
obligatory)
H5P,H6P.................Indication lamp compr circuit 1, circuit 2 (field
supply, not obligatory)
S7S ........................Switch for cool/heat selection or dual setpoint
selection (field supply, not obligatory)
S9S ........................Switch for remote start/stop selection or dual
setpoint selection (field supply, not obligatory)
E5H........................Field heater (field supply, optional)
X2M (E5H) .............Terminal for field heater connection (optional)
--- ...........................Field wiring
Power circuit and cable requirements
A power circuit must be provided for connection of the unit. This
circuit must be protected with the required safety devices, i.e. a slow
blow fuse on each phase and an earth leak detector. For maximum
cable section (mm
2
) refer to the table.
Connection of the power supply
1 Using the appropriate cable, connect the power circuit to the N,
L1, L2 and L3 terminals of the main switch as shown on the
wiring diagram.
2 Connect the earth conductor (yellow/green) to the earthing
terminal PE.
A Water volume (l)
B Installation height difference (m)
C Pre-pressure
D Factory setting (1.5 bar)
NOTE
In this example it is allowed to keep the pre-pressure
factory setting from 1.5 bar. In this case the initial
water-pressure must be ±2.2 bar
NOTE
In this example it is not allowed to keep the pre-
pressure factory setting from 1.5 bar.
NOTE
A terminal is foreseen in the switchbox on which a
heater (tape) can be connected for preventing the water
piping from freezing during the cold weather months.
Refer to the wiring diagram supplied with the unit.
All field wiring and components must be installed by a
licensed electrician and must comply with relevant Euro-
pean and national regulations.
The field wiring must be carried out in accordance with the
wiring diagram supplied with the unit and the instructions
given below.
Be sure to use a dedicated power circuit. Never use a
power supply shared by another appliance.
Description Legend 5~24 Hp
Powerlines L1, L2, L3, N 10
Main earth cable PE 10
NOTE
Select the power cable in accordance with relevant
local and national regulations.
Switch off the main isolator switch before making any
connections.
For units equipped with freeze protection:
Keep in mind that the heaters are automatically switched
off when the main isolator switch is switched off. For this
reason the main switch should be switched on during the
cold weather months.
4PW61653-1_digital_EN.book Page 8 Thursday, August 26, 2010 1:49 PM
11

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Daikin EUWA water chillers bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Daikin EUWA water chillers in de taal/talen: Engels als bijlage per email.

De handleiding is 2,89 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

loading

Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info