TDMA CONTROL 601/701:
7
Published 07/2007
System variation 1
Return flow tempe-
rature raising
No function, Solid
fuel boiler,
T-Pro
Return flow sensor
No winter switch
over
System variation 2, 3
Heating regulation
Inflow sensor
CONTROL 701
Regulator Setting
Sensor
System variation
1,2,3
Heating regulation
Inflow sensor
Solar Difference:
2...12 K
The temperature difference by which the collector sensor
temperature must be higher than the lower thermal store
temperature to enable solar loading of the thermal store is
set using the „Solar Difference“ function. A lower value
can be set if the pipe diameters are small and the insula-
tion is good. Long pipe runs, larger diameter pipework,
poor insulation or unfavourable sensor positioning require
a higher temperature difference.
Example:
With 15 mm diameter pipes, 20 m pipe run, an electri-
cally economic pump and good pipe insulation a value
of 6K can be set. Using a setting of 6K the solar pump
will switch on when the collector sensor temperature is at
least 6K higher than the lower thermal store temperature.
When the temperature difference between the collector
and the lower thermal store drops below 4K (hysteresis
of 4K set in the factory) the solar pump will switch off.
Solar pump: Inputs – Function - Output
Input
Function
Collector sensor
(in delivery package)
Top loading (Stratified
loading function)
Solar difference
Maximum solar input
Lower thermal store sensor
(in delivery package)
Solar difference
Maximum solar input
Inflow / Return flow sensor
(Art. N
o
. RE 046)
Winter switch over
Output: Solar pump
2.3.2 East-West-Valve-Regulation
A system which includes two solar collector array areas,
one oriented east and one oriented west, can be regulated
using the „East-West- Valve“ function.
Solar Difference 2:
2...12 K
The „Solar Difference 2“ function is used to set the tem-
perature difference by which the temperature registered at
the sensor on the second collector must be higher than the
temperaure at the lower thermal store sensor before solar
loading of the thermal store can begin. The „East-West-
Valve“ switches a three way valve to AB-A to divert the
warm water flow to the second collector when the second
collector is 3K warmer than the first collector.
East-West-Valve: Input - Function - Output
Input
Function
Collector sensor 2
(Art. N
o
. RE 040)
Solar difference 2
Maximum solar input
Output: East-West-Valve
2.3.3 Cooling, Twin Thermal Store and Swimming Pool
Regulating
It is possible to choose between the following functions us-
ing Optional Function 1: Cooling / Cooling via the heat-
ing circuit / Twin thermal store prioritizing / Twin thermal
store balancing / Swimming pool.
These functions prevent overheating of the collectors or al-
low a second thermal store to be loaded with hot water.
The solar pump continues to run while the thermal store
cools down, as long as the maximum collector or thermal
store temperature is not exceeded.
Cooling Optional Function:
If the upper thermal store temperature reaches the preset
value „cooling“ is activated. This function can be used for
example to control a thermal store loading pump to cool
the thermal store or to divert the heated water to another
thermal store.
Cooling temperature:
30...90 °C
The required cooling temperature can be set here.
Hysteresis:
2...10 K
The switch hysteresis for cooling can be set here.
For example, if a temperature of 85 °C and a hysteresis of
5 K is chosen, the contact will be closed at 85 °C and re-
opened at 80 °C.
Cooling via Heating Circuit Optional Function:
This function allows the thermal store to be cooled via a
heating circuit when it reaches a set temperature. The
mixer and the heating circuit pump will operate automati-
cally.
Setting the cooling temperature and hysteresis are de-
scribed under „Cooling Optional Function“.
Heating Circuit Inflow Temp: Target:
30...90 °C
The required heating circuit target inflow temperature can
be set here.
Optional Function Twin Thermal Store Prioritizing: When
the upper thermal store sensor reaches the preset tempera-
ture the „twin thermal store“ function is activated. This acti-
vates a three way valve so that the heat flow is diverted to
another thermal store, and simultaneously switches from
7

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Consolar Control 601 bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Consolar Control 601 in de taal/talen: Engels als bijlage per email.

De handleiding is 5,12 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

loading

Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info