694420
12
Verklein
Vergroot
Pagina terug
1/24
Pagina verder
12
®
INSTALLATION INSTRUCTIONS
CHIMNEY
In order for the appliance to perform satisfactorily the chimney
height must not be less than 4 metres measured vertically from the
outlet of the stove to the top of the chimney. The internal dimensions
of the chimney should preferably be 150-200 mm (6”- 8”) either
square or round and MUST NOT BE LESS THAN 125 mm (5”) -
Skye 5 or 150 mm (6”) - Skye 7.
If an existing chimney is to be used it must be swept and checked,
it must be in good condition, free from cracks and blockages, and
should not have an excessive cross sectional area. If it was previously
used by an open fire then the chimney should be swept one month
after installation to clear any soot falls which may have occurred due
to the difference in combustion between the stove and the open fire.
If you find that the chimney is in poor condition then expert advice
should be sought regarding the necessity of having the chimney lined.
If it is found necessary to line the chimney then a lining suitable for
Solid Fuel must be used.
If there is no existing chimney then a prefabricated block chimney
or a twin walled insulated stainless steel flue to BSEN 15287-1:2007
can be used either internally or externally. These chimneys must be
fitted in accordance with the manufacturers instructions and Building
Regulations.
Single wall flue pipe is suitable for connecting the stove to the chimney
but is not suitable for using for the complete chimney. If it is found
that there is excessive draw in the chimney then a draught stabiliser
should be fitted.
It is important that there is sufficient draw in the chimney and that the
chimney does not suffer from down-draught. When the chimney is
warm the draw should be not less than 1.25mm (0.05”) water gauge
(12 Pa). If in doubt about the chimney seek expert advice.
HEARTH AND FIRE SURROUND
The stove must stand on a fireproof hearth and must not be situated
closer than the minimum distance from combustible materials (see
specification table) to the sides or rear above hearth level unless
adequately fireproofed in accordance with local building regulations.
The hearth must be of fireproof material and at least 12mm (1/2in.)
thick. The positioning of the stove and the size of the hearth are
governed by building regulations for Class 1 appliances. These
building regulations state that the hearth must extend in front of the
stove by at least 225mm (9 in.) and to the sides of the stove by at
least 150mm (6 in.). When the fire door is open, it extends beyond
the flat front of the stove by 430mm - Skye 5 or 480mm - Skye 7.
If in doubt as to the positioning of the stove, expert advice should be
sought either from the supplier or the local building inspector. The
fireplace must allow good circulation of air around the appliance to
ensure that maximum heat is transferred to the room and also to
prevent the fireplace from overheating. A gap of 150mm (6”) each
side and 300mm (12”) above the appliance should give sufficient air
circulation. If a wooden mantelpiece or beam is used in the fireplace
it should be a minimum of 460mm (18”), and preferably 600mm
(24”) from the appliance. In some situations it may be necessary to
shield the beam or mantelpiece to protect it.
In order for the fire to operate correctly and to allow for access,
there must be an air gap behind the appliance of at least 50mm, but
be aware that this distance will need to be greater in some cases to
meet Building Regulation requirements.
The appliance should be installed on a floor with adequate load-
bearing capacity. If an existing construction does not meet this
requirement then please take suitable measures to achieve this. (e.g.
load distributing plate.)
CONNECTIONS TO FLUES
The stove must be connected to the flue using flue pipe of the
following sizes:
125mm (5”) diameter - Skye 5. 150mm (6”) diameter - Skye 7.
This may be stainless steel, cast iron, or thick wall steel pipe. Straight
lengths of Charnwood Pipe to match the stove are available if
required. If using twin wall flue, the flue spigot must be shielded
to protect exposed combustible material. This can be done with a
shielded starter length of flue.
There are several ways of connecting the stove to the flue. These are
illustrated in Figs. 7 to 10.
If the top flue connection or optional vertical rear flue connector is
used then the chimney may be swept through the appliance.
A spacer (part 77, pages 20-21) is required to attach the optional
vertical rear flue connector to the Skye 7.
Horizontal lengths of flue must be kept to a minimum and should not
be more in length than the flue diameter.
The stove comes with the blanking plate (fig. 11) fitted to the top
12

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Charnwood Skye 5 bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Charnwood Skye 5 in de taal/talen: Engels als bijlage per email.

De handleiding is 3.53 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

loading

Andere handleiding(en) van Charnwood Skye 5

Charnwood Skye 5 Gebruiksaanwijzing - Français - 20 pagina's


Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info