USER MANUAL
PELLET THERMOSTOVE
Original Instructions | ©2022 CADEL srl | All rights reserved - Tutti i diritti riservati
new
RIVER IDROTECH 18 - RIVER IDROTECH 24
RIVER IDROTECH 24H2O
RIVER IDROTECH 18 - 24 - 24H2O
2
SUMMARY
1 MANUAL SIMBOLOGY .................................... 3
2 DEAR CUSTOMER ..........................................3
2.1 REVISIONS TO THE PUBLICATION ............................4
2.2 CARE OF THE MANUAL AND HOW TO CONSULT IT ... 4
3 SAFETY REQUIREMENTS ............................5
4 CAUTIONS  WARRANTY CONDITIONS .............6
4.1 INFORMATION .........................................................6
4.2 INTENDED USE ........................................................6
4.3 PRODUCT PERFORMANCE CHECKS. .........................6
4.4 WARRANTY CONDITIONS ........................................7
5 SPARE PARTS ...............................................8
6 DISPOSAL OF MATERIALS ..............................8
6.1 WARNINGS FOR THE CORRECT DISPOSAL OF THE
PRODUCT ...........................................................................8
6.2 INFORMATION FOR MANAGEMENT OF ELECTRIC AND
ELECTRONIC APPLIANCE WASTE CONTAINING BATTERIES OR
ACCUMULATORS ................................................................9
6.3 INSTRUCTIONS FOR PACKAGING DISPOSAL ............9
7 WIFI  BLUETOOTH CONNECTION ................10
7.1 EASY CONNECT PLUS ............................................. 10
8 USE ...........................................................11
8.1 INTRODUCTION .....................................................11
8.2 CONTROL PANEL DISPLAY .....................................11
8.3 MAIN MENU ..........................................................12
8.4 SETTINGS MENU ....................................................12
8.5 INFO MENU ...........................................................16
8.6 IGNITION OF THE STOVE ........................................17
8.7 FAILED IGNITION ...................................................17
8.8 SWITCH OFF ON PANEL: OFF WITH FLASHING
FLAME ............................................................................17
8.9 POWER FAILURE .................................................... 17
8.10 ADJUSTMENTS MENU ...........................................18
8.11 PROGRAMMED MODE TIMER  MAIN MENU ......18
8.12 PROGRAMMING EXAMPLES: .................................19
8.13 NOTES FOR TIMER OPERATION .............................. 19
8.14 AUTO ECO MODE SEE SECTION FG ..................... 19
8.15 SLEEP FUNCTION MAIN MENU ...........................19
8.16 EASY SET FEATURE SEE SECTION X SETTINGS MENU
A PAG. 12 .......................................................................20
8.17 PELLETS RECIPE SEE SECTION J SETTINGS MENU A
PAG. 12 .......................................................................... 21
8.18 SMOKE RPM VARIATION SEE SECTION K SETTINGS
MENU A PAG. 12 ........................................................... 21
8.19 CHIMNEY SWEEP FUNCTION FOR MAINTENANCE
TECHNICIANS ONLY  SEE SECTION N SETTINGS MENU A
PAG. 12 ..............................................................21
9 FUEL ..........................................................21
9.1 FUEL ......................................................................21
9.2 PELLET SUPPLY .....................................................22
9.3 PELLET REFUELLING TIMER ...................................22
10 SAFETY DEVICES AND ALARMS ....................23
10.1 PRESSURE SWITCH ................................................ 23
10.2 SMOKE TEMPERATURE PROBE ..............................23
10.3 CONTACT THERMOSTAT IN THE FUEL HOPPER.......23
10.4 ELECTRICAL SAFETY .............................................. 23
10.5 SMOKE FAN ...........................................................23
10.6 GEAR MOTOR ......................................................... 23
10.7 TEMPORARY POWER CUT ......................................23
10.8 FAILED STARTUP .................................................. 23
10.9 BLACKOUT WITH THE BOILER ON ..........................24
10.10 CONTACT THERMOSTAT IN THE BOILER .................24
10.11 WATER TEMPERATURE PROBE...............................24
10.12 ANTIFREEZE FUNCTION ......................................... 24
10.13 PUMP ANTISEIZURE FUNCTION ........................... 24
10.14 CLEANER BLOCKED ................................................ 24
10.15 ALARM ALERTS .....................................................25
10.16 ALARM RESET .......................................................26
11 ROUTINE MAINTENANCE .............................26
11.1 INTRODUCTION .....................................................26
11.2 BEFORE EACH STARTUP .......................................26
11.3 HOPPER CLEANING ...............................................27
11.4 FUME PIPES ANNUAL CLEANING ..........................27
11.5 GENERAL CLEANING ..............................................27
11.6 CLEANING OF PAINTED METAL PANELS ................27
11.7 CLEANING OF CERAMIC AND STONE PANELS ........27
11.8 GASKET REPLACEMENT ......................................... 27
11.9 GLASS CLEANING ..................................................27
11.10 ASH DRAWER CLEANING IDRO ..............................28
11.11 CLEANING THE EXCHANGER AND THE COMPARTMENT
UNDER THE BRAZIER EVERY 7 DAYS MAX ........................ 28
11.12 PIPE UNIT CLEANING .............................................29
11.13 SHUTDOWN END OF SEASON .............................29
11.14 CHECKING THE INNER COMPONENTS ....................30
12 IN CASE OF ANOMALY ..................................30
12.1 PROBLEM SOLVING ...............................................30
12.2 PROBLEM SOLVING THERMOSTOVE ...................33
13 TECHNICAL DOCUMENTATION FOR LOCAL SPACE
HEATERS ACCORDING TO COMMISSION REGULATIONS
EU 2015/1185  EU 2015/1186 PRODUCT FICHE
.................................................................35
3
RIVER IDROTECH 18 - 24 - 24H2O
1 MANUAL SIMBOLOGY
USER
AUTHORISED TECHNICIAN
(ONLY to interpret or the Stove-manufacturer or the Authorized Technician of
Technical Assistance Service approved by the Stove-manufacturer)
SPECIALIZED STOVE-REPAIRER
CAUTION:
READ CAREFULLY THE NOTE
CAUTION:
DANGER OR IRREVERSIBLE DAMAGE POSSIBILITY
The icons with the stylized figures indicates whom the subject dealt in the paragraph is addressed to (between the User and/
or the Authorized Technician and/or the Specialized Stove-repairer).
WARNING symbols indicates an important note.
2 DEAR CUSTOMER
Dear Customer,
Our products are designed and manufactured in accordance with standards in force, with high quality materials and using our
extensive experience in the transformation processes.
To get the best performance, we suggest you read the instructions in this manual carefully.
This installation guide is an integral part of the product: ensure that the manual is always supplied with the appliance, even if it
changes owner. If the manual is lost, you can request another copy from the local Technical Dept. or download it directly from the
company’s website.
All local regulations, including those referring to national and European standards, must be observed when installing the appliance.
In Italy, for the installation of systems with a biomass below 35KW, refer to the Ministerial Decree 37/08 and the qualified instal-
lation technician with the suitable requirements must issue a certificate of compliance for the system installed. (By system we
intend Stove+Flue+Air inlet).
Our solid bio-combustible products, (hereinafter called “Products”) are designed and manufactured in compliance with one of the
following European standard harmonised to Regulation (UE) no. 305/2011 for construction products:
EN 14785: “Residential space heating appliances fired by wood pellets”
EN 13240: “Room heaters fired by solid fuel.
EN 13229: “Inset appliances including open fires fired by solid fuels
EN 12815: “Residential cookers fired by solid fuel”
The products also comply with the essential requirements of Directive 2009/125/EC (Eco Design) and, where applicable, Direc-
tives:
2014/35/EU (LVD - Low Voltage directive)
2014/30/EU (EMC - Electromagnetic Compatibility directive)
2014/53/EU (RED - Radio Equipment directive)
2011/65/EU (ROhS)
Hereby CADEL S.r.l. declares that the radio equipment type Easy Connect Plus + Navel Stand Alone is in compliance with
Directive 2014/53/EU.
According to (EU) No. 305/2011 regulation, the " Declaration of Performance" and "Declaration of Conformity" are available online,
in the download area, at the web sites:
RIVER IDROTECH 18 - 24 - 24H2O
4
- www.cadelsrl.com
- www.free-point.it
- www.pegasoheating.com
Having specified the above, we highlight and report that:
This manual and technical data sheet, also available on our website, bear all of the specific indications and necessary
and essential information to choose the product, to install it correctly and to properly size the smoke expulsion system;
the Products must be installed, controlled and serviced by a qualified operator, according to the instructions in this ma-
nual and in compliance with the laws and installation and maintenance standards in force in individual countries, so as to
provide an efficient heating system, properly sized according to the needs of the home.
If the Products are thermally stressed, constantly operating for several hours at high power (e.g. 3, 4 hours a day at ou-
tputs P4 or P5), we recommend more frequent cleaning and reducing the interval between routine maintenance operations
according to the operating condition of the product. We furthermore point out that these operating conditions increase the
risk of premature wear of the product, especially those parts exposed to the direct heat of the fire (e.g. combustion chamber),
the original condition of which can undergo modifications and deterioration which, among other things, could generate noise
during operation of the unit due to mechanical expansion.
The manufacturer will not be held liable if the above information is ignored.
2.1 REVISIONS TO THE PUBLICATION
The content of this manual is strictly technical and the property of CADEL S.r.l.
No part of this manual may be translated into other languages, adapted and/or reproduced, even in part, in other mechanical and/
or electronic form or media, for photocopies, recordings or other, without the prior written authorisation of CADEL S.r.l.
The company reserves the right to make changes to the product at any time without prior notice. The owner company reserves its
rights according to law.
2.2 CARE OF THE MANUAL AND HOW TO CONSULT IT
Take care of this manual and store it in an easily and quickly accessible place.
Should this manual be lost or destroyed, request a copy from your retailer or directly from the authorised Technical assistance
department. It can also be downloaded from the company’s website.
“Bold text” requires special attention.
5
RIVER IDROTECH 18 - 24 - 24H2O
3 SAFETY REQUIREMENTS
Installation, electrical connection, functional verification and maintenance must only be
performed by qualified or authorised personnel.
Live electrical parts: disconnect the product from the 230V power supply before perfor-
ming any maintenance operation. Only power the product after completing assembly.
Special maintenance must only be performed by authorised and qualified personnel.
All local regulations, including those referring to national European standards, must be
respected during appliance installation.
The manufacturer declines any responsibility in case of installation which are not in com-
pliance with current regulations, in case of a wrong room ventilation system, in case of an
electric connection which is not in compliance with regulations and in case of a wrong use of
the appliance.
It is forbidden to install the stove in bedrooms, bathrooms and in rooms used for storing
combustible materials and in one-room flats.
The installation in one-room flats is allowed if they are in sealed chamber.
In any case the stove must not be installed in rooms where it can get in touch with water or
water splashes because this can cause burn hazards and short-circuit.
Please check that the floor has an adequate load capacity. If the existing one does not
satisfy this requirement, appropriate measure should be provided (for example a plate for di-
stributing the load).
For safety fire regulations the distances from flammable or sensible to heat objects (sofas,
pieces of furniture, wooden covering, etc...) must be respected.
If there are highly flammable objects (curtains, fitted carpet, etc...), all these distances
must be further increased with 1 meter.
If the floor is made of combustible material, we recommend using a protector made of in-
combustible material (steel, glass, etc.) that also protects the front part from any falling burnt
particles during cleaning.
The electrical cable must not get in touch with the fume exhaust pipe and nor with every
other part of the stove.
The user, or whoever is operating the product, must read and fully understand the contents
of this installation and use guide before performing any operation. Errors or incorrect settings
can cause hazardous conditions and/or poor operation.
The type of fuel to use is only the pellets.
Do not use the appliance as waste inceneretor.
Do not place laundry on the product to dry. Any clothes horses or similar objects must be
kept at a safe distance from the product. Fire hazard.
It is forbidden to operate the product with the door open or the glass broken.
It is forbidden to modify the appliance without authorization.
Do not use flammable liquids during the ignition (alcool, petrol, oil, etc...).
After a failed ignition the burning pot must be empty from the amassed pellets, before
starting the stove up again.
The pellet hopper must always be closed with its own lid.
Before of every intervention leave the fire completely extinguish till the cooling and always
disconnect the plug from the electric socket.
This appliance can be used by children aged from 8 years and above and persons with re-
duced physical, sensory or mental capabilities or lack of experience and knowledge if they
have been given supervision or instruction concerning use of the appliance in a safe way and
understand the hazards involved. Children shall not play with the appliance. Cleaning and
user maintenance shall not be made by children without supervision.
Packaging are not toys and could cause suffocation or strangulation and other health ha-
zards! People (childreen included) with reduced mobility, psycological deseases or without
RIVER IDROTECH 18 - 24 - 24H2O
6
experience and knowledge must be kept away from packaging. The stove IS NOT a toy.
Childreen must be constantly overseen in order to assure that they do not play with the
appliance.
During its running, the stove reaches high temperatures: keep away childreen and animals
and for your safety please use appropriate fireproof devices, such as heat-protecting gloves.
The stove is equipped with a safety device that stops the feed screw immediately when the
pellet loading door is opened. This safety device (standard EN 60335-2-102) prevents the user
from coming into contact with the moving parts of the appliance.
The chimney flue must be cleaned, since the soot and unburnt oil deposits reduce its sec-
tion so blocking the draught. In great quantities they can flare up.
If the pellets are of bad quality (if contains sizing agents, oils, varnishes, plastic remains or
if it is mealy), deposits will form along pellets drop pipe during the running. When the stove is
switched off, these remains could form little hot coals that rising along the pipe could reach the
pellets on the hopper burning them and creating a thick and harmful smoke inside the room.
Please always keep the hopper closed with its own lid. If the pipe is sooty, please clean it.
In case it would be necessary to extinguish the fire emitted by the stove or by the chimney
flue, use a fire-extinguisher or contact the firemen. DO NOT use water to extinguish the fire
inside the burning pot.
Remote control (if present): keep the batteries out of the reach of children, risk of swal-
lowing. If swallowed, seek medical advice immediately.
Pellets must not be fed manually into the burner - this wrong behaviour can generate an
abnormal amount of unburned gas, with a risk of explosion in the chamber.
4 CAUTIONS  WARRANTY CONDITIONS
4.1 INFORMATION
Please contact the retailer or qualified personnel for any information, problem or malfunction.
Only use the fuel specified by the manufacturer.
When the product is switched on for the first time, it is normal for it to emit smoke due to the paint heating up for the first time.
Therefore make sure the room it is installed in is well-ventilated.
Periodically check and empty the inspectionable parts of the smoke duct (e.g. Tee fitting caps)
Have the smoke outlet system periodically checked and cleaned
The product is not a cooking appliance.
Always keep the cover of the fuel hopper closed.
Store this installation and user manual with care as it must accompany the product for the duration of its useful life. If the
product is sold or transferred to another user, always ensure the manual is also handed over.
4.2 INTENDED USE
The product only works with wood pellets and must be installed inside a room.
4.3 PRODUCT PERFORMANCE CHECKS.
All our products undergo ITT TESTS carried out by a notified third party laboratory (system 3) and in accordance with Regulation
(EU) number 305/2011 “Construction products”, according to standard EN 14785:2006 for household appliances and “Machinery
Directive EN 303-5 for boilers.
In the case of tests for any market surveillance or inspections by third parties, please consider the following warnings:
To reach the declared performance levels, the product must perform an operating cycle of at least 6/8 hours beforehand.
Set the average draught of the combustion fumes as specified in the “technical product features” table
The type of pellets used must comply with the current EN ISO 17225-2 class A1 regulation. Fir pellets are usually used for
certification.
The amount of thermal energy can vary according to the length and calorific value of the fuel. This may require some adjustments
(accessed from the user menu) to comply with the hourly consumption specified in the “technical product features” table.
Using class A1 pellets guarantees a calorific value that is likely to be close to that used in the product certification; the size of
the pellet grains can significantly affect hourly fuel loading and consequently performance; it is therefore suggested to use
pellets with a 6 mm diameter and an average length of around 24 mm (avoid pellets that are too long or excessively crushed).
7
RIVER IDROTECH 18 - 24 - 24H2O
With wood-burning appliances, the fuel must comply with the current EN ISO 17225-5 class A1 regulation. Check the correct
moisture of the fuel, as it must be within the range of 12 - 20% (it is best if the moisture is close to 12%, as is normally used in
certification). As the fuel moisture increases, different combustion air settings are required, which are implemented from the
combustion air register, thereby modifying the mixture of primary and secondary air
It is important to check the operation of devices that can affect performance (for example air fans or electric safety devices) in
case of damage due to handling.
Nominal performance has been obtained by setting the maximum flame power and room ventilation in automatic mode.
4.4 WARRANTY CONDITIONS
The duration, conditions and limitations of CADEL S.r.l. can be found on the guarantee card enclosed with the device.
The company guarantees the product, with the exception of elements subject to normal wear listed below, for a period of
2 (two) years from the date of purchase attested by:
a document to serve as proof of purchase (invoice and/or receipt) that shows the name of the vendor and the date on which
the purchase was made;
forwarding of the completed certificate of guarantee within 8 days of purchase.
Furthermore, the product must be installed and started by specialised personnel who must, where provided, issue a declaration of
conformity of the plant and of the proper functioning of the product, for the warranty to be valid and effective.
We recommend testing the product before completion with the relative finishes (claddings, painting of walls, etc.).
Installations not meeting the current standards, improper use and lack of maintenance as expected by the manufacturer, void the
product warranty.
The guarantee is valid on the condition that the instructions and warnings contained in the use and maintenance manual are
observed, and therefore the product is used correctly.
The replacement of the entire system or the repair of one of its components does not extend the guarantee period, and the original
expiry date remains unchanged.
The guarantee covers the replacement or free repair of parts recognised as being faulty at source due to manufacturing
defects.
To benefit from the guarantee, in the event of a fault, the customer must have the guarantee certificate and present it with the
proof of purchase document to the Technical Assistance Office.
The guarantee does not cover malfunctions and/or damage to the appliance that arise due to the following causes:
Damage caused during transportation or relocation.
All parts that develop faults due to negligence or improper use, incorrect maintenance, installation that does not comply with
the manufacturer's instructions (always refer to the installation and use manual provided with the appliance).
Incorrect dimensioning with regards to the use or faults in the installation or failure to adopt the necessary devices to guaran-
tee proper execution.
Improper overheating of the equipment, use of fuels not conforming to the types and quantities indicated in the instructions
provided.
Further damage caused by incorrect user interventions in an attempt to fix the initial fault.
Worsening of the damage due to the continued use of the equipment by the user, once the defect has been noticed.
In the presence of a boiler, any corrosions, incrustations or breaks caused by water flow, condensation, hardness or acidity of
the water, improperly performed descaling treatments, lack of water, mud or limescale deposits.
Inefficiency of chimneys, flues or parts of the plant affecting the equipment.
Damage caused by tampering with the appliance, atmospheric agents, natural disasters, vandalism, electrical discharges, fires,
faults in the electric and/or hydraulic system.
Failure to have the stove cleaned on an annual basis by an authorised technician or qualified personnel will result in the loss
of the warranty.
Also excluded from this guarantee are:
Parts subject to normal wear such as gaskets, glass, claddings and cast iron grids, painted, chrome-plated or gilded parts,
handles and electric cables, bulbs, indicator lights, knobs, all parts which can be removed from the hearth.
Variations in colour of the painted or ceramic/serpentine parts and craquelure ceramics as they are natural characteristics of
the material and product use.
Masonry work.
Plant parts (if present) not supplied by the manufacturer.
Any technical interventions on the product to eliminate the above-said defects and consequent damages must be agreed upon
with the Technical Assistance Centre, who reserves the right to accept the relative appointment or not. However, said interventions
will not be carried out under warranty but as technical assistance to be granted at part of any eventual and specific agreed condi-
RIVER IDROTECH 18 - 24 - 24H2O
8
tions and in accordance with the fee in force for the work to be carried out.
The user will also be charged for any costs incurred to remedy the incorrect technical interventions, tampering or damage to the
appliance, not attributable to original faults.
Save for the legal or regulatory limits, the guarantee does not cover the containment of atmospheric and acoustic pollution.
The company declines all liability for any damage which may be caused, directly or indirectly, to persons, animals
or objects as a consequence of non compliance with any prescription specified in the manual, especially warnings
regarding installation, use and maintenance of the appliance.
5 SPARE PARTS
For each repair or adjustment which should be necessary, please contact the dealer where you purchased your stove or your nea-
rest Technical Assistance Service, specifying:
Appliance model
Serial number
Type of problem
Use only original spare parts which you can find at our Technical Assistance Services.
6 DISPOSAL OF MATERIALS
6.1 WARNINGS FOR THE CORRECT DISPOSAL OF THE PRODUCT
The owner is the sole party responsible for demolishing and disposing of the product. This must be performed in compliance with
laws related to safety and environmental protection in force in his/her country.
At the end of its working life, the product must not be disposed of as urban waste.
It must be taken to a special differentiated waste collection centre set up by the local authorities or to a retailer that provides this
service.
Separating and recycling prevents potential negative effects on the environment and health (often caused by inappropriately
disposing of product parts). It also allows materials to be recovered in order to obtain significant savings in energy and resources.
The following table and the exploded view it refers to highlight the main components that can be found in the device and indica-
tions on how to separate and dispose of them correctly when no longer used.
More specifically, the electric and electronic components must be separated and disposed of in authorised centres, in compliance
with the WEEE directive 2012/19/EU and the relative national transpositions.
Fig. 1 - Exploded drawing
9
RIVER IDROTECH 18 - 24 - 24H2O
LEGENDA WHERE TO DISPOSE MATERIALS
A. OUTER CLADDING If there is any, to be disposed of separately based on
the material used:
Metal
Glass
Tiles or ceramics
Stone
B. GLASS DOORS If there is any, to be disposed of separately based on
the material used:
Glass ceramic (fire door): to be disposed of with
inert or mixed waste
Tempered glass (oven door): to be disposed of with
glass
C. INTERIOR CLADDING If there is any, to be disposed of separately based on
the material used:
Metal
Refractory materials
Insulating panels
Vermiculite
Insulation, vermiculite and refractory materials
that have come into contact with flames or exhaust
gases (dispose of in mixed waste)
D. ELECTRIC AND ELECTRO-
NIC COMPONENTS
To be disposed of separately in authorised centres,
as indicated in the WEEE directive 2012/19/EU and
the relative national transposition.
Wiring, motors, fans, circulators, display panels,
sensors ignition plug, electronic cards, batteries.
E. METAL STRUCTURE To be disposed of separately with metal -
F. COMPONENTS THAT CAN-
NOT BE RECYCLED To be disposed of with mixed waste E.G.: Gaskets, rube piping, silicone or fibres, plastic.
G. HYDRAULIC COMPONENTS Piping, fittings, expansion vessel, valves. If there
are any, to be disposed of separately based on the
material they are made of:
Copper
Brass
Stainless steel
Other materials
6.2 INFORMATION FOR MANAGEMENT OF ELECTRIC AND ELECTRONIC APPLIANCE WASTE CON
TAINING BATTERIES OR ACCUMULATORS
Fig. 2 - Waste disposal
This symbol, which is used on the product, batteries, accumulators or on the packaging or documents, means that at the end of its
useful life, this product, the batteries and the accumulators included must not be collected, recycled or disposed of together with
domestic waste.
Improper management of electric or electronic waste or batteries or accumulators can lead to the leakage of hazardous substances
contained in the product. For the purpose of preventing damage to health or the environment, users are kindly asked to separate
this equipment and/or batteries or accumulators included from other types of waste and to arrange for disposal by the municipal
waste service It is possible to ask your local dealer to collect the waste electric or electronic appliance under the conditions and
following the methods provided by national laws transposing the Directive 2012/19/EU.
Separate waste collection and recycling of unused electric and electronic equipment, batteries and accumulators helps to save
natural resources and to guarantee that this waste is processed in a manner that is safe for health and the environment.
For more information about how to collect electric and electronic equipment and appliances, batteries and accumulators, please
contact your local Council or Public Authority competent to issue the relevant permits.
6.3 INSTRUCTIONS FOR PACKAGING DISPOSAL
The material that the appliances packaging is made of must be managed correctly, in order to make collection, reuse, recovery
and recycling easier, where possible.
The table below illustrates the possible components that the packaging is made of, and the relative instructions for correct disposal.
RIVER IDROTECH 18 - 24 - 24H2O
10
DESCRIPTION CODE MATERIAL SYMBOL DIRECTIONS FOR COLLECTION
- WOOD BED
- WOOD CAGE
- WOOD PALLET
WOOD
FOR 50
SORTED waste collection
WOOD
Check with the competent body on
how to dispose of this packaging at
the recycling depot
- CARDBOARD BOX
- CARDBOARD CORNER
- CARDBOARD SHEET
CORRUGATED CARDBOARD
PAP 20
SORTED waste collection
PAPER
Check the instructions of the com-
petent body
- APPLIANCE BAG
- BAG OF ACCESSORIES
- BUBBLE WRAP
- PROTECTIVE SHEET
- LABELS
POLYETHYLENE
LD PE 04
SORTED waste collection
PLASTIC
Check the instructions of the com-
petent body
- POLYSTYRENE
- FOAM PEANUTS POLYSTYRENE
PS 6
SORTED waste collection
PLASTIC
Check the instructions of the com-
petent body
- STRAP
- TAPE POLYPROPYLENE
PP 5
SORTED waste collection
PLASTIC
Check the instructions of the com-
petent body.
- SCREWS
- STAPLES FOR STRAP
- FASTENING BRACKET
IRON
FE 40
SORTED waste collection
METAL
Check with the competent body on
how to dispose of this packaging at
the recycling depot
7 WIFI  BLUETOOTH CONNECTION
7.1 EASY CONNECT PLUS
Procedure if only valid for models with EASY CONNECT PLUS Wi-Fi technology.
11
RIVER IDROTECH 18 - 24 - 24H2O
Fig. 3 - EASY CONNECT PLUS module Fig. 4 - EASY CONNECT PLUS display Fig. 5 - EASY CONNECT PLUS app
The documentation for connecting the Wi-Fi and using the App are available online at the following addresses:
https://www.cadelsrl.com/donwload-wi-fi/
http://www.free-point.it/it/downloads/
https://www.pegasoheating.com/it/documenti/
8 USE
8.1 INTRODUCTION
To have the best performance with the lowest consumption please follow the here descripted instructions.
The lightning of the pellets occurs very easily if the installation is correct and if the chimney flue is efficient.
Switch on the stove at Power 5, for at least 2 hours, in order to enable the materials which make up the boiler and the
fireplace to adjust the inner springing stress. After 2 hours, the smell of paint and smoke will disappear.
By using the stove the varnish inside the combustion chamber could be subjected to alterations. This occurrence can be attri-
buted to different reasons: an excessive stove overheating, the presence of chemical agents in bad quality pellets, bad chimney
draught, etc. Therefore varnish endurance in the combustion chamber cannot be guarantee.
Oily plant waste and lacquers can cause smells and smoke during the first working hours: it is advisable to
ventilate the room because they could be noxious to people and animals.
Set values from 1 to 5 are defined by the manufacturer and they can be changed only by an authorized tech-
nician.
The product will be subject to expansion and contraction during the ignition and cooling stages, therefore
slight creaking noises may be heard. This is perfectly normal as the structure is made of laminated steel and
must not be considered a defect.
8.2 CONTROL PANEL DISPLAY
Menu items.
RIVER IDROTECH 18 - 24 - 24H2O
12
Fig. 6 - Display Fig. 7 - Display Fig. 8 - Display
LEGEND Fig. 6|Fig. 7|Fig. 8
1Boiler lighting/shutdown (ESC)
2Scrolling of programming menu to decrease
3Menu
4Scrolling of programming menu to increase
5Decrease set temperature/programming functions
6Increase set temperature/programming functions
7Display
8Time
9Status
10 Temperature set by user
11 Instant power
12 Ambient temperature
13 If there is "." = 0.5 °C (29.° = 29.5°)
8.3 MAIN MENU
It is accessed by pressing key 3 (menu). The items that are accessed are:
Time and Date
Timer
Sleep (only with the stove on)
Settings
Info
Date and time setting
To set the date and time act as follows:
Press the “menu button.
Select “Time and Date”.
Select by pressing menu”
Scroll with the arrows and select the variables to be modified one at a time: Day, Hours, Minutes, Day number, Month, Year.
Select menu to confirm.
Modify with the + - keys.
Finally press “menu to confirm and esc to exit.
Timer setting (see relative chapter)
Sleep setting (see relative chapter)
8.4 SETTINGS MENU
The SETTINGS menu allows to act on the boiler operating mode:
a - Language.
b - Cleaning (displayed only when the boiler is switched off).
c - Feed screw loading (displayed only when the boiler is switched off).
d - Tones.
e - External thermostat (activation).
f - Auto Eco (activation).
g - Eco-Shutdown T (default 10 minutes).
h - Pump on T (default 50°C).
i - Auxiliary boiler (default deactivated).
x - Easy set.
13
RIVER IDROTECH 18 - 24 - 24H2O
j - Pellet recipe.
k - Smoke rpm % ventilation.
l - Maximum power (1-5 - default 5).
m - Components test (displayed only when the boiler is switched off)
n - “Chimney sweep function (activated only when the boiler is switched on, for field emissions test).
o - System configuration.
p - Season.
q - Technical menu.
NOTE: Some of the items listed above cannot be activated in certain system configurations”.
a - Language
To select the language act as follows:
Press the “menu button.
Scroll to “Settings” using the arrows
Press “menu to confirm.
Scroll to language using the arrows.
Press “menu to confirm.
With the + - keys select the language of interest (IT/EN/DE/FR/ES/NL/PL/DA)
Press “menu to confirm and esc” to exit.
b - Cleaning
To select “Cleaning (only when the boiler is switched off) act as follows:
Press the “menu button.
Scroll to “Settings” using the arrows
Press “menu to confirm.
Scroll to “Cleaning” using the arrows.
Press “menu to confirm.
Select On” with the + - keys.
Press “menu to confirm and esc” to exit.
c - Feed screw loading
Allows to fill the pellets loading system. It can only be activated with the boiler switched off, it displays an 180” countdown after
which the feed screw stops automatically, as when exiting the menu.
To select “Feed screw loading” (only when the boiler is switched off) act as follows:
Press the “menu button.
Scroll to “Settings” using the arrows
Press “menu to confirm.
Scroll to “Feed screw loading using the arrows.
Press “menu to confirm.
Select “Enable with the + - keys.
Press “menu to confirm and esc” to exit.
d - Tones
This function is disabled by default, so to enable act as follows:
Press the “menu button.
Scroll to “Settings” using the arrows
Press “menu to confirm.
Scroll to “tones” using the arrows.
Press “menu to confirm.
Select On” with the + - keys.
Press “menu to confirm and esc” to exit.
e - External thermostat (see relative chapter)
EXTERNAL THERMOSTAT (not included with the boiler, it is the user’s responsibility)
The stove can also be temperature-controlled by an external room thermostat. It is positioned centrally with respect to the room
where the appliance is installed and ensures greater consistency between the heating temperature requested of the stove and the
actual temperature the stove supplies.
Connect the wires from the external thermostat (INSTALLER MANUAL)
RIVER IDROTECH 18 - 24 - 24H2O
14
Once the thermostat is connected, it must be enabled.
Do so as follows:
Press the “menu button.
Scroll to “Settings” using the arrows.
Select by pressing menu”.
Scroll once again to “External thermostat” using the arrows.
Select by pressing menu”.
Press the - + buttons.
Select On” to activate the external thermostat.
Press the “menu button to confirm.
Press the esc button to exit.
f - Auto-Eco activation
To select the Auto-Eco function act as follows:
Press the “menu button.
Scroll to “Settings” using the arrows
Press “menu to confirm.
Scroll to Auto-Eco using the arrows.
Press “menu to confirm.
Select On” with the + - keys.
Press “menu to confirm and esc” to exit.
g - Eco Shutdown t
To select the Eco - shutdown t function act as follows:
Press the “menu button.
Scroll to “Settings” using the arrows
Press “menu to confirm.
Scroll to “Eco - shutdown t” using the arrows.
Press “menu to confirm.
Enter the minutes with the + - keys.
Press “menu to confirm and esc” to exit.
h - Pump On T
This menu item allows to adjust the pump activation temperature.
To select the Pump On T function act as follows:
Press the “menu button.
Scroll to “Settings” using the arrows
Press “menu to confirm.
Scroll to “Pump On T using the arrows.
Press “menu to confirm.
Modify the °C with the + - keys.
Press “menu to confirm and esc” to exit
i - Auxiliary boiler
An additional (optional) module must be installed to allow an auxiliary boiler to be switched on should the stove be off or in alarm
conditions. By default, this function is disabled; if necessary, activate it through the settings menu.
x - Easy Set
To select the "Easy Set" function act as follows:
Press the “menu button.
Scroll to “Settings” using the arrows
Press “menu to confirm.
Scroll to "Easy Set" using the arrows.
Press “menu to confirm.
With the + - keys select "Easy Set" of interest (SET1 - SET2 - SET3 - SET4)
Press “menu to confirm and esc” to exit.
15
RIVER IDROTECH 18 - 24 - 24H2O
j - Pellet Recipe
To change the recipe act as follows:
Press the “menu button.
Scroll to “Settings” using the arrows
Press “menu to confirm.
Scroll to “Pellet Recipe using the arrows.
Press “menu to confirm.
Modify the % with the + - keys.
Press “menu to confirm and esc” to exit
k - Smoke rpm % ventilation
To change the parameter act as follows:
Press the “menu button.
Scroll to “Settings” using the arrows
Press “menu to confirm.
Scroll to “Smoke rpm variation using the arrows.
Press “menu to confirm.
Modify the % with the + - keys.
Press “menu to confirm and esc” to exit
l - Maximum power
It allows to set the maximum flame limit at which the boiler can operate to reach the set temperature target.
To change the power act as follows:
Press the “menu button.
Scroll to “Settings” using the arrows
Press “menu to confirm.
Scroll to “Maximum power” using the arrows.
Press “menu to confirm.
Change the power from 01 to 05 with the + - keys
Press “menu to confirm and esc” to exit
m - Components test
It can only be carried out with the boiler switched off, it allows to select the components to be tested:
Spark plug: it is turned on for a fixed time of 1 minute during which the panel displays the countdown seconds.
Feed screw: it is powered for a fixed time of 1 minute during which the panel displays the countdown seconds.
Extractor: it is activated at 2500 rpm for a fixed time of 1 minute during which the panel displays the countdown seconds.
Exchanger: it allows to carry out the test in V5 for a fixed time of 1 minute during which the panel displays the countdown
seconds.
Pump: it is activated for a fixed time of 10 seconds during which the panel displays the countdown.
3 way: the 3 way valve is activated for a fixed time of 1 minute during which the panel displays the countdown seconds.
Cleaner: is activated for 2 cleaning cycles.
To activate the “Components test” function (only when the boiler is switched off) act as follows:
Press the “menu button.
Scroll to “Settings” using the arrows
Press “menu to confirm.
Scroll to “Components test” using the arrows.
Press “menu to confirm.
Select the test to be performed with the + - keys
Press “menu to confirm and esc” to exit
n - Chimney sweep function
This function can be activated only when the boiler is on and with power output and heating operation power with parameters
P5, with fan (if present) in V5. Any loading/smoke ventilation percentage corrections must be taken into account. This status lasts
20 minutes, the countdown is displayed on the panel. During this interval the thermostat/puffer/room set point/H20 set point are
not taken into account, only the safety shutdown at 85°C remains active. At any time the technician can interrupt this stage by
quickly pressing the on/off key.
To activate the “Chimney sweep function act as follows:
RIVER IDROTECH 18 - 24 - 24H2O
16
Press the “menu button.
Scroll to “Settings” using the arrows
Press “menu to confirm.
Scroll to the “Chimney sweep function using the arrows.
Press “menu to confirm.
Select On” with the + - keys (Off by default)
Press “menu to confirm and esc” to exit
o - System configuration
To change the system configuration act as follows:
Press the “menu button.
Scroll to “Settings” using the arrows
Press “menu to confirm.
Scroll to “System configuration” using the arrows.
Press “menu to confirm.
Change the configuration from 01 to 05 with the + - keys
Press “menu to confirm and esc” to exit.
p - Season
In configurations 2 and 3, by enabling the summer” function, the deviation of the 3-way valve to the heating system is inhibited
in order to prevent the radiators from heating up, therefore the flow is always directed towards the domestic hot water (DHW) - if
envisaged.
By activating the summer option one automatically enables the auto-eco function (it cannot be deactivated). The room probe/
external thermostat are not taken into account.
To change the function act as follows:
Press the “menu button.
Scroll to “Settings” using the arrows
Press “menu to confirm.
Scroll to “Season using the arrows.
Press “menu to confirm.
Select “Summer” or “Winter” with the + - keys.
Press “menu to confirm and esc” to exit.
q - Technical menu
To access the technical menu one must contact an assistance centre as one needs a password to enter.
To intervene on the “technical menu act as follows:
Press the “menu button.
Scroll to “Settings” using the arrows
Press “menu to confirm.
Scroll to Technical menu using the arrows.
Press “menu to confirm.
Select “Product Type, “Service, “Parameters, “DHW Parameters”, “Meters memories”, “Enable fan” and “Puffer data with the
+ - keys.
Press “menu to confirm and esc” to exit
8.5 INFO MENU
Product Type
Firmware Version
Software info
Total hrs.
Ignition N.
Rpm Smoke Fan
Smoke Temp.
Air Fan Voltage
Screw Loading
Fire
17
RIVER IDROTECH 18 - 24 - 24H2O
8.6 IGNITION OF THE STOVE
We remind you that the first ignition must be carried out by a specialized and authorixed technician who will check that all is
installed in compliance with current regulations and checks the efficiency.
If inside the combustion chamber there are booklets, manuals, etc..., remove them.
Check if the door is correctly closed.
Check if the stove is correctly inserted in the electric socket.
Before switching the stove on, assure you the burning pot is clean.
To start the stove, keep the P1 button pressed until the ON sign and a flashing flame to its side appear. The ignition resistance
pre-heating starts. After some seconds the feed screw loads pellets and the resistance pre-heating continues. When the tem-
perature is high enough (after about 5-8 minutes), ignition is considered to be completed.
Once the ignition step is complete, the stove moves into operating mode and shows the selected heat output, the ambient
temperature and the big flame (see Fig. 9).
If the ambient temperature value exceeds the limit set on the button panel in the temperature set, the heat output is brought
to its lowest value and the small flame is shown (see Fig. 10). When the ambient temperature decreases below the set tem-
perature, the stove goes back to the set output.
Fig. 9 - Big ame Fig. 10 - Small ame
8.7 FAILED IGNITION
If pellets should not ignite, the lack of ignition will be signalled by the A01 "No Ignition" warning.
If the ambient temperature is below 5°C, the resistance may not heat up enough to guarantee the pallet ignition. In this case,
remove the unburned pellets from the burning pot and restart ignition.
Too much pellets in the burning pot, or humid pellet, or sooty burning pot make ignition difficult and create dense white smoke
which is harmful to health and can cause explosions on the combustion chamber. It is therefore necessary not to stand in front of
the stove during ignition stage if dense white smoke is present.
If after some months the flame appears weak and/or orange colored or the glass tends to blackens and the
burning pot to become encrusted, clean the stove, clean the fume conduit and the chimney flue.
ATTENTION!
Make sure pellets and ash have not accumulated in the brazier due to failed ignition. If the brazier is not clea-
ned before reattempting, there is the risk of further failed ignitions and even explosions in some cases.
8.8 SWITCH OFF ON PANEL: OFF WITH FLASHING FLAME
If the shutdown key is pressed or if there is an alarm signal, the boiler goes into the thermal shutdown phase which entails the
automatic execution of the following stages:
Pellet loading is stopped.
The room fan continues to operate until the requested temperature is reached.
The flue fan is set to its highest value, which it keeps until the requested temperature is reached, plus a safety time of 10
additional minutes. After that, if the fume temperature has decreased below the switch off threshold, it stops, otherwise the
cooling process goes on.
If the stove has switched off normally, but owing to thermal inertia, the fume temperature goes over the threshold again, the
switch off process is reactivated until the temperature decreases again.
8.9 POWER FAILURE
After a black-out lower than 10 seconds, the stove turns back to the power which was settled.
After a black-out of more than 10 seconds, the stove enters the during shutdown. Completed this phase, it starts automatically
up with the different phases.
RIVER IDROTECH 18 - 24 - 24H2O
18
8.10 ADJUSTMENTS MENU
To access the adjustments menu act as follows:
Press the + - keys
Scroll with the <> arrows and select “Set Room T or “Set Water T” or “Exchanger Speed”
Press “menu to access the selected option.
Modify with the + - keys.
Press “menu to confirm and esc” to exit.
Fig. 11 - Display
Note: The full stop to the right of the ambient temperature shown in the control panel display (upper right) indicates the half
degree (e.g. 23.° means 23.5°C).
Air V. Speed - this function allows selecting the desired speed for the ambient fans from 1 to 5.
Water temperature - temperature adjustable from 30° to 80°
8.11 PROGRAMMED MODE TIMER  MAIN MENU
Setting the current day and time is essential for the proper operation of the timer.
There are six TIMER programmes, for each one the user can decide the start-up and shutdown time as well as the day of the week
in which it is active.
When one or more programmes are active, the panel alternately displays the boiler status and TIMER “n whereby n is the number
relating to the activated timer programmes, separated from each other with a dash
Example:
TIMER 1 Timer programme 1 active.
TIMER 1-4 Timer programmes 1 and 4 active.
TIMER 1-2-3-4-5-6 Timer programmes all active.
EXAMPLE OF PROGRAMMING
With boiler on or off:
access the MENU,
scroll to TIMER with the <> arrows,
press the “Menu” key
the system proposes “P1” (Press the <> keys for the subsequent timers P2,P3, P4, P5, P6)
to activate “P1” press the “Menu” key
press + - and select “ON”
confirm with the “Menu key
At this point it will propose 00:00 as starting time, with key + - adjust the starting time and press the menu” key to confirm.
The next step proposes a shutdown time of 10 minutes above that set for start-up: press the + key and adjust the shutdown time,
confirm with the menu key.
Subsequently the system proposes the days of the week in which to activate or deactivate the previously set timer. With the - or +
key highlight with the white background the day in which one wishes to activate the timer and confirm with the “menu key. If no
day of the week is confirmed as active, in turn the timer programme will not appear active in the status screen.
Continue to program the following days or press “ESC” to exit. Repeat the procedure to program the other timers.
19
RIVER IDROTECH 18 - 24 - 24H2O
8.12 PROGRAMMING EXAMPLES:
P1 P2
on off day on off day
08:00 12:00 mon 11:00 14:00 mon
Boiler on from 08:00 to 14:00
on off day on off day
08:00 11:00 mon 11:00 14:00 mon
Boiler on from 08:00 to 14:00
on off day on off day
17:00 24:00 mon 00:00 06:00 tue
Boiler on from 17:00 on monday to 06:00 on tuesday
8.13 NOTES FOR TIMER OPERATION
Start-up with the timer always takes place with the last temperature and ventilation settings (or with default 20°C and V3
settings in the event they have never been changed).
It is possible to set the shutdown time from “ignition time + 10 minutes” up to 23:50. If 24:00 is set as shutdown time, the stove
will not switch off (use this shutdown time, for example, when the next day is programmed to continue from 00:00).
If the shutdown time is not already memorised, it proposes a start-up time in + 10 minutes.
A timer programme switches the boiler off at 24:00 of one day and another programme switches it on at 00:00 of the next day:
the boiler stays on.
A programme proposes a start-up and shutdown in times included within another timer programme: if the boiler is already on,
start will not have any effect, while OFF will switch it off.
In the boiler on and timer active condition, press the OFF key and the boiler will switch off, it will switch on automatically at
the next time set on the timer.
In the boiler off and timer active condition, press the ON key and the boiler will switch on, it will switch off at the time set on
the active timer.
8.14 AUTO ECO MODE SEE SECTION FG
To activate the Auto Eco” mode and adjust the time refer see section f-g.
The possibility to adjust the “ECO shutdown t” comes from the need to ensure proper operation in the various rooms the boiler
can be installed in and prevent continuous shutdowns and start-ups in the event the temperature is subject to sudden changes (air
currents, poorly insulated rooms, etc.).
The ECO shutdown procedure is activated automatically when all the power demand devices involved in the system configu-
ration are satisfied: room probe/external thermostat, flow switch, puffer thermostat/ntc (10 k ß3435) or boiler thermostat/
ntc (10 k ß3435). If all devices present are satisfied the “ECO shutdown t” time decrease starts (by default 10 minutes, it can
be changed within the “Settings menu”). During this stage the panel displays ON with a small flame and alternately Chrono (of
active) - Eco active. The minutes indicating the countdown for the Eco Stop are shown at the top of the display. The flame goes into
P1 and stays there until the programmed “Eco shutdown t” time has elapsed and if the conditions are still satisfied, it goes into the
shutdown stage. The ECO switch off countdown resets if one of the devices boosts power again.
When switch off starts the panel displays: Off - Eco Active - small flashing flame.
Once the boiler has reached the off condition, the panel displays OFF-ECO with the extinguished flame symbol.
To restart from ECO the following conditions must be satisfied simultaneously:
Power demand
After 5 minutes from the beginning of shutdown.
TH2O < TSetH2O.
If the domestic hot water (DHW) demands power - if envisaged - the first 5’ are ignored and the boiler restarts as needed.
NOTE: In configuration 4 - 5 the Auto Eco mode is enabled automatically. Even when one sets the summer function in configura-
tion 2 - 3 it is enabled automatically. In the cases where it is designed to be active, it is not possible to deactivate the mode.
8.15 SLEEP FUNCTION MAIN MENU
The sleep function is activated only when the boiler is switched on and allows to quickly set a time at which the product must
switch off.
To set the Sleep function act as follows:
Enter MENU
Scroll to SLEEP with the <> arrows
RIVER IDROTECH 18 - 24 - 24H2O
20
Press Menu
With the + - keys adjust the desired shutdown time.
The panel proposes a shutdown time of 10 minutes from the current time, adjustable with key 4 until the next day (I can therefore
delay the shutdown for up to a maximum of 23 hours and 50 minutes).
Fig. 12 - Sleep
If the SLEEP function is active with the TIMER active the first has priority over the latter, therefore the boiler will not switch off at
the time set on the timer but instead by the time established by the sleep function, even if later than the time set on the timer.
8.16 EASY SET FEATURE SEE SECTION X SETTINGS MENU A PAG. 12
Proper operation of a stove mainly depends on the flue it is connected to. Once it is connected, it is equally important to perform
proper adjustment of combustion parameters.
The Easy Set feature makes it possible to adjust combustion more easily, in the event that one should notice that the stove does
not properly burn the fuel.
In the “Settings” menu, under the heading Easy Set, there are 4 configurations, SET1-SET2-SET3-SET4.
Select the SET based on the type of installation.
Caution, before changing the stove’s programming :
It is recommended to change the factory settings under the supervision of an authorised technician.
Before installation, ensure the flue has been installed and certified by suitable personnel according to the legal provisions in
force.
Examples of available “Easy Set configurations compared to «typical» installation of reference:
SET 0 : Default parameters
SET 1 : Vertical exhaust
SET 2 : Concentric vertical exhaust (mainly used in France)
SET 3 : Horizontal concentric wall exhaust (only used and permitted in France)
SET 4 : Smoke fitting with horizontal section
Fig. 13 - Ensemble d'exemples
LEGENDA
ASmoke Outlet
BCombustion Air Intake
TInspection cap
21
RIVER IDROTECH 18 - 24 - 24H2O
8.17 PELLETS RECIPE SEE SECTION J SETTINGS MENU A PAG. 12
Changes to be made with the support of the authorised technician.
Activates only with the Easy Set function disabled, "SET: 0" !
This function is for adapting the stove to the pellets that are being used. In fact, as there are several types of pellets on the market,
boiler operation is extremely variable depending on the fuel quality. In the event the pellets tend to clog the brazier due to an
excessive load of fuel or in the event the flame is always high even at low powers and, vice versa if the flame is low one can decre-
ase/increase the amount of pellets in the brazier:
The available values are:
-30= 30% reduction with respect to the default setting.
-25= 25% reduction with respect to the default setting.
-20= 20% reduction with respect to the default setting.
-15 = 15% reduction with respect to the default setting.
-10= 10% reduction with respect to the default setting.
-5= 5% reduction with respect to the default setting.
0= No variation.
+5= 5% increase with respect to the default setting.
+10 = 10% increase with respect to the default setting.
+15 = 15% increase with respect to the default setting.
8.18 SMOKE RPM VARIATION SEE SECTION K SETTINGS MENU A PAG. 12
Changes to be made with the support of the authorised technician.
Activates only with the Easy Set function disabled, "SET: 0" !
If the installation presents difficulties for smoke evacuation (no draught or no pressure in the duct), the smoke and ash expulsion
speed can be increased. This change resolves all the potential problems related to pellets clogging in the brazier and deposits
forming at the bottom of the brazier itself caused by poor quality fuel or fuel that produces a lot of ashes. The values available are
from -27% to +27% with variations of 3 points at a time. The variation in negative can be used in case the flame is too low.
8.19 CHIMNEY SWEEP FUNCTION FOR MAINTENANCE TECHNICIANS ONLY  SEE SECTION N SET
TINGS MENU A PAG. 12
This function can be activated only when the boiler is on and with power output and heating operation power with parameters
P5, with fan (if present) in V5. Any loading/smoke ventilation percentage corrections must be taken into account. This status lasts
20 minutes, the countdown is displayed on the panel. At any time the technician can interrupt this stage by quickly pressing the
on/off key.
9 FUEL
9.1 FUEL
Use top-quality pellets because they have influence in the calorific value and in ash remains.
Not adequate pellets cause a bad combustion, a frequent burning pot obstruction and exhaust conduits obstruction. Further it
decreases the calorific value, soils the glass and increases consumptions and ash and unburnt granules quantity.
RIVER IDROTECH 18 - 24 - 24H2O
22
Humid pellets cause a bad combustion and running, so please assure you that they are stored in dry places and
far at least one meter from the stove and/or any other source of heat.
It is advisable to try different type of pellets available on the market and to choose that which gives the best performance.
Pellets of variable quality and size are available on the market: the smaller the pellet, the greater the fuel supply, resulting in
poor combustion
Depending on the type of pellets it could be necessary a parameters adjustment, please contact an Authorized
Assistance Service.
The main quality certifications for pellets currently available on the European market guarantee that the fuel complies with class
A1/A2 according to ISO 17225-2. These certifications include, for example, ENPlus, DINplus, Ö-Norm M7135, and specifically assure
that the following characteristics are complied with:
calorific value: 4.6 - 5.3 kWh/kg.
Water content: ≤ 10% of the weight.
Percentage of ash: max 1.2% of the weight (A1 less than 0.7%).
Diameter: 6±1/8±1 mm.
Length: 3-40 mm.
Content: 100% untreated wood without the addition of binding agents.
The company recommends using certified fuel for its products (ENPlus A1, DINplus, Ö-Norm
M7135).
The use of pellets that do not comply with the characteristics specified previously may com-
promise the operation of your product and therefore invalidate the warranty and product
liability.
9.2 PELLET SUPPLY
Fig. 14 - Wrong opening of the pellets bag Fig. 15 - Right opening of the pellets bag
It is necessary to avoid to fill the hopper with the pellet when the stove is running.
Do not get the bag of pellet in contact with hot stove surfaces.
Do not empty the hopper with remaining fuels (unburnt pellet) from the burning pot coming from ignition waster.
9.3 PELLET REFUELLING TIMER
This stove is equipped with a safety timer that activates after the pellet hopper door has been open for 90 seconds during reloa-
ding (see Fig. 16 and Fig. 18). After 90 seconds, the stove goes into "A05" depression alarm and proceeds to switch off.
Wait until it switches off, then light it again.
23
RIVER IDROTECH 18 - 24 - 24H2O
Fig. 16 - Door open Fig. 17 - deteriorated gasket Fig. 18 - Timer: 90 seconds
To operate correctly, the stove must work with the pellet hopper door always closed; should it remain open for
more than 90 seconds, the stove switches off.
The loading system stops when the tank door is opened.
Before closing the lid, make sure there are no pellets below the gasket. Pellets deteriorate the gasket and
eliminate its airtight sealing. (vedi Fig. 17)
10 SAFETY DEVICES AND ALARMS
The product is supplied with the following safety devices
10.1 PRESSURE SWITCH
It controls pressure in the fume duct. It blocks the pellet feed screw in the following instances:
clogged exhaust
Significant negative (wind)
clogged fume passages
open pellet loading tank
open fire door or worn/broken gaskets.
see SMOKE RPM VARIATION User Manual
10.2 SMOKE TEMPERATURE PROBE
Detects the temperature of the smoke, thereby enabling start-up or stopping the product when the temperature drops below the
preset value.
10.3 CONTACT THERMOSTAT IN THE FUEL HOPPER
If the temperature exceeds the preset safety level, it immediately shuts down boiler operation.
10.4 ELECTRICAL SAFETY
The product is protected against sudden current surges by a main fuse in the power supply panel on the rear part of the product.
Other fuses that protect the electronic boards are found on the latter.
10.5 SMOKE FAN
If the fan stops, the electronic board promptly shuts off the pellets supply and an alarm message is displayed.
10.6 GEAR MOTOR
If the gear motor stops, the boiler will continue to run until the flame goes out due to lack of fuel and until a minimum level of
cooling is reached.
10.7 TEMPORARY POWER CUT
If the power cut lasts less than 10” the boiler returns to its previous operating status; if it lasts more it carries out a cooling/restart
cycle.
10.8 FAILED STARTUP
If during ignition no flame develops, the boiler will go into alarm condition.
RIVER IDROTECH 18 - 24 - 24H2O
24
10.9 BLACKOUT WITH THE BOILER ON
In the event of a power cut (BLACKOUT) the boiler behaves as follows:
Blackout below 10”: it returns to its operation in progress;
In the event of a power cut that lasts over 10” with the boiler on or in the start-up stage, when the boiler is powered again it
goes back to the previous operating condition with the following procedure:
1) It performs a cooling phase to the maximum.
2) Performs a new ignition.
During stage 1 the panel displays ON BLACK OUT.
During stage 2 the panel displays Start-up.
If during stage 1 the boiler receives commands from the panel and thus carried out manually by the user, then the boiler stops
executing the blackout recovery status and proceeds to restart or shutdown as requested by the command.
10.10 CONTACT THERMOSTAT IN THE BOILER
If the temperature exceeds the preset safety level, it immediately shuts down boiler operation.
10.11 WATER TEMPERATURE PROBE
If the water temperature approaches the shutdown temperature (85°C) the probe makes the boiler perform the “OFF Stand-by”
automatic shutdown.
10.12 ANTIFREEZE FUNCTION
If the probe in the boiler detects a water temperature of less than 5°C, the circulation pump is automatically activated to prevent
the system from freezing.
10.13 PUMP ANTISEIZURE FUNCTION
If the pump is not used for prolonged periods, it is activated periodically for a few seconds to prevent it from seizing up.
TAMPERING WITH THE SAFETY DEVICES IS PROHIBITED
If the product is NOT used as described in this instruction manual, the manufacturer declines all liability for
any damage caused to persons and property. The manufacturer furthermore refuses to accept responsibility
for damage to persons and property arising from the failure to observe all the rules contained in the manual
and in particular:
• All the necessary measures and/or precautions must be adopted when performing maintenance, cleaning
and repairs.
• Do not tamper with the safety devices.
• Do not remove the safety devices.
• Connect the product to an efficient smoke expulsion system.
• Verify that the room in which the appliance will be installed is adequately ventilated.
The product can be started-up and the automatic function of the probe restored only after having eliminated
the cause that triggered the safety system. This manual will help you understand which anomaly has occur-
red, and explain how to intervene according to the alarm message displayed on the appliance.
10.14 CLEANER BLOCKED
If the burn pot grid does not close correctly, the alarm A23 is triggered. Clean the burn pot. Check that there are no pellets stuck
between grid and burn pot. (see Fig. 19). Break up the pellets using a pointed tool (see Fig. 20). Clear the alarm and switch the
stove back on.
25
RIVER IDROTECH 18 - 24 - 24H2O
Fig. 19 - Burn pot Fig. 20 - Burn pot
10.15 ALARM ALERTS
Whenever an operating condition other than that designed for the regular operation of the boiler occurs, there is an alarm condi-
tion.
The control panel gives information on the reason of the alarm in progress. A sound signal is not envisioned for alarms A01-A02
only so to PANEL ALERTnot disturb the user in the event of pellets running out in the hopper during the night.
PANEL ALERT TYPE OF PROBLEM SOLUTION
A01 The fire does not ignite. Check whether the brazier is clean / level of pellets in the
hopper.
A02 The fire goes off abnormally. Check the level of pellets in the hopper.
A03 Thermostat
alarms
The temperature of the pellets hopper or the
water temperature exceed the envisioned safety
threshold.
Wait for the cooling stage to end, cancel the alarm and
restart the boiler setting the fuel loading at minimum (SET-
TINGS menu - Pellets recipe). If the alarm persists, contact
the service centre. Check if the room fan works properly (if
present).
A04 Smoke overheating. The set smoke threshold has been exceeded. Reduce pellets
loading (SETTINGS menu - Pellets recipe).
A05 Pressure
switches alarm Smoke pressure switch intervention or water pres-
sure insufficient. Verify chimney obstruction / door opening or hydraulic
system pressure.
A08 Abnormal smoke fan operation. If the alarm persists, contact the service centre.
A09 Smoke probe faulty. If the alarm persists, contact the service centre.
A19 Water probe faulty. Water probe disconnected / interrupted / defective / not
recognised.
A20 Puffer probe alarm. Puffer probe disconnected / interrupted / defective / not
recognised.
A21 Triac alarm The triac of the electronic card has stalled. Replace the card.
SERVICE Routine maintenance alert (it does not block the
system).
When this flashing message appears upon start-up, it
means that the preset operating hours have elapsed before
maintenance. Contact the service centre.
A23 Cleaner blocked Check the foreign object blocking the movement
RIVER IDROTECH 18 - 24 - 24H2O
26
10.16 ALARM RESET
NEVER open the stove door while it is starting up initially or switching off, as the pellets are
still burning at this point and there may be volatile substances.
ATTENTION!
If smoke flows into the room from the appliance or the flue during operation or initial igni-
tion, switch off the device, air out the room, and immediately contact the installation/custo-
mer service technician.
To reset the alarm, you must hold down key 1 (ESC) for a few seconds. The stove performs a check to determine whether what
caused the alarm is still present.
If this is the case, the alarm will be shown again, otherwise the stove will switch OFF.
If the alarm persists, contact a service centre.
11 ROUTINE MAINTENANCE
11.1 INTRODUCTION
For a long working life of the stove, have a periodic cleaning of the stove as described in the following paragrafs.
Fume outlet pipes (fume conduit + chimney flue + chimney pot) must always be cleaned, scrubbed and checked by an autho-
rized technician in compliance with local regulations, with the instructions of the manufacturer and those of your insurance
company.
If there are no local regulations and no instruction from your insurance company, it is necessary to have your fume pipe, chim-
ney flue and chimney pot cleaned at least once a year.
It is also necessary to have the combustion chamber, motors and fans cleaned and to have the gaskets and the electronical
elements checked at least once a year.
All these operations must be planned in time with your Autorized Technical Assistance Service.
After a long ineffective time, before turning on the stove check if there are obstructions in the fume exhaust.
If the stove had been using continuously and intensely, the whole system (chimney included), must be cleaned and checked
more frequently.
In case of replacement of damaged pieces please ask for the original spare part at the Autorized Retailer.
11.2 BEFORE EACH STARTUP
Clean the ash and any deposits in the brazier that could clog the air passage holes.
If the pellets in the hopper finish, unburned pellets may accumulate in the brazier. Always empty the residue in the brazier before
startingup.
Check that there is no excessive ash accumulated under the burning pot compartment. If it exceeds 2 cm of height, we recommend
sucking it.
REMEMBER THAT ONLY A CORRECTLY POSITIONED AND CLEAN BRAZIER CAN GUARANTEE START-UP AND OPTI-
MAL OPERATION OF YOUR PELLET PRODUCT.
For the brazier to be cleaned properly, remove it from its housing completely and thoroughly clean all the holes and the grate on
the bottom.
If good quality pellets are used, you will normally only need to use a brush to restore the optimal operating conditions of the
component.
27
RIVER IDROTECH 18 - 24 - 24H2O
Fig. 21 - Example of cleanly brazier Fig. 22 - Example of dirty brazier
11.3 HOPPER CLEANING
Fig. 23 - Hopper cleaning
Per each pellets supply, check the probable presence of meal, sawdust and other remanins on the hopper bottom. If present, they
must be removed with the aid of a vacuum cleaner (see Fig. 23 ).
11.4 FUME PIPES ANNUAL CLEANING
Clean annually from soot with brushes.
The cleaning operation must be executed by a specialized stove-repairer who will provide for the cleaning of fume pipe, chimney
flue and chimney pot. He will also check their eficiency and will release a written declaration of the safety of the appliance. This
operation must be executed at least once a year.
11.5 GENERAL CLEANING
For cleaning external and inner parts of the stove do not use steel wools, muriatic acid or other corrosive and abrasive materials.
11.6 CLEANING OF PAINTED METAL PANELS
To clean painted metal panels use a soft cloth. Do not use degreasant agents like alcool, diluents, acetone, gasoline because these
could irremediably damage the varnish.
11.7 CLEANING OF CERAMIC AND STONE PANELS
Some stove models has an external lining made up of ceramic or stone. These pieces are handmade therefore they could inevitably
present crazings, seedinesses, shadings.
To clean ceramic or stone panels use a soft and dry cloth. If using any cleaners this will seep through the crazings putting them in
evidence.
11.8 GASKET REPLACEMENT
In case of deterioration of fire door, hopper or fume chamber gaskets, it is necessary to replace them by an autorized technician in
order to guarantee the good running of the stove.
Use exclusively original spare parts.
11.9 GLASS CLEANING
The glass-ceramic of the fire door is able to stand till 700°C but not to thermal shocks.
The probable cleaning with usual sale product for glass cleaning must be effected at cool glass in order to avoid explosions.
RIVER IDROTECH 18 - 24 - 24H2O
28
You should clean the fire door glass every day!
11.10 ASH DRAWER CLEANING IDRO
Press door “H” to the bottom right and open it. Turn the handle of door “G to the right and open it downwards.
Pull out and empty ash drawer “D”. Remove any ash residue from the compartment before reinserting the drawer. Experience and
pellet quality will determine the frequency of the ash drawer cleaning. In any case, it is advisable not to exceed 2 or 3 days.
When cleaning the ash drawer, we recommend removing part “C” near the brazier and using a vacuum cleaner nozzle to remove
any ash build-up.
Fig. 24 - Drawer removal Fig. 25 - Brazier removal
NOTE: Check whether there are any pellet grains behind the cleaner.
11.11 CLEANING THE EXCHANGER AND THE COMPARTMENT UNDER THE BRAZIER EVERY 7 DAYS
MAX
Cleaning the exchanger and the compartment under the brazier is a simple task but very important to always maintain the decla-
red performance.
As such, we recommend cleaning the internal exchanger every 5 - 6 days, following these simple tasks in order:
Activate “CLEANING” function - when the boiler is off, press - menu, select “Settings”, use the <> arrows to select “Clea-
ning”, confirm with “Menu, active cleaning “ON” using the +- keys. This procedure activates the smoke extraction fan to the
maximum, in order to expel the soot that is stirred up while cleaning the exchanger.
Clean the pipe unit - Using lever A, located under the tank cover, vigorously shake the turbulators 5-6 times. This removes
the soot deposited on the exchanger smoke ducts during normal boiler operation.
Disable the “CLEANING” function - this function is automatically disabled after two minutes. If you need to stop this fun-
ction sooner, press the “Esc” key.
Clean the smoke conveyor compartment(fig. on next page)
The boiler is equipped with a removable ash drawer to collect any soot and ash build-up (previous page).
Once cleaning is complete, close the cover and ash drawer.
If this cleaning is not done every 5-6 days, the stove could become clogged with ash after several hours of
operation and go into alarm conditions.
29
RIVER IDROTECH 18 - 24 - 24H2O
Fig. 26 - Turbulator cleaning lever
11.12 PIPE UNIT CLEANING
For improved boiler performance, once a month it is necessary to clean the pipes inside the combustion chamber.
Open the firebox door and use the supplied brush to clean the 5 pipes located at the top inside the combustion chamber. Do this
several times so that the ash deposited inside these pipes falls into the lower area around the brazier.
Use a vacuum cleaner to remove all the fallen material.
Fig. 27 - Pipe unit cleaning
11.13 SHUTDOWN END OF SEASON
At the end of each season, before switching the product off, it is recommended to remove all the pellets from the hopper with a
vacuum cleaner with a long pipe.
We recommend removing the unused pellets from the hopper because they can retain moisture. Disconnect any combustion air
ducting that can lead to moisture inside the combustion chamber but, above all, ask the specialised technician to refresh the paint
inside the combustion chamber with the special silicone spray paints (available at any store or Technical Assistance Centre) during
the necessary annual end of season scheduled maintenance operations. This way the paint will protect the inner parts of the com-
bustion chamber, blocking any type of oxidative process.
Fig. 28 - Shutter with fuses to remove
When not in use the appliance must be disconnected from the mains power supply. It is recommended to remove
the power cable for additional safety, especially in the presence of children.
The service fuse may have to be replaced if the control panel display does not switch on.
There is a fusebox on the back of the product, near the power socket.
After removing the plugs from the power socket, open the fusebox cover with a screwdriver and replace the fuses if necessary (3.15
RIVER IDROTECH 18 - 24 - 24H2O
30
A delayed) - seek assistance from an authorised and qualified technician.
11.14 CHECKING THE INNER COMPONENTS
ATTENTION!
Only qualified personnel with technical knowledge of combustion and electricity can check the inner electri-
cal-mechanical components.
. PARTS/FREQUENCY 2-3 DAYS 7 DAYS 1 YEAR
VRT3@UNDER THE USER'S Brazier* X
RESPONSIBILITY Ash pan X
Glass X
Lower compartment X
Turbulators X
BY THE QUALIFIED TECHNICIAN Complete heat exchanger X
Smoke duct X
Door gasket X
Internal parts X
Flue X
Circulation pump X
Plate heat exchanger X
Plumbing components X
Electro-mechanical components X
Overpressure silicon damper for combustion
chamber X
Door closure operation X
Cleaner X
* THE FREQUENCY OF CLEANING SHOULD BE INCREASED IF THE PELLETS ARE OF POOR QUALITY.
We recommend this maintenance be done annually (with a scheduled service contract), which focuses on a visual and functional
check of the inner components. Below is a summary of the checks and/or service that are essential for proper product operation:
Gear motor
Smoke extraction fan
Smoke probe
Ignition spark plug
Pellet/water automatically rearming thermostat
Room/water probe
Motherboard
Panel-board protective fuses
Wiring
12 IN CASE OF ANOMALY
12.1 PROBLEM SOLVING
Before of every Authorized Technician intervention, the same Technician has the duty to check if the parame-
ters of the mother board correspond to those of the table you own.
In case of doubts regarding the use of the stove, please contact ALWAYS the Authorized Technician on order to
avoi irreparable damages!
31
RIVER IDROTECH 18 - 24 - 24H2O
PROBLEM CAUSE SOLUTION INTERVENTION
The control display
does not switch on
The stove is without
power supply Check if the plug is connected.
Burned protection
fuse in the electric
socket Replace the protection fuses in the electric socket (3.15A-250V).
Faulty control
display Replace the control display.
Faulty flat cable Replace the flat cable.
Faulty electronic
board Replace the mother board.
Pellets do not reach
the combustion
chamber
Empty hopper Full the hopper.
Open fire door or
open pellet door Close fire door and pellet door and check that there are no pellet
grains at the gasket level.
Clogged stove Fume chamber cleaning
Auger blocked by a
foreign object (for
example nails) Clean the auger.
The auger geared
motor is out of order Replace the geared motor.
Check if on the
display there is an
"ACTIVE ALARM" Have the stove checked.
RIVER IDROTECH 18 - 24 - 24H2O
32
PROBLEM CAUSE SOLUTION INTERVENTION
The fire extinguish
and the stove stops
Empty hopper Full the hopper.
Auger blocked by a
foreign object (for
example nails) Clean the auger.
Bad quality pellets Try other types of pellets.
Pellet drop value too
low "phase 1" Adjust the pellet loading.
Check if on the
display there is an
"ACTIVE ALARM" Have the stove checked.
The door does not
close perfectly or the
gaskets are worn Check the door seal and replace the gaskets.
Ignition step is not
completed Empty the brazier and repeat ignition.
Clogged exhaust The exhaust chimney is partially or totally obstructed. Call a skilled
chimney technician to check from the stove exhaust to the chim-
neypot. Clean immediately.
Flames are weak and
orange coloured,
pellets do not burn
properly and the
glass blackens
Not sufficient com-
bustion air
Check as following: probable obstructions of the combustible air
inlet from the back or from the bottom of the stove; burning pot
obstructed holes with too ash remains. Have the fan blades and
auger cleaned. (see SMOKE RPM VARIATION User Manual)
Obstructed exhaust The exhaust chimney is partially or totally obsturcted. Contact an
expert stove-repairer who checks the stove from the exhaust up to
the chimney pot. Provide immediately for stove cleaning.
Obstructed stove Provide immediately at the inner cleaning of the stove.
The fume fan is out
of order
The pellets can burn also thanks to chimney flue depression
without the aid of the fume fan. Have the fume fan immediately
replaced. It can be noxious to health to let the stove running
without fume fan.
The exchanger fan
continues to turn
even though the
stove has just cooled
Faulty fume tempe-
rature probe Replace the fume probe.
Faulty mother board Replace the mother board.
Ash remains along
the stove
Faulty or out of order
door gaskets Replace the gaskets.
Not sealed fume
pipes
Contact an expert stove-repairer who will immediately provide for
sealing the junctions with high-temperature silicone and/or for
replacing pipes with those in compliance to current regulations. A
not sealed fume channelisation can be noxious to health.
33
RIVER IDROTECH 18 - 24 - 24H2O
PROBLEM CAUSE SOLUTION INTERVENTION
The stove is at its
highest power but
does not heat up.
Ambient temperatu-
re reached. The stove is at its minimum value. Increase the desired ambient
temperature.
Stove running and
display showing
"Smoke Overtepe-
rature"
Reached fume outlet
limit temperature The stove runs at minimum. NO PROBLEM!
The stove's smoke
duct produces
condensation
Low smoke tempe-
rature
Check that the flue is not clogged.
Increase stove power to minimum (pellet drop and fan revs).
Install condensation collection cup.
Stove running and
display showing
"SERVICE"
Routine maintenan-
ce alert (it does not
block the system)
When this flashing message appears upon start-up, it means that
the preset operating hours have elapsed before maintenance.
Contact the service centre.
12.2 PROBLEM SOLVING THERMOSTOVE
PROBLEM POSSIBLE CAUSES SOLUTIONS INTERVENTION
In automatic
position, the boiler
always works at
maximum power
Thermostat set to
the minimum Reset the thermostat temperature.
Room thermostat
in a position that
always detects cold. Change the position of the thermostat
Faulty temperature
detection probe. Check and, if necessary, replace the probe
Faulty circuit board Replace board
The boiler does not
start
Power failure Make sure the power cable is plugged in and the main switch is in
the “I” position.
Blown fuse Replace the fuse.
Clogged smoke duct
or exhaust Clean the smoke exhaust and/or smoke duct.
Water temperature
probe has tripped Call customer service
RIVER IDROTECH 18 - 24 - 24H2O
34
PROBLEM POSSIBLE CAUSES SOLUTIONS INTERVENTION
Temperature does
not increase with
the boiler working
Improper combu-
stion adjustment. Check recipe and parameters.
Dirty boiler/system Check and clean the boiler.
Insufficient boiler
power. Make sure the boiler is appropriately proportional to the system
requirements.
Poor quality pellets Use quality pellets
WATER ON FLOOR
BOILER EXTERNAL
CONDENSATE Adjust the boiler to a higher temperature
NO ANTI-CONDENSA-
TION VALVE INSTALL ANTI-CONDENSATION VALVE
LEAK FROM PIPES CHECK CLOSURE of the PIPE FITTINGS
Radiators cold in the
winter
Room thermostat
(local or remote)
adjusted too low. If
remote thermostat,
check whether it is
defective.
Adjust it to a higher temperature. Replace it if necessary (if remote)
The circulator does
not turn because it is
blocked.
Release the circulator by removing the cap and turning the shaft
with a screwdriver
The circulator does
not turn. Check its electrical connections, replace it if necessary
Air inside the
radiators Bleed the radiators
No HEATING water
comes out
Circulator (pump)
blocked Release the circulator (pump)
NO PRESSURE in
SYSTEM INCREASE PRESSURE and CHECK FOR LEAKS
Noise and gurgling Air in the system Vent the air and fill the system
DOMESTIC HOT
WATER DOES NOT
COME OUT
3-WAY VALVE
BLOCKED CHECK 3-WAY VALVE
35
RIVER IDROTECH 18 - 24 - 24H2O
13 TECHNICAL DOCUMENTATION FOR LOCAL SPACE HEATERS ACCORDING TO COM
MISSION REGULATIONS EU 2015/1185  EU 2015/1186 PRODUCT FICHE
Manufacturer CADEL srl - Via Foresto Sud 7 - 31025 Santa Lucia di Piave (TV) - Italy
Trademak: model identifier CADEL: RIVER IDROTECH 18 T1
FREEPOINT:
PEGASO:
Description Pellet stove
Indirect heating functionality Yes
Direct heat output 5 kW
Indirect heat output 12,7 kW
CPR harmonised standard EN 14785
Notified body IMQ Spa (N.B.0051)
Preferred fuel (unique) Compressed wood with moisture content < 12 % YES
Wood logs with moisture content ≤ 25 % NO
Other woody biomass NO
ηs91 %
EEI 133 -
Energy Efficiency Class (A++ to G scale) A++
Space heating emissions at nominal heat output
PM (al 13% O2)10 mg/Nm3
OGC (al 13% O2)1mg/Nm3
CO (al 13% O2)106 mg/Nm3
NOx (al 13% O2)99 mg/Nm3
Space heating emissions at minimum heat output
Only required if correction factors F(2) or F(3) are applied
PM (al 13% O2)12 mg/Nm3
OGC (al 13% O2)2mg/Nm3
CO (al 13% O2)209 mg/Nm3
NOx (al 13% O2)100 mg/Nm3
Heat output Nominal heat output (Pnom)17,7 kW
Minimum heat output (indicative) (Pmin)4,4 kW
Useful efficiency (NCV as received) Useful efficiency at nominal heat output (ηth,nom)94,8 %
Useful efficiency at minimum heat output (indicative)
th,min)95,9 %
Auxiliary electricity consumption At nominal heat output (elmax)0,126 kW
At minimum heat output (elmin)0,065 kW
In standby mode (elsb)0,005 kW
Type of heat output/room temperature control (select
one)
Single stage heat output, no room temperature control NO
Two or more manual stages, no room temperature
control NO
With mechanic thermostat room temperature control NO
With electronic room temperature control NO
With electronic room temperature control plus day
timer NO
With electronic room temperature control plus week
timer YES
Other control options (multiple selections possible)
Room temperature control, with presence detection NO
Room temperature control, with open window detec-
tion NO
With distance control option NO
Permanent pilot flame power requirement Pilot flame power requirement (if applicable) (Ppilot)N.A. kW
Observe the specific precautions for installation, assembly and maintenance indicated in the manual accompanying the
product.
Issue date: 13.09.2022
RIVER IDROTECH 18 - 24 - 24H2O
36
14 TECHNICAL DOCUMENTATION FOR LOCAL SPACE HEATERS ACCORDING TO COM
MISSION REGULATIONS EU 2015/1185  EU 2015/1186 PRODUCT FICHE
Manufacturer CADEL srl - Via Foresto Sud 7 - 31025 Santa Lucia di Piave (TV) - Italy
Trademak: model identifier CADEL: RIVER IDROTECH 24 T1
FREEPOINT:
PEGASO:
Description Pellet stove
Indirect heating functionality YES
Direct heat output 6 kW
Indirect heat output 18,2 kW
CPR harmonised standard EN 14785
Notified body IMQ Spa(N.B. 0051)
Preferred fuel (unique) Compressed wood with moisture content < 12 % YES
Wood logs with moisture content ≤ 25 % NO
Other woody biomass NO
ηs89 %
EEI 131 -
Energy Efficiency Class (A++ to G scale) A++
Space heating emissions at nominal heat output
PM (al 13% O2)12 mg/Nm3
OGC (al 13% O2)1mg/Nm3
CO (al 13% O2)169 mg/Nm3
NOx (al 13% O2)92 mg/Nm3
Space heating emissions at minimum heat output
Only required if correction factors F(2) or F(3) are applied
PM (al 13% O2)12 mg/Nm3
OGC (al 13% O2)6mg/Nm3
CO (al 13% O2)209 mg/Nm3
NOx (al 13% O2)100 mg/Nm3
Heat output Nominal heat output (Pnom)24,2 kW
Minimum heat output (indicative) (Pmin)4,4 kW
Useful efficiency (NCV as received) Useful efficiency at nominal heat output (ηth,nom)92,9 %
Useful efficiency at minimum heat output (indicative)
th,min)95,9 %
Auxiliary electricity consumption At nominal heat output (elmax)0,126 kW
At minimum heat output (elmin)0,065 kW
In standby mode (elsb)0,005 kW
Type of heat output/room temperature control (select
one)
Single stage heat output, no room temperature control NO
Two or more manual stages, no room temperature
control NO
With mechanic thermostat room temperature control NO
With electronic room temperature control NO
With electronic room temperature control plus day
timer NO
With electronic room temperature control plus week
timer YES
Other control options (multiple selections possible)
Room temperature control, with presence detection NO
Room temperature control, with open window detec-
tion NO
With distance control option NO
Permanent pilot flame power requirement Pilot flame power requirement (if applicable) (Ppilot)N.A. kW
Observe the specific precautions for installation, assembly and maintenance indicated in the manual accompanying the
product.
Issue date: 13.09.2022
37
RIVER IDROTECH 18 - 24 - 24H2O
15 TECHNICAL DOCUMENTATION FOR LOCAL SPACE HEATERS ACCORDING TO COM
MISSION REGULATIONS EU 2015/1185  EU 2015/1186 PRODUCT FICHE
Manufacturer CADEL srl - Via Foresto Sud 7 - 31025 Santa Lucia di Piave (TV) - Italy
Trademak: model identifier CADEL: RIVER IDROTECH 24 H2O T1
FREEPOINT:
PEGASO:
Description Pellet stove
Indirect heating functionality YES
Direct heat output 6 kW
Indirect heat output 18,2 kW
CPR harmonised standard EN 14785
Notified body IMQ Spa(N.B. 0051)
Preferred fuel (unique) Compressed wood with moisture content < 12 % YES
Wood logs with moisture content ≤ 25 % NO
Other woody biomass NO
ηs89 %
EEI 131 -
Energy Efficiency Class (A++ to G scale) A++
Space heating emissions at nominal heat output
PM (al 13% O2)12 mg/Nm3
OGC (al 13% O2)1mg/Nm3
CO (al 13% O2)169 mg/Nm3
NOx (al 13% O2)92 mg/Nm3
Space heating emissions at minimum heat output
Only required if correction factors F(2) or F(3) are applied
PM (al 13% O2)12 mg/Nm3
OGC (al 13% O2)6mg/Nm3
CO (al 13% O2)209 mg/Nm3
NOx (al 13% O2)100 mg/Nm3
Heat output Nominal heat output (Pnom)24,2 kW
Minimum heat output (indicative) (Pmin)4,4 kW
Useful efficiency (NCV as received) Useful efficiency at nominal heat output (ηth,nom)92,9 %
Useful efficiency at minimum heat output (indicative)
th,min)95,9 %
Auxiliary electricity consumption At nominal heat output (elmax)0,126 kW
At minimum heat output (elmin)0,065 kW
In standby mode (elsb)0,005 kW
Type of heat output/room temperature control (select
one)
Single stage heat output, no room temperature control NO
Two or more manual stages, no room temperature
control NO
With mechanic thermostat room temperature control NO
With electronic room temperature control NO
With electronic room temperature control plus day
timer NO
With electronic room temperature control plus week
timer YES
Other control options (multiple selections possible)
Room temperature control, with presence detection NO
Room temperature control, with open window detec-
tion NO
With distance control option NO
Permanent pilot flame power requirement Pilot flame power requirement (if applicable) (Ppilot)N.A. kW
Observe the specific precautions for installation, assembly and maintenance indicated in the manual accompanying the
product.
Issue date: 13.09.2022
NOTE
NOTE
CADEL srl
31025 S. Lucia di Piave - TV
Via Foresto sud, 7 - Italy
Tel. +39.0438.738669
Fax +39.0438.73343
www.cadelsrl.com
www.free-point.it
www.pegasoheating.com
Rev. 00 - 2022
37

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Cadel RIVER IDROTECH 24 bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Cadel RIVER IDROTECH 24 in de taal/talen: Engels als bijlage per email.

De handleiding is 0.67 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

Andere handleiding(en) van Cadel RIVER IDROTECH 24

Cadel RIVER IDROTECH 24 Gebruiksaanwijzing - Deutsch - 40 pagina's


Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info