Installation | 23
LP conversion kit installation (SSB399 - SSB512)
Natural Gas to LP conversion
The heating unit is factory preset for operating with natural gas. This
set-up can be changed using the conversion kits supplied by the
manufacturer.
NOTICE: This change may only be performed by a qualied
installer or service technician, according to the following
procedure.
Switching from NATURAL GAS to LP
Close the gas cock
Disconnect the electric power supply from the boiler
WARNING: to avoid electrical shock, it is mandatory to
disconnect the boiler from the power supply using a service
disconnect external switch.
Remove the front panel
Unscrew the swivel joint ‘A indicated in Fig. 23 to separate the valve
from the connection pipe with the fan
Separating the two components, you can see the hole where the gas
passes with its gasket
Place the provided metal orice ‘B’ (Fig. 23) between the two gaskets
Tighten the swivel joint
Switch the main power supply to ON
Fig. 23
(*) Balancing tube shown removed for clarity.
Boiler model N° on orice
SSB255 7.0
SSB399 10.5
SSB512 9.5
Tab. 2
F
NOTICE: Make sure there is no demand or call for heat.
Use the control panel to enter in the parameter list and change the
parameter N° 98 (Gas Type) from “NG” to “LPG”
Reopen the gas shut-off cock
Adjust the CO
2
parameter as explained in chapter “5.7 Adjusting
and setting CO2 limits” (see “Tab. 17 Number of turns for gas valve
settings”)
Afx the gas type label from the gas conversion kit to the appliance
(Fig. 24).
Fig. 24 Afxing the gas type label
4.7 Venting and air piping system
WARNING: Do not connect this gas appliance with any
other appliance unless approved by manufacturer.
Failure to comply with this WARNING could result in the
accumulation of carbon monoxide gas which can cause
severe personal injury or death.
DANGER: The condensate discharge must be lled with
water or combustion gases will enter the room with a risk of
an excessive level of carbon monoxide. For instruction see
par 4.4.6.
NOTICE: DO NOT use PVC for vent piping when using
anti-freeze in the primary circuit of the boiler. Use CPVC, PP
or stainless steel only!.
Make sure that the combustion air is not contaminated by:
Permanent wave solutions;
Chlorinated waxes/cleaners;
Chlorine-based swimming pool chemicals;
Calcium chloride
Sodium chloride used for water softening;
Refrigerant leaks;
Paint or varnish removers;
Hydrochloric acid/muriatic acid;
Cements and glues;
Antistatic fabric softeners used in clothes dryers;
Chlorine-type bleaches, detergents, and cleaning solvents found in
household laundry rooms;
Adhesives used to fasten building products and other similar products.
To prevent contamination do not connect the combustion ait inlet and
exhaust near:
Dry cleaning/laundry areas and establishments;
Swimming pools;
Metal fabrication plants;
Beauty shops;
Refrigeration repair shops;
Photo processing plants;
Auto body shops;
Plastic manufacturing plants;
Furniture renishing areas and establishments;
A
B
(*)
DIRECT VENT BOILER FOR EITHER DIRECT VENT INSTALLATION OR FOR
INSTALLATION USING INDOOR COMBUSTION AIR
CHAUDIÈRE À ÉVENT DIRECT PUT INSTALLATION AVEC ÈVACUATION
DIRECTE OU AVEC AIR COMBURANT
Catégorie
Modèle
Référence
Category
Model
Model no.
IV
SSB-512
7 738 004 896
Converted to LPG (Propane) with conversion kit X XXX XXX XXX
CO
2 (max. rate/ min rate)
Min. inlet gas pressure
Max. inlet gas pressure
Mainfold pressure
Min. input rate
Max. input rate
Output rate
Minimun relief valve capacity
Altitude
10,7/10,3 %
8,0 in.W. C.1,99 kPa
3,23 kPa
30,0 kW
150,0kW
144,0 kW
13,0 in.W. C.
cfactory set - not adjustable
102,360 Btu/hr
511,800 Btu/hr
491,328 Btu/hr
0-2000 ft0-610 m
(Refer to installation instruction for higher altitudes)
This boiler was converted on (day - month - year)
(name and address of organization making this conversion), which accepts
the responsability that this conversion has been properly made.
to gas. By
IV
SSB-512
7 738 004 896
Convertie vers LPG (Propane) a vec le kit de conversion X XXX XXX XXX
CO
2 ( max / min)
Min. pression d’alimentation en gaz
Max. pression d’alimentation en gaz
Pression à la conduite de gaz
Consommation calorifique min.
Consommation calorifique max.
Puissance utile nominal
Capacité minimale de la soupape de sécurité
Altitude
232,1 kg/hr 511,8 lbs/hr
10,7/10,3 %
8,0 in.W. C.
150,0kW
144,0 kW
13,0 in.W. C.
cfactory set - not adjustable
102,360 Btu/hr
511,800 Btu/hr
491,328 Btu/hr
0-2000 ft0-610 m
232,1 kg/hr 511,8 lbs/hr
(Se référ à la notice d’installtion en cas d’altitude plis élevée)
Ce appareil a été converti le (jour- mois- année) en
(nome ed adtrsse de l’organisme effectuant cette conversion), qui accepte la
responsabilité de la bonne execution de cette conversion.
gaz par
X XXX XXX XXX (2015/04)
23

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Buderus SSB399 bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Buderus SSB399 in de taal/talen: Engels als bijlage per email.

De handleiding is 9,92 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

loading

Andere handleiding(en) van Buderus SSB399

Buderus SSB399 Installatiehandleiding - Français - 68 pagina's


Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info