Commissioning | 27
6 720 805 218 (2016/02)SB625WS/SB745WS
Example DHW demand (where the 4000 series controls the DHW
system):
Sum of the set DHW temperature (140 °F) and parameter "Boiler rise"
(40 °F) in the "DHW" menu:
140 °F+ 40 °F = Maximum temperature demand 180 °F
Example heating circuits (where the 4000 series controls the
heating circuits):
Add of the set temperature of the heating circuit with mixing valve with
the highest temperature required (15 °F) and parameter "Boiler rise"
(160 °F) in the "Heating circuit data" menu:
160 °F+ 15 °F = Maximum temperature demand 175 °F
Notes on setting third party control units
The third party control unit (building management system or PLC
controllers) must ensure a maximum internal boiler water
temperature that is sufficiently different from the high limit safety
cut-out. It must also be ensured that the digital burner controller
rather than the boiler water temperature regulator switch the burner
on and off.
The control unit must ensure that the burner is switched to low load
before being shut down.
Select control equipment that allows a gentle start-up with a time
delay when the system is cold.
After the burner demand, an automatic timer (for example) should
limit the burner to low load for a period of approx. 180 seconds. This
restricted heat demand will prevent uncontrolled starting and
stopping of the burner.
It must be possible to show the number of burner starts on the
control unit used.
6.2 Hydraulic connection to the heating system
If the system temperatures are different, use both return connectors
3 (high temperature) and 2 (low temperature)(chapter 2.9.3.
Fig. 5 and 6,page 11, table 6, page 12)
Connect heating circuits with high return temperatures to connector
3, and heating circuits with low return temperatures to connector 2.
Restrict the water flow rate in the boiler to a temperature difference
of at least 7 K between supply and return.
Size the pumps correctly.
Before connecting the boiler, flush sludge and dirt out of the heating
system.
Ensure that no oxygen enters the heating water during operation.
Only operate the boiler in sealed unvented systems.
6.3 Hydraulic flow through boiler
The SB Series does not require a minimum flow rate in order to maintain
warranty. The boiler has been designed to operate with a temperature
difference between the supply and return of up to 100 °F. Flow should
be initiated with the start of the burner to minimize temperature
fluctuations and control deviations. The field installed manual reset high
limit (as required by CSD-1) must be fitted to the instrument bulb/probe
socket of the heating supply, set to 210 °F and electrically connected
into the Logamatic 4321 safety circuit terminals (17,18) or the burner
enable/disable circuit directly (see Fig 26).
Fig. 26
[1] Instrument bulb/probe socket of the heating supply
NOTICE: System damage due to incorrect sensor
position!
Safety cut-out and thermostat sensors of third party
control units must be fitted in the instrument bulb/probe
socket of the heating supply (Fig. 1[6], page 5) of the
boiler.
Do not change the length of the immersion sleeve.
Unit Value
Temperature control unit s 40
Monitor/limiter s 40
Minimum difference between burner on and
off temperatures
K 7
Table 14 Conditions of use
For an optimum energy yield, we recommend supplying
a flow rate of 10 of the total nominal flow rate via the
low temperature flange, with a return temperature below
the dew point.
If there are no varying return temperatures, only the low
temperature flange needs to be connected.
Restriction of the temperature difference is not
necessary if the system is equipped with a dirt trap
device.
High flow rates and oversized pumps can result in the
accumulation of sludge or deposits on the heat
exchanger surfaces.
1
6 720 805 218-61.1T
27

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Buderus SB625WS bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Buderus SB625WS in de taal/talen: Engels als bijlage per email.

De handleiding is 3,62 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

loading

Andere handleiding(en) van Buderus SB625WS

Buderus SB625WS Gebruiksaanwijzing - English - 12 pagina's

Buderus SB625WS Installatiehandleiding - Français - 56 pagina's


Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info