Rego 1000 – 6 721 831 662 (2021/03) en 17
Reset condition: The error in the electric heater has been overcome and
no alarm signal.
Category: F.
Alarm lamp/buzzer: Yes.
Restart: Acknowledgement is required.
Contact the dealer if the alarm remains after acknowledgement.
7.7.15 Failure on sensor E31.T32 anti-freeze cooling
Function: The mixing valve in the collector circuit is closed. Activated
when the sensor's value indicates a temperature lower than -10 °C. The
sensor is used in certain cooling applications and is placed in the
collector circuit for cooling to prevent the heat exchanger from freezing.
Reset requirement:The value of the sensor indicates >-10 °C.
Category: G.
Alarm lamp/buzzer: Yes.
Restart: Automatic once the alarm cause has disappeared.
Contact the dealer if the alarm remains active for more than three
hours or recurs often.
7.7.16 Short circuit on sensor E31.T32 anti-freeze cooling
Function: The mixing valve in the collector circuit is closed. Activated
when the sensor's value indicates a temperature higher than 30 °C. The
sensor is used in the collector circuit for cooling in order to prevent the
heat exchanger from freezing.
Reset requirement:The value of the sensor indicates >30 °C.
Category: G.
Alarm lamp/buzzer: Yes.
Restart: Automatic once the alarm cause has disappeared.
Contact the dealer if the alarm remains active for more than three
hours or recurs often.
7.7.17 Error dew point sensor E1x.TM
Function: Cooling on current mixing valve is aborted. Activated when
the signal from the sensor deviates from its normal operating range. The
alarm may appear after a power failure but the alarm cause normally
disappears automatically and the only thing that has to be done is to
acknowledge the alarm.
Reset condition: The sensor's signals return to the normal operating
range.
Category: G.
Alarm lamp/buzzer: Yes.
Restart: Automatic once the alarm cause has disappeared.
Contact the dealer if the alarm remains active for more than three
hours or recurs often.
7.7.18 Faulty protective anode E41.F31
Function: Does not affect the compressor or additional heat. The alarm
is activated when the anode in the hot water heater is broken or does not
work.
Reset condition: The anode should be taken care of so as to prevent
corrosion in the hot water heater.
Category: H.
Alarm lamp/buzzer: Yes.
Restart: Acknowledgement is required.
Contact the dealer.
7.7.19 Failure on sensor E11.T1 flow
Function: The system switches over to control based on sensor T8. The
alarm is activated when the sensor's value indicates a temperature lower
than 0 °C.
Reset condition: The value of the sensor indicates >0 °C.
Category: H.
Alarm lamp/buzzer: Yes.
Restart: Automatic once the alarm cause has disappeared.
Contact the dealer if the alarm remains active for more than three
hours or recurs often.
7.7.20 Short circuit on sensor E11.T1 flow
Function: The system switches over to control based on sensor T8. The
alarm is activated when the sensor's value indicates a temperature
higher than 110 °C.
Reset condition: The value of the sensor indicates
< 110 °C.
Category: H.
Alarm lamp/buzzer: Yes.
Restart: Automatic once the alarm cause has disappeared.
Contact the dealer if the alarm remains active for more than three
hours or recurs often.
7.7.21 Failure on sensor E12.T1, E13.T1... flow
Function: The mixing valve for the circuit is closed completely. The
alarm is activated when the sensor's value indicates a temperature lower
than 0 °C.
Reset condition: The value of the sensor indicates >0 °C.
Category: H.
Alarm lamp/buzzer: Yes.
Restart: Automatic once the alarm cause has disappeared.
Contact the dealer if the alarm remains active for more than three
hours or recurs often.
7.7.22 Short circuit on sensor E12.T1, E13.T1... flow
Function: The mixing valve for the circuit is closed completely. The
alarm is activated when the sensor's value indicates a temperature
higher than 110 °C.
Reset condition: The value of the sensor indicates
< 110 °C.
Category: H.
Alarm lamp/buzzer: Yes.
Restart: Automatic once the alarm cause has disappeared.
Contact the dealer if the alarm remains active for more than three
hours or recurs often.
7.7.23 Failure on sensor T2 outdoor
Function: In the event of a failure on T2, the outdoor temperature is set
to 0 °C so that the heat pump can continue to produce heat. The alarm is
activated when the sensor's value indicates a temperature lower than -
50 °C.
Reset condition: The value of the sensor indicates
> -50 °C.
Category: H.
Alarm lamp/buzzer: Yes.
Restart: Automatic once the alarm cause has disappeared.
Contact the dealer if the alarm remains active for more than three
hours or recurs often.
7.7.24 Short circuit on sensor T2 outdoor
Function: In the event of a short circuit on T2, the outdoor temperature
is set to 0 °C so that the heat pump can continue to produce heat. The
alarm is activated when the sensor's value indicates a temperature
higher than +70 °C.
17

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Bosch Rego 1000 bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Bosch Rego 1000 in de taal/talen: Engels als bijlage per email.

De handleiding is 4.13 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info