ERROR MANAGEMENT
6 720 806 630 (2013/02)14
There are two sensors, T8 and T71, in the Hydrolight/Hydrocomfort
unit, which for safety reasons stop the heat pump if the temperature of
the flow rises above the set value.
PROBABLE CAUSE 1; INSUFFICIENT FLOW OVER THE HEAT PUMP:
▶Select Acknowledge.
Check that all the valves are open. The thermostat valves in heating
systems should be fully open and in floor heating systems at least half
of the coils should be fully open.
Contact the installer in the event of repeated alarms.
POSSIBLE CAUSE 2; BLOCKED PARTICLE FILTER:
▶Select Acknowledge.
Contact the installer in the event of repeated alarms.
13.5.4 ERROR IN MAIN BOARD, HEATING SYSTEM
An error has occurred in the communication between the Hydrolight/
Hydrocomfort module and the heat pump.
Contact the installer in the event of repeated alarms.
13.5.5 ERROR IN ACCESSORY BOARD
Fault in the accessories board (IOB-B) in the Hydrolight/Hydrocomfort
module or corresponding communication.
▶Select Acknowledge.
Contact the installer in the event of repeated alarms.
13.5.6 ERROR IN ROOM SENSOR BOARD (ROOM CONTROLLER)
OR ERROR IN E12.T5 ROOM SENSOR BOARD
Fault in the CAN-BUS connected room controller or communication to it.
▶Select Acknowledge.
Contact the installer in the event of repeated alarms.
13.5.7 ERROR IN MULTI FUNCTION BOARD
Fault in the multifunction board or corresponding communication.
▶Select Acknowledge.
Contact the installer in the event of repeated alarms.
13.5.8 FAULT ON ADDITIONAL HEATER
Alarm from additional electric heater.
Check status in the booster heating.
▶Select Acknowledge.
Contact the installer in the event of repeated alarms.
13.5.9 FREEZE PROTECTION EXCHANGER T9 ACTIVATED
An error has occurred with the frost protection for the exchanger.
▶Select Acknowledge.
Contact the installer in the event of repeated alarms.
13.5.10 ALARM HEAT PUMP
The heat pump has developed a fault.
▶Select Acknowledge.
Contact the installer in the event of repeated alarms.
13.5.11 LOW MAINS VOLTAGE
If the mains voltage falls below 170 V, the information symbol in the
display lights up. If the voltage falls below 170 V for more than one hour,
the alarm is activated.
Contact the installer.
13.5.12 OR SAFETY THERMOSTAT VS2 TRIPPED
Acknowledge Thermostat with alarm
Contact the installer in the event of repeated alarms.
13.5.13 SCREED DRYING SET POINT VALUE FOR HEATING NOT
REACHED
The alarm is activated if the temperature at the current stage in the
drying program is not reached within the set time.
13.5.14 OVERLOADED TRANSFORMER
▶Select Acknowledge.
Contact the installer in the event of repeated alarms.
13.5.15 FAULT ON ELECTRIC ELEMENT
Fig. 32
Possible cause 1: overheating protection of the power supply has
tripped.
Check that the heat carrier pump has not stopped.
Reset overheating protection of power supply. A reset button is
located in the switch box of the Hydrolight/Hydrocomfort module.
▶Select Acknowledge.
Contact the installer in the event of repeated alarms.
13.5.16 NO PRESSURE IN SYSTEM
If the system pressure is less than 0.5 bar (Hydrocomfort only), this trips
the pressure switch which switches off the power supply and triggers
the alarm No pressure in system. To remedy the fault:
Check that the expansion tank and safety valve are suited for the
correct pressure in the system.
Slowly increase the pressure in the heat system by adding water via
the filling valve.
Acknowledge the alarm manually by pressing the rotary selector in the
user interface of the Hydrocomfort unit (, fig. 2).
13.6 WARNING MESSAGE
13.6.1 IS THE HEAT PUMP FUSED FOR THIS OUTPUT?
The warning is activated to ensure that the system is designed to handle
the load produced.
In the info log is stored Check fuse.
Check that the heat pump and the Hydrolight/Hydrocomfort unit is
connected to the correct fuse size.
13.6.2 MAXIMUM WORKING TEMPERATURE HEAT PUMP
In the info log is stored Maximum working temperature heat pump.
Fig. 33
The temperature sensor T9 located in the Hydrolight/Hydrocomfort unit
stops the heat pump for safety reasons as soon as the temperature of the
return water exceeds a certain limit (>56 °C).
Probable cause 1; The heat setting is set so high that the heating
system’s return temperature is too high:
Reduce the heat setting.
Possible cause 2: valves on the underfloor heating system or
radiators are closed.
6 720 648 148-56.1I
6 720 641 467-29.1I
14

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Bosch Greensource Hydrolight - Hydrocomfort bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Bosch Greensource Hydrolight - Hydrocomfort in de taal/talen: Engels als bijlage per email.

De handleiding is 1.66 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

loading

Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info