SDC12-31 ACD01 TUV
163
ATMOS ACD01 – SERVICE MANUAL EN
8.12.2 Example of parameter settings for hydraulic diagram no. 0033
HYDRAULIC Menu
Parameter
Description
Setting
1 Hydraulic diagram 0032
2 DHW pump output 1 (DHW charging pump)
3 Output of mixing circuit 1 3 (Mixing circuit)
4 Output of mixing circuit 2 3 (Mixing circuit)
5 Output of the heating circuit (HC) pump DKP (fixed)
6 Variable output 1 L2 Boiler burner (fixed)
7 Variable output 2 16 (PLP)
8 Variable input 1 16 (AGF) Flue gas
sensor
9 Variable input 2 PF (fixed)
10 Variable input 3 OFF
SOLID FUEL Menu
1 Boiler type 6
2 Minimum temperature (boiler type 2,3,4) 80°C
3 Maximum temperature (boiler type 2,3,4) 95°C
4 Switch-on of the boiler pump (DKP) 30°C
5 Boiler pump differential 5K
7 Switch-on differential of the fan 3K
16 Forced losses of heater 3 - buffer
17 Switch-over of the boiler pump to WF/AGF 2 (AGF)
18 Minimum flue gas temperature 60°C
20 Protection of the circulation pump of the boiler on switch-
on
OFF
BUFFER Menu
1 Minimum temperature - release of heating circuits 40°C
2 Maximum temperature 105°C
9 Charging protection ON
14 Min. required tank temperature (min. SET-POINT) 60°C
15 DKP switching differential (between the tank and boiler) -3 K
16 Differential of DKP restart 0 K
SOURCES Menu
1 Automatic switch over after burning out of SRC-1 1 (SRC-2)
12 Name of SRC-1 WOOD
13 Name of SRC-2 PELET