cated with the cylinder. The tundish must also be in a position visible to the occupants, and positioned away from
any electrical devices. The discharge pipe from the tundish should terminate in a safe place where there is no risk to
persons in the vicinity of the discharge and to be of metal.
2) Discharge pipes from the temperature & pressure relief and pressure relief valve may be joined together.
3) The pipe diameter must be at least one pipe size larger than the nominal outlet size of the safety device unless its
total equivalent hydraulic resistance exceeds that of a straight pipe 9 m long.
i.e. Discharge pipes between 9 m and 18 m equivalent resistance length should be at least 2 sizes larger than the
nominal outlet size of the safety device. Between 18 m and 27 m at least 3 times larger, and so on.
Bends must be taken into account in calculating the ow resistance. See g.1 and Table 2.
4) The discharge pipe must have a vertical section of pipe at least 300 mm in length, below the tundish before any
elbows or bends in the pipe work.
5) The discharge pipe must be installed with a continuous fall.
6) The discharge must be visible at both the tundish and the nal point of discharge, but where this is not possible or
practically dicult; there should be clear visibility at one or other of these locations. Examples of acceptance are:
i) Ideally below a xed grating and above the water seal in a trapped gully.
ii) Downward discharges at a low level; i.e. up to 100 mm above external surfaces such as car parks, hard standings,
grassed areas etc. These are acceptable providing that where children may play or otherwise come into contact with
discharges, a wire cage or similar guard is positioned to prevent contact, whilst maintaining visibility.
iii) Discharges at high level; i.e. into a metal hopper and metal down pipe with the end of the discharge pipe clearly vis
-
ible (tundish visible or not). Or onto a roof capable of withstanding high temperature discharges of water 3 m from
any plastic guttering systems that would collect such a discharge (tundish visible).
3) The pipe diameter must be at least one pipe size larger than the nominal outlet size
of the safety device unless it’s total equivalent hydraulic resistance exceeds that of a
straight pipe 9 m long.
i.e. Discharge pipes between 9 m and 18 m equivalent resistance length should be at
least 2 sizes larger than the nominal outlet size of the safety device. Between 18
m and 27 m at least 3 times larger, and so on.
Bends must be taken into account in calculating the flow resistance.
See fi
g..5 and Table 2.
4) The discharge pipe must have a vertical section of pipe at least 300 mm in length,
below the tundish before any elbows or bends in the pipe work.
5) The discharge pipe must be installed with a continuous fall.
6) The discharge must be visible at both the tundish and the final point of discharge,
but where this is not possible or practically difficult; there should be clear visibility at
one or other of these locations. Examples of acceptance are:
i) Ideally belo
w a fixed grating and above the water seal in a trapped gully.
ii) Downward discharges at a low level; i.e. up to 100 mm above external surfaces
such as car parks, hard standings, grassed areas etc. These are acceptable providing
that where children may play or otherwise come into contact with discharges, a wire
cage or similar guard is positioned to prevent contact, whilst maintaining visibility.
iii) Discharges at high level; i.e. into a metal hopper and metal down pipe with
the
end of the discharge pipe clearly visible (tundish visible or not). Or onto a roof capable
15
600 mm Max.
300 mm
Min.
Temperature & pressure
relief valve
Metal discharge pipe (D1) from
temperature & pressure relief valve.
to tundish.
Metal discharge pipe (D2) from tundish
with continuous fall. See Table 2 and worked
example.
Tundish
Fixed grating
Trapped gulley
Discharge below
fixed grating.
(see page 6 for
alternative points
of discharge).
Fig.. 4
Suggest ways of terminating discharge pipes safely
42.0.01.07204.03 pag. 9-20.qxd:42.0.01.07204.01 pag. 9-20 7-10-2016 11:28 Pagina 15
iv) Where a single pipe serves a number of discharges, such as in blocks of ats, the number served should be limited to
no more than 6 systems so that any installation can be traced reasonably easily. The single common discharge pipe
should be at least one pipe size large than the largest individual discharge pipe to be connected. If unvented hot
water storage systems are installed where discharges from safety devices may not be apparent i.e. in dwellings oc
-
cupied by the blind, inrm or disabled people, consideration should be given to the installation of an electronically
9

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Ariston Pro 1 Eco bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Ariston Pro 1 Eco in de taal/talen: Engels als bijlage per email.

De handleiding is 1,62 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

loading

Andere handleiding(en) van Ariston Pro 1 Eco

Ariston Pro 1 Eco Gebruiksaanwijzing - Nederlands - 16 pagina's

Ariston Pro 1 Eco Gebruiksaanwijzing - Français - 24 pagina's


Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info