Heat pump water heater – INSTALLATION
38
4.10 Hydraulic connections
Connect the water heater inlet and outlet to pipes or pipe fittings that can withstand the operating pressure and
temperature of the hot water, which may reach 75 °C. It is not advisable to use materials that cannot withstand such
temperatures. The dielectric union fitting (supplied with the product) must be applied to the hot water outlet
pipe, prior to performing the connection.
Screw a “T” fitting identified by a blue collar onto the appliance’s water inlet pipe.
It is mandatory to fit a safety valve onto the appliance’s water inlet pipe. The device
must comply with the EN 1487:2002 standard and must have a maximum pressure of
0.7 Mpa (7 bar). Moreover, it must at least include the following components: a cut-
off valve, a non-return valve, a control mechanism for the non-return valve, a safety
valve and a water pressure shut-off device.
The device’s relief outlet must be connected to a relief pipe with a diameter no less than that of the appliance’s
connection (3/4”), with the aid of a siphon creating an air gap of at least 20 mm to allow for visual inspection; this is to
prevent any harm to persons and animals or damage to objects should the device activate and for which the
manufacturer shall not be held liable. Use a flexible pipe to connect the pressure safety device inlet to the cold water
system pipe, using a cut-off valve if necessary. Additionally, a water discharge pipe must be fitted to the outlet in case
the drainage tap is opened.
Avoid overtightening the pressure safety device and do not tamper with it. It is normal for water to trickle from the
pressure safety device during the heating phase; for this reason, it is necessary to connect the outlet, which must
always be left exposed to the atmosphere, to a drainage pipe that slopes downwards and towards an area not subject
to frost. It is advisable to also connect the condensate outlet to the same pipe, through the connection located on the
lower side of the water heater.
The appliance must not operate with water hardness levels below 12 °F; on the other hand, it is advisable to use a
suitably calibrated and monitored water softener in the event of particularly hard water (>25 °F); in this event, the
residual hardness must not fall below 15 °F.
If the mains pressure is close to the calibrated valve values, a pressure reducer must be installed as far as possible
from the appliance.
FIG 12. Caption: A:hot water outlet pipe / B: cold water inlet pipe / C: safety assembly / D: interception tap / E:
dielectric connection.
WARNING! It is advisable to carefully wash the system’s pipes in order to remove any residues of screw
thread, welding or dirt which may hamper the correct operation of the appliance.
4.11 Electrical connections
Description
Availability
Cable
Type
Protection
Alimentation cable not supplied 3G 1.5 mm
2
H05VV-F
16°
HC-HP connection cable not supplied 2G 0.5 mm
2
H05VV-F
External unit connection cable cable not supplied 5G 0.75÷1.5 mm
2
H05RN-F
Shielded probe connection cable between units cable supplied 4G
shielded – UL2464
WARNING: BEFORE YOU GET ACCESS TO TERMINALS, ALL SUPPLY CIRCUITS MUST BE DISCONNECTED
The batteries ensure that the product is protected against corrosion, when the appliance is not powered.
It is advisable to carry out a check on the electrical system to verify conformity to the regulations in force. Verify that
the electrical system can suitably withstand the water heater’s maximum power consumption values (refer to the data
plate), in terms of the size of the cables and their conformity to the regulations in force. It is forbidden to use multiple
outlet sockets, extension cables or adaptors. The earth connection of the appliance is required. It is forbidden to
use piping from the water, heating and gas systems for earthing the appliance.
Prior to operating the machine, make sure that the electricity mains voltage conforms to the value indicated on the
appliance’s data plate. The manufacturer of the appliance shall not be held liable for any damage caused by failure to
earth the system or due to anomalies in the electric power supply. To disconnect the appliance from the mains, use a
bipolar switch complying with all applicable IEC-EN regulations in force (minimum distance between contacts 3 mm,
switch preferably equipped with fuses).
The appliance must comply with the European and national standards, and must be protected by a 30 mA RCD.
38

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Ariston NUOS 200 SPLIT bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Ariston NUOS 200 SPLIT in de taal/talen: Nederlands, Engels, Frans, Italiaans als bijlage per email.

De handleiding is 2,77 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

loading

Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info