Control panel for air to water Inverter heat pump
Pannello di controllo per pompa di calore Inverter aria / acqua
Panneau de contrôle pour pompe à chaleur Inverter air / eau
37.4254.086.03 05/2018
EN
IT
OPERATING
INSTRUCTIONS
ISTRUZIONI
D’USO
MODE
D’EMPLOI
FR
2
EN
2
CONTENTS
1 - Presentation of control elements ............................................................................................ 2
2 - Operation ................................................................................................................................. 3
3 - Settings ................................................................................................................................... 5
4 - Graphs ................................................................................................................................... 10
1 - PRESENTATION OF CONTROL ELEMENTS
CONTROL PANEL
BUTTONS
BUTTON ON/OFF - BACK TO THE PREVIOUS MENU
s BUTTON UP
t BUTTON DOWN
SET SETTINGS BUTTON
35 .0°C
[35.0°C]
ON: HEAT PUMP IN OPERATION
OFF: HEAT PUMP STOPPED
BLINKING: HEAT PUMP IS STARTING
ON: PUMP IN OPERATION
OFF: PUMP STOPPED
ON: BACKUP HEATING ACTIVE
OFF: BACKUP HEATING NOT ACTIVE
ON: “ECO” OPERATION ACTIVE
OFF: “ECO” OPERATION NOT ACTIVE
RETURN WATER
TEMPERATURE
RETURN WATER
SETPOINT
DISPLAY - MAIN SCREEN WITH UNIT SWITCHED ON
3
EN
3
2 - OPERATION
2.1 - SWITCHING THE UNIT ON/OFF
• Toturnontheunit,pressandholdthebutton for3seconds.Thefollowingtwoscreenswillappear
sequentially:
- - - -
- - - -
• Whentheunitispowered,thefollowingscreenappears:
• Thenthemainscreenwillappear:
35 .0°C
[35.C]
model r01
DISPLAYr01
UNIT MODEL
SOFTWARE VERSION
OF THE UNIT
SOFTWARE VERSION
OF THE DISPLAY
DISPLAY OR REMOTE
4
EN
• Toturnofftheunit,pressandholdthebutton for3seconds.Thefollowingtwoscreenswillappear
sequentially:
- - - -
- - - -
2.2 - SETPOINT MODIFICATION (RETURN WATER TO THE UNIT)
Ifthexedsetpointhasbeenselected(P05=1,seeparameterlist),youcansetthesetpointmanually.
Tochangethesetpoint,pressthebuttonss or tuntilthedesiredsetpointisdisplayedinthesecondline.
2.3 - KEYBOARD LOCKED / UNLOCKED
Tolockthekeyboardsothatitisnotpossibletoaccidentallypressthebuttons,pressthebuttonssandtsimul-
taneouslyfor3seconds.
Thefollowingscreenwillappear:
KEYBOARD
L OCKED
KEYBOARD
UNLOCKED
Repeatthesameoperationtounlockthekeyboard.Thefollowingscreenwillappear:
NOTE:Oncetheunithasbeenswitchedoff,thewaterpumpmaycontinuetooperateinordertopreventfrostin
the pipes.
2.4 - DEFROST
Duringthedefrostcyclesoftheunit,thefollowingscreenwillappear:
35 .0°C
DEFROST
Therstlinewilldisplaythereturnwatertemperature.
5
EN
5
3.2 - AUTHORIZED SERVICE CENTER PARAMETERS SETTING - LEVEL 2
• PressandholdSETbuttonfor3secondstoenterthemenulevel2(seetableonthenextpage).
• Theparameterforthesettingofthepumpmodewillbedisplayed.
• Press SETtomodifythepumpmode(seeP03)orpressbuttonss or t toentertheparameterlist(thelist
isaccessibleonlybypassword).
• EnterthepasswordandconfirmwiththeSET button.
• Pressbuttonss or t toscrollthroughtheparameters.
• Press SETtovisualisetheselectedparameter.
• PressandholdSETbuttonfor3secondstomodifytheparameter.Theparametervaluewillblinktoindicate
the change in progress.
• Pressbuttonss or t tochangetheparametervalue.
• Press SET to confirm or
to cancel.
• Pressthebutton
toreturntothepreviousmenu.
3.1 - USER PARAMETERS SETTING - LEVEL 1
• PresstheSETbuttononcetoenterthemenulevel1(seetable):
• Utilisebuttonss or t toselectthedesiredparameter.
• Press SETtovisualiseormodifytheselectedparameter.
• Press SETtoconfirmanychanges.
• Pressthebutton
toreturntothepreviousmenu.
Name Description Notes
H2Opressure Waterpressureinthewatercircuit
PumpSpeedselection Select the water pump speed and
readbackthe correspondingwater
ow
Once desired speed has been se-
lected,pressbutton
to conrm
the selection
Waterow Waterowlevelbar
Sensorsreading Listofmainsensorsreading RWT,SWT,OAT,WaterFlow,Pump
Speed
Workingmodeselection HEAT:heatingmodeselected
COOL:coolingmodeselected
SelectionavailableonlyifP14=1
See parameter P04
Error List List of last 10 errors Holdbuttonsfor5secondstode-
letethelist(possibleonlyifP07=1)
Languageselection 0=French
1=English
2=Italian
See parameter P08
LEGEND OF ACRONYMS (CONTAINED IN THE PARAMETER TABLES)
DHW: DOMESTIC HOT WATER
RWT: RETURN WATER TEMPERATURE
SWT: SUPPLY WATER TEMPERATURE
OAT: OUTDOOR AIR TEMPERATURE
ICT1:OUTLET(HEAT)/INLET(COOL)HEATEXCHANGER(PLATE-TYPE)
ICT2:INLET(HEAT)/OUTLET(COOL)HEATEXCHANGER(PLATE-TYPE)
OCT: OUTDOOR COIL TEMPERATURE
CDT: COMPRESSOR DISCHARGE TEMPERATURE
CTST: COMPRESSOR TOP SHELL TEMPERATURE
ICP:CONDENSATIONPRESSURE(HEAT)/EVAPORATIONPRESSURE(COOL)
3 - SETTINGS
6
EN
6
3.2.1 - SETTING OF GENERAL PARAMETERS
Num. Description Unit
Default value Range
Incre-
ment
Value description Notes
Floor Fan coils Radiators Min. Max.
- Sensorsreading Readonly RWT - SWT - OAT - ICT1 - ICT2 - OCT CDT -
CTST - ICP
WaterFlow
PumpSpeed
Listofallthesensorsvalue
P02 On-Offhysteresis °C 1.5 1.5 1.5 0.5 10 0.5 Hysteresisofheatpumprestartonthereturn
watertemperature
See graph “ON/OFF HYSTERESIS”
P03 Waterpump
mode
- Auto(0) Auto(0) Auto(0) Auto(0) ON(1) 1 AUTO=Automode
ON=WaterpumpalwaysON
P04 Workingmode - Heat(0) Heat(0) Heat(0) Heat(0) Cool(1) 1 HEAT=heatingmodeselected
COOL=coolingmodeselected
SelectionavailableonlyifP14=1
P05 Setpointmode - 0 0 0 0 1 1 0=Automaticsetpoint(climaticcurve)
1=Fixedsetpoint(userselection)
In2-zonesapplication,ifautomodeisselected
thewarmest(heatingmode)orthecoldest(cooling
mode)setpointisselected
P06 Secondarywater
pump
- 0 0 0 0 1 1 0=Unitpumponly
1=Secondarypumpinstalled(primary/second-
arycircuit)
P07 Error list reset
enable
- 0 0 0 0 1 1 0=Errorlistresetforbidden
1=Errorlistresetallowed
IfP07=1gototheerrorlistandholdthebutton
s
for5secondstoclearthelist
P08 Language - English(1) English(1) English(1) 0 2 1 0=French
1=English
2=Italian
P09 Backupheating
mode
- 0 0 0 0 3 1 0=Backupheatingdisabled
1/2/3=Externalbackupheatingenabled
P10 Backupheating
delay
Min. 20 20 20 5 120 1 Timeofheatpumpfunctioningbeforebackup
heatingactivation
ValidonlyifP40<OAT<P12
See graph “OPERATING RANGE OF HEAT PUMP/
BACKUP HEATING”
P11 Boostmode - 0 0 0 0 1 1 0=Boostmodedisabled
1=Boostmodeactivated
IfP11=1,backupheating(accordingtoP09)will
beimmediatelyactivateduptothesetpoint,then
P11isautomaticallyresetto0
P12 Backupheating
threshold
°C -10 -10 -10 P40 +35 1 Heatingmode:
OAT>P12:backupheatingdisabled
OAT<P12:backupheatingenabled
See graph “OPERATING RANGE OF HEAT PUMP/
BACKUP HEATING”
P13 DHWvalvedelay Sec. 15 15 15 15 300 5 TimetomovetheDHWvalvefromoneposi-
tion to the other
7
EN
7
Num. Description Unit
Default value Intervallo
Incre-
ment
Value description Notes
Floor Fan coils Radiators Min. Max.
P14 Workingmode
selection
- 0 0 0 0 1 1 0=Workingmodeselectedbythermostat
1=WorkingmodeselectedwithP04
P20 Alarm contact
function
- 0 0 0 0 2 1 0=Alarm
1=Defrost
2=Alarmordefrost
P21 DHW contact
function
- 0 0 0 0 1 1 0=DHW
1=Secondarysetpoint
IfP21=0,whenDHWcontactisclosedtheunitwillautomati-
callymanagetheDHWproduction.
IfP21=1,whenDHWcontactisclosedtheunitwillusethe
secondarysetpointP22(heatingonly).
P22 Secondary
setpoint
°C 50 50 50 20 55 0,5 SetpointusedifP21=1andDHWcontactis
closed
P23 MaximumDHW
productiontime
h 5 5 5 1 24 1
P31 Antifreezefunc-
tionthreshold
°C 1 1 1 -20 +35 1 IfOAT<P31,antifreezefunctionisactivatedin
ordertoavoidwaterfreezinginthepipings.
See graph “ANTIFREEZE FUNCTION”
P32 Antifreeze
threshold(P31)
hysteresis
°C 1 1 1 1 5 0,5 HysteresisonP31 See graph “ANTIFREEZE FUNCTION”
P33 Minimumwater
ow
m
3
/h 0,3 0,4 0,4 0,3 4,0 0,1 Minimumwaterowthreshold IfwaterowdropsbelowP33,waterowerrorwillappearand
theunitwillstop
P40 Heatpump
threshold
°C -20 -20 -20 -20 P12 1 Heatingmode:
OAT<P40:heatpumpdisabled
OAT>P40:heatpumpenabled
See graph “OPERATING RANGE OF HEAT PUMP/BACKUP
HEATING”
P41 Defrost - 0 0 0 0 1 1 IfP41issetto1andunitisrunninginheating
mode,adefrostwillstart.Attheendofdefrost
cycleP41isautomaticallyresetto0
P50 Factorydefault
reset
- 0 0 0 0 1 1 IfP50issetto1,allparameterswillberesetto
thedefaultvalue.Aftertheresethasbeendone,
P50isautomaticallyresetto0
P51 Maximumheat
pumpsetpoint
°C 58 58 58 20 55 0,5 Maximumsetpointfortheheatpump.
Ifcalculatedsetpointis>P51,heatpumpwill
stopwhenP51isreachedandsetpointcanonly
bereachedwithbackupheating(ifenabled).
P60 Ecomodepower
limit
% 75 75 75 30 100 1
P61 Ecomodeenable - 1 1 1 0 1 1 0=Ecomodecommanddisabled
1=Ecomodecommandenabled
8
EN
8
Num. Description Unit
Default value Range
Incre-
ment
Value description Notes
Floor Fan coils Radiators Min. Max.
P101 Planttype
(singlezoneorzone1)
- 0 1 2 0 2 1 0=Underoor
1=Fancoil
2=Lowtemperatureradiators
WhenP101ischanged,P105/P106/P120/P121
P123areresettothecorrespondingdefaultvalue.
P105 Maximumclimatic
curvesetpoint
(singlezoneorzone1)
°C 35 45 50 30 55 0,5 Onlyforheatingmode
See graph “CLIMATIC CURVE”
P106 Minimumclimatic
curvesetpoint
(singlezoneorzone1)
°C 20 35 40 20 40 0,5 See graph “CLIMATIC CURVE”
P120 Temperatureformaxi-
mumsetpoint
(singlezoneorzone1)
°C -7 -7 -7 -20 P121 0,5 Settotheminimumexpectedregionaltemperature
See graph “CLIMATIC CURVE”
P121 Temperatureformini-
mumsetpoint
(singlezoneorzone1)
°C 17 17 17 P120 +35 0,5 IfP121<P120,P120isautomaticallysettoP121
See graph “CLIMATIC CURVE”
P123 Cooling setpoint
(singlezoneorzone1)
°C 23 12 - 10 30 0,5 Incoolingmodethesetpointisxedanditcorresponds
to P123
P130 Calculatedsetpoint
(singlezoneorzone1)
°C Readonly
P131 Lowestcooling
setpointwith0-10V
control
(singlezoneorzone1)
°C 23 12 - 10 P132 0,5 ActiveonlyifP150=1,itcorrespondstoasignalof10V
See graph “0-10V CONTROL”
P132 Highest cooling
setpointwith0-10V
control
(singlezoneorzone1)
°C
30 30 - P131 30 0,5 ActiveonlyifP150=1,itcorrespondstoasignalof0V.
IfP132<P131,P132isautomaticallysettoP131
See graph “0-10V CONTROL”
P150 0-10Vsignalfunction
(singlezoneorzone1)
- 0 0 0 0 4 1 0=Disabled
1=Thermalload
2=Setpointcommand
3=Thermalloadonoutdoorunit
4=Setpointcommandonoutdoorunit
IfP150=3or4,0-10Vsignalisreadonoutdoorunit
onlyandsignalsonzone1and2willbeignored
See graph “0-10V CONTROL”
P151 Maximum0-10V
setpoint shift
°C 5 5 5 1 10 0,5 ActiveonlyinheatingmodeandifP150=1.
Itrepresentstheshiftonthesetpointwithasignalof
10V.(Seegraph“0-10VCONTROL”)
P152 Manualsetpointshift °C 0 0 0 0 10 0,5 Climaticcurvemanualsetpointshiftinheatingmode
P160 Mixingvalvedelay sec 60 60 60 30 300 5
P161 Mixingvalvecontrol
type
- 0 0 0 0 1 1 0=230Vaccontrol(2or3points)
1=0-10Vcontrol
• Tosetthesinglezoneorzone1useparametersfromP101toP161(seetable).
3.2.2 - SETTING OF SINGLE ZONE OR ZONE 1
9
EN
9
Num. Description Unit
Default value Range
Incre-
ment
Value description Notes
Floor Fan coils Radiators Min. Max.
P201 Planttype
(zone2)
- 0 1 2 0 2 1 0=Underoor
1=Fancoil
2=Lowtemperatureradiators
WhenP201ischanged,P205/P206/P220/P221
P223areresettothecorrespondingdefaultvalue.
P205 Maximumclimaticcurve
setpoint(zone2)
°C 35 45 50 30 55 0,5 Onlyforheatingmode
See graph “CLIMATIC CURVE”
P206 Minimumclimaticcurve
setpoint(zone2)
°C 20 35 40 20 40 0,5 See graph “CLIMATIC CURVE”
P220 Temperatureformaximum
setpoint(zone2)
°C -7 -7 -7 -20 P221 0,5 Settotheminimumexpectedregionaltemperature
See graph “CLIMATIC CURVE”
P221 Temperatureforminimum
setpoint(zone2)
°C 17 17 17 P220 +35 0,5 IfP221<P220,P220isautomaticallysettoP221
See graph “CLIMATIC CURVE”
P223 Cooling setpoint
(zone2)
°C 23 12 - 10 30 0,5 Incoolingmodethesetpointisxedanditcorresponds
to P223
P230 Calculatedsetpoint
(zone2)
°C
- - -
Readonly
P231 Lowestcoolingsetpoint
with0-10Vcontrol
(zone2)
°C 23 12 - 10 P232 0,5 ActiveonlyifP250=1,itcorrespondstoasignalof10V.
See graph “0-10V CONTROL”
P232 Highest cooling setpoint
with0-10Vcontrol
(zone2)
°C 30 30 - P231 30 0,5 ActiveonlyifP250=1,itcorrespondstoasignalof0V.
IfP232<P231,P232isautomaticallysettoP231
See graph “0-10V CONTROL”
P250 0-10Vsignalfunction
(zone2)
- 0 0 0 0 2 1 0=Disabled
1=Thermalload
2=Setpointcommand
IfP250=3or4,0-10Vsignalisreadonoutdoorunit
onlyandsignalsonzone1and2willbeignored.
See graph “0-10V CONTROL”
P251 Maximum0-10Vsetpoint
shift
°C 5 5 5 1 10 0,5 ActiveonlyinheatingmodeandifP250=1.
Itrepresentstheshiftonthesetpointwithasignalof
10V.(Seegraph“0-10VCONTROL”)
P252 Manualsetpointshift °C 0 0 0 0 10 0,5 Climaticcurvemanualsetpointshiftinheatingmode
P260 Mixingvalvedelay sec 60 60 60 30 300 5
P261 Mixingvalvecontroltype - 0 0 0 0 1 1 0=230Vaccontrol(2or3points)
1=0-10Vcontrol
• Tosetzone2useparametersfromP201toP261.
3.2.3 - SETTING OF ZONE 2
10
EN
4 - GRAPHS
4.1 - ON/OFF HYSTERESIS
Return water
temperature
P130
(setpoint)
Heat pump ON
Heat pump OFF
P02
4.2 - OPERATING RANGE OF HEAT PUMP/BACKUP HEATING
P40 P12
Outdoor air
temperature
Heat pump
+
backup heating
Heat pump
only
Backup heating
only
4.3 - CLIMATIC CURVE (HEATING MODE)
X
Y
P105
P106
P120 P121
P130 (setpoint)
Outdoor air
temperature
Return water
setpoint
4.4 - ANTIFREEZE FUNCTION
Outdoor air
temperature
P31
Atifreeze function
activated
Atifreeze function
not activated
P32
Iftheantifreezefunctionisactive:
Return water
temperature
(RWT)
5°C
Unit in forced
function for
water heating
Unit in normal
operation
15°C
11
EN
X
Y
P105
P106
P120 P121
P130 (setpoint)
Outdoor air
temperature
Return water
setpoint
Thermal load
(P150 = 1)
Y+Z
Z = P151 * (0-10V)%
Example:
P151 = 5°C
0-10V signal = 6V = 60%
Z = 5°C * 60% = 3°C
P105
P106
Return water
setpoint
Setpoint command
(P150 = 2)
0-10V
0V
10V
P130 (setpoint)
X
Y
HEATING
P132
P131
Return water
setpoint
0-10V
0V
10V
P130 (setpoint)
X
Y
COOLING
4.5 - 0-10V CONTROL
NOTE:
Thegraphsreferringtotheparametersofzone1arethesameforzone2withthecorrespondingparameters
.
ViaAlfenoVaro,35-25020Alfianello-BS-Italy
Tel.+390331755111-Fax+390331755501
www.argoclima.com
10

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Argo IM bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Argo IM in de taal/talen: Engels als bijlage per email.

De handleiding is 0,8 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

Andere handleiding(en) van Argo IM

Argo IM Gebruiksaanwijzing - Deutsch - 12 pagina's

Argo IM Gebruiksaanwijzing - Français - 12 pagina's

Argo IM Gebruiksaanwijzing - Italiano - 12 pagina's

Argo IM Gebruiksaanwijzing - Português - 12 pagina's

Argo IM Gebruiksaanwijzing - Espanõl - 12 pagina's


Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info