Suspend Charging mode
Installation guide
Addendum
Eve Single S-line
Eve Single Pro-line
Eve Double Pro-line
2
EVE SINGLE S-LINE
EVE SINGLE PRO-LINE
EVE DOUBLE PRO-LINE
with charging cable
with charging cable with socket
EVE SINGLE S-LINE
EVE SINGLE PRO-LINE
with socket
ENGLISH
3
Background information on
the Suspend Charging mode
Section 14a of the Energiewirtschaftsgesetz (German energy law) species the possibility
for consumers to use electricity at reduced standing charges if it complies with certain
conditions. The option only applies to customers who have a controllable device containing
an independent measuring module (for instance an EV charging station) connected to their
domestic energy connection.
The grid operator’s energy meter is equipped with a potential free contact. By connecting
the customer’s device to the grid operator’s energy meter via data cables, the grid operator
can send a signal to the charging station to temporarily abort the energy demand to
avoid an overload of the grid. During the shut-o time the customer will not be able to
charge, but will still be able to use other household equipment. Temporarily disabling the
possibility to charge is called the Suspend Charging mode.
This document describes the installation and conguration of the Suspend Charging mode
functionality.
4Suspend Charging mode installation guide | Version 1.0 | July 2019
ENGLISH
1 Safety and usage instructions 5
1.1 Purpose and intended audience 5
1.2 General safety 5
1.3 Copyright 5
1.4 Registered trademarks 5
1.5 Disclaimer of liability 5
1.6 Addendum to the manual and
installation guide 5
2 Functionality 6
2.1 Functionality 6
3 Assembly and connecting 7
3.1 Hardware setup 7
4 Installation 8
4.1 Requirements 8
4.2 Installationandcongurationprocedure 9
5 Conguration 10
5.1 Conguration 10
5.2 Enabling Suspend Charging mode using
a central management system 11
5.3 Enabling suspend Charging mode via
the Service installer 11
TABLE OF CONTENT
5
Suspend Charging mode installation guide | Version 1.0 | July 2019
ENGLISH
1. SAFETY AND USAGE INSTRUCTIONS
1.1 Purpose and intended audience
Make use of this addendum to the installation manual to
properly install and commission the charging station.
Installation, commissioning and maintenance of this
installationmayonlybeperformedbyaqualiedelectrician
(Alfen-ICUcertiedpartner).Itisessentialthatthe
qualiedtechnicianhas:
Expertiseonallrelevantgeneralandspecicrules
regarding safety and incident prevention
Comprehensive knowledge of applicable electrical
regulations.
The ability to identify risks and avoid potential hazards.
Received and read these installation and operation
instructions.
1.2 General safety
DANGER!
These safety instructions are important to ensure safe
operation. Failure to comply with them in accordance with
general electrical safety regulations could result in a risk of
electricalshock,reand/orlifethreateninginjury.
Using this product is expressly prohibited in the following
situations:
Inthevicinityofexplosiveorhighlyammable
substances.
If the product is located in or close to water.
If the product or its individual components are damaged.
Usage by children or individuals not able to properly
assess the risks associated with using this product.
Alfen ICU B.V. shall not be liable in any way, for any kind
of damage, and all warranties on both the product and
accessoriesshallbecomevoidwhere:
There has been a failure to comply with the instructions
in this manual.
Improper use.
Installation and commissioning has been undertaken
byunqualiedpersons.
The product or accessories have been expanded or
modiedwithoutourknowledge.
Replacement parts have been used that are not
approved or manufactured by Alfen.
The ambient temperature is below -25 °C or
above40°C.
Situations have occurred that are beyond our control.
More extensive safety information is available in the
relevant sections of this document.
1.3 Copyright
Copyright©AlfenN.V.2019.Allrightsreserved.The
disclosure, duplication, distribution and editing of this
document, or utilization and communication of the content
are not permitted, unless authorized in writing. All rights,
including rights created by patent grant or registration of a
utility model or a design, are reserved.
1.4 Registered Trademarks
Eve ® is a registered trademarks of Alfen B.V. Therefore
unauthorized use of the trademark Eve or Eve Double Pro
Line® or Eve Double P.G. Line is illegal.
All other designations in this document can be trademarks
whose use by third parties for their own purposes can
infringe the rights of the owner.
1.5 Disclaimer of Liability
Thisdocumenthasbeensubjectedtorigoroustechnical
review before being published. It is revised at regular
intervals,andanymodicationsandamendmentsare
included in the subsequent issues. The content of this
document has been compiled for information purposes only.
Although Alfen ICU B.V. and Alfen B.V. have made best
eortstokeepthedocumentaspreciseandup-to-dateas
possible, Alfen ICU B.V. and Alfen B.V. shall not assume any
liability for defects and damage which result through use of
the information contained herein.
All obligations of Alfen ICU B.V. and Alfen B.V. are stated
in the relevant contractual agreements. Alfen ICU B.V. and
Alfen B.V. reserve the right to revise this document from
time to time.
1.6 Addendum to the manual and installation
guide
This installation guide is an addendum to the Alfen Eve
single(S-line,Pro-line)andEvedoubleusermanualsand
installationguides.Refertothespecicsectionsinthe
User manuals for relevant safety information.
6Suspend Charging mode installation guide | Version 1.0 | July 2019
ENGLISH
2.1 Functionality
Alfen has developed a solution to suspend a running
charging session on request of the grid operator.
Suspending the charging session is done in a controlled
way, according to the Mode 3 protocol.
The grid operators energy meter is equipped with a
potential free contact. The grid operator controls the
energymeterandcaneitheropenorclosethecontact(S1).
When the contact is closed, the charging station can charge
at full power. When the contact is open, the charging power
isreducedto0W.
The charging station makes sure a running transaction is
suspended according to the Mode 3 protocol. The screen
onthechargingstationwillshowamessagefortheuser:
‘Charging session halted by energy supplier’. In case the
charging station is not equipped with a screen, the blue
led will blink to indicate the power supply is halted by the
energysupplier.Duringtheshut-otimeitispossibleto
start a new charging session; the session, however, will be
paused immediately. As soon as the potential free contact
(S1)closesagain,thechargingstationwillcontinuethe
suspended charging session.
Image 1: Overview of the energy meter and charging station
2. FUNCTIONALITY
DANGER!
In this document the contact is considered to be closed
when charging is allowed. In practice it is possible that the
contact is open when charging is allowed. The installer is
responsible to assess the situation and act accordingly.
NOTICE!
This functionality is developed for all Eve (Single and
Double)chargingstationsandavailablefromsoftware
version 3.4.2 and higher.
S1
7
Suspend Charging mode installation guide | Version 1.0 | July 2019
ENGLISH
3. ASSEMBLY AND CONNECTING
RJ11
RJ12
RJ11
RJ12
RJ11
RJ12
3.1 Hardware setup
AnRJ11(orRJ12)datacableisusedtosendtheS1contactsignalstothechargingstation.Thedatacablesofthepotential
freecontactshouldbeconnectedtotheRJ11/RJ12connectoronthecontrollerboardofthechargingstation.
Image 2: Location RJ11/RJ12 connector CTL910 controller board
Image 3: Location RJ11/RJ12 connector on CTL920 controller board
Image 4: Location RJ11/RJ12 connector CTL910 controller board
EVE SINGLE S-LINE EVE SINGLE PRO-LINE
EVE DOUBLE PRO-LINE NOTICE!
Refer to the user manual and quick installation guide on
how to remove and install the front cover of the charging
station.
DANGER!
Refertothespecicsectionsintheusermanualandquick
installation guide manuals for relevant safety information.
8Suspend Charging mode installation guide | Version 1.0 | July 2019
ENGLISH
4. INSTALLATION
4.1 Requirements
Connecting the potential free contact with the charging station controller board should be done under the following strict
conditions:
1. No other connection is allowed. The two signal cables can only be connected to a potential free contact.
Image 5: Overview of the energy meter and charging station
2. The charging station should be the only device connected to the potential free contact
Image 6: Overview of the energy meter and charging station
3. NeveroeranexternalvoltageonthecontactsoftheRJ11connector.
S1
S1
9
Suspend Charging mode installation guide | Version 1.0 | July 2019
ENGLISH
4.2 Installation and conguration procedure
1. Verifythetypeofcontactintheenergymeterofthegridoperator(NOorNCcontact).
2. AdjustthechargingstationcongurationtoSuspendChargingmodebeforecontinuingtheinstallation.
Checkthecongurationchapterhowtocongurethechargingstation.
3. Dependingonthechosencongurationsetting,followthetestprocedureasshownbelow:
4. When the test is done successfully, the data cables can be attached to the potential free contact of the energy meter.
RJ11connector:Usesignalcable2and4toconnectwiththeenergymeterofthegridoperator.
RJ12connector:Usesignalcable3and5toconnectwiththeenergymeterofthegridoperator.
Image 7: RJ11 and RJ 12 connector
5. Start a charging session and check whether the behaviour of the charging station is as expected.
4. INSTALLATION
Station response Normally Closed (NC) contact Normally Open (NO) contact
Allow charging Suspend when closed Suspend when opened
Suspend charging Suspend when closed Suspend when opened
NOTICE!
Before installing the system read the requirements as described in the paragraph 'Requirements'.
NOTICE!
Selectingtherightsettingshouldbedoneaccordingtothecongurationofthecontactintheenergymeterofthegrid
operator.
Station response Test procedure
Suspend when closed Test procedure A
Step1:Shortcircuitpin2and4(RJ11)orpin3and5(RJ12).
Startachargingsession.Whenthecongurationissetright,thechargingstationwill
respondby(dependingonthetypeofchargingstation):
Showing the message ‘Charging session halted by energy supplier’ on the screen
Blinking the blue led when starting the charging process
Step2:Undotheshortcircuitingandstartachargingsession.Chargingispossible.
Suspend when opened Test procedure B
Step1:Shortcircuitpin2and4(RJ11)orpin3and5(RJ12).Startachargingsession.
Charging is possible.
Step2:Undotheshortcircuitingandstartachargingsession.Whenthecongurationis
setright,thechargingstationwillrespondby(dependingonthetypeofchargingstation):
Showing the message ‘Charging session halted by energy supplier’ on the screen
Blinking the blue led when starting the charging process
10 Suspend Charging mode installation guide | Version 1.0 | July 2019
ENGLISH
5.1 Conguration
CongurationoftheSuspendChargingmodecanbedoneviathebackoce(e.g.ICUConnect)orviatheServiceInstaller
application.
TocongurethestationforSuspendChargingMode,thefollowingcongurationkeyisavailable:
ThenameofthecongurationkeytosettheSuspendChargingmodedierspersoftwareversion:
Image 8: ICU Connect Conguration tab
5. CONFIGURATION
Conguration key Meaning Values
Direct external suspend
signal
Congureforwhich
purposetheRJ11/RJ12
port is used.
DSMR P1
Suspend when closed
Suspend when open
Conguration key Firmware version
Direct external signal 4.2.0andhigher
RJ11- Mode 3.4.1-3.4.3
(Not available) 3.4.0andearlier
NOTICE!
The Suspend Charging mode cannot be activated in combination with the Active Load Balancing functionality via P1
(SmartMeter).WhentheActiveLoadBalancingfunctionalityviaP1isenabledandthesettingforSuspendCharging
mode is activated, then this will be reverted to ‘DSMR P1’ when the charging station reboots. Therefore make sure P1 load
balancing is disabled before enabling the Suspend Charging mode. This can be done by deactivating the Active
LoadBalancingfunctionalityintheServiceInstallerapp(notpossibleviathebackoce).
11
Suspend Charging mode installation guide | Version 1.0 | July 2019
ENGLISH
5. CONFIGURATION
5.2 Enabling Suspend Charging mode using
a central management system
InthisparagraphthestepstocongureSuspendCharging
Mode are described using Alfen ICU Connect as an example.
Thecongurationparametersarealsomadeavailablein
third party central management systems. In case a third
party central management system is used to connect to
the stations, please refer to the third party’s description
aboutchangingcongurations.
1. Open ICU Connect and navigate to the charging
stations of interest
2. Go to tab Conguration
3. Press on Get Conguration
4. Gotoitem‘Directexternalsuspendsignal/RJ11-Mode’
andpressonEdit;thefollowingscreenwillappear:
Image 9: Edit conguration item screen
5. Adjustthevaluetooneofthefollowing:
6. Press Save
7. Sendthechangedcongurationbyclickingonthe
button
Image 10: Edit conguration item menu bar
8. Resetchargingstationtoeectuatethechanged
conguration
.
5.3 Enabling Suspend Charging mode via the
Service installer
The Suspend Charging mode is available in version 3.4.1
(andhigher)oftheServiceInstallerapplication.Ifapplicable
disable the Active Load Balancing functionality, before
settingthecongurationtoenableSuspendCharging
mode.
Value Function
DSMR Ready for P1 load balancing
Suspend when closed Suspends charging when closed
Suspend when open Suspends charging when open
Thiscanbedoneasfollows:
1. Go to the Load balancing tab
2. Go to Active Load Balancing
3. Deactivate the box at Active Load Balancing.
The functionality is now disabled.
4. Click on Save
Image 11: Service installer load balancing tab
ToenableSuspendchargingmode:
1. Go to the Power tab
2. Go to Installation
3. Select Allowed, suspend when closed or Allowed,
suspend when open
4. Click on Save.
5. Reboot the charging station by clicking the button
Image 12: Service installer Power settings tab
NOTICE!
Refer to the user manual and quick installation guide on
how to remove and install the front cover of the charging
station.
DANGER!
Refertothespecicsectionsintheusermanualandquick
installation guide manuals for relevant safety information.
Contact
Alfen ICU B.V.
Hefbrugweg 28
1332 AP Almere
The Netherlands
P.O. Box 1042
1300 BA Almere
The Netherlands
Tel. Sales Support: +31 (0)36 54 93 402
Tel. Service: +31 (0)36 54 93 401
Website: www.alfen.com/nl/oplaadpunten-ev
www.alfen.com/en/ev-charge-points
Contact
Alfen ICU B.V.
Hefbrugweg 28
1332 AP Almere
The Netherlands
P.O. box 1042
1300 BA Almere
The Netherlands
Tel. Sales Support: +31 (0)36 54 93 402
Tel. Service: +31 (0)36 54 93 401
Website: www.alfen.com/en/ev-charge-points
10

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Alfen Suspend Charging mode - Addendum bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Alfen Suspend Charging mode - Addendum in de taal/talen: Engels als bijlage per email.

De handleiding is 5.99 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info