ATTACHED ACCESSORIES
INSTALLATION / SERVICE TOOLING FOR R410A Changes
Gauge manifold As the working pressure is high, it is impossible to measure the working pres-
sure using conventional gauges. In order to prevent any other refrigerant from
being charged, the port diameters have been changed.
Charge hose In order to increase pressure resisting strength, hose materials and port sizes
have been changed (to 1/2 UNF 20 threads per inch). When purchasing a
charge hose, be sure to confirm the port size.
Electronic scale for
refrigerant charging
As working pressure is high and gasification speed is fast, it is difficult to read
the indicated value by means of charging cylinder, as air bubbles occur.
Torque wrench
(nominal dia. 1/2, 5/8)
The size of opposing flare nuts have been increased. Incidentally, a common
wrench is used for nominal diameters 1/4 and 3/8.
Flare tool (clutch type) By increasing the clamp bar's receiving hole size, strength of spring in the tool
has been improved.
Gauge for projection adjustment Used when flare is made by conventional flare tool.
Vacuum pump adapter
& check valve
Connected to a conventional vacuum pump. It is necessary to use an adapter
to prevent vacuum pump oil from flowing back into the charge hose. The charge
hose connecting part has two ports -- one for conventional refrigerant (7/16
UNF 20 threads per inch) and one for R410A. If the vacuum pump oil (mineral)
mixes with R410A a sludge may occur and damage the equipment.
Gas leakage detector Exclusive for HFC refrigerant.
Incidentally, the “refrigerant cylinder” comes with the refrigerant designation (R410A) and protector coating in the U.S’s ARI specified rose colour
(ARI colour code: PMS 507). Also, the “charge port and packing for refrigerant cylinder” requires 1/2 UNF 20 threads per inch corresponding to
the charge hose’s port size.
CAUTION R410A Air Conditioner Installation ______________________________________________________
THIS AIR CONDITIONER ADOPTS THE NEW HFC REFRIGERANT
(R410A) WHICH DOES NOT DESTROY OZONE LAYER. R410A
refrigerant is apt to be affected by impurities such as water, oxidizing
membrane, and oils because the working pressure of R410A refrig erant
is approx. 1.6 times of refrigerant R22. Accompanied with the adoption
of the new refrigerant, the refrigeration machine oil has also been
changed. Therefore, during installation work, be sure that water, dust,
former refrigerant, or refrigeration machine oil does not enter into the
new type refrigerant R410A air conditioner circuit. To prevent mixing of
refrigerant or refrigerating machine oil, the sizes of connecting sections
of charging port on main unit and installation tools are different from
those used for the conventional refrigerant units. Accordingly, special
tools are required for the new refrigerant (R410A) units. For connecting
pipes, use new and clean piping materials with high pressure fittings
made for R410A only.
Moreover, do not use the existing piping because there are some
problems with pressure fittings and possible impurities in existing
piping.
Changes in the product and components
In air conditioners using R410A, in order to prevent any other refrigerant
from being accidentally charged, the service port diameter size of the
outdoor unit control valve (3 way valve) has been changed. (1/2 UNF
20 threads per inch).
In order to increase the pressure resisting strength of the refrigerant
piping, flare processing diameter and opposing flare nuts sizes have
been changed. (for copper pipes with nominal dimensions 1/2 and
5/8).
In case of pipes welding please make sure to use dry Nitrogen inside
the pipes.
Use copper tube of special thickness for R410A: 1/4”-1/2” 0.8 mm
5/8”-3/4” 1 mm
7/8” 1.1 mm
Description Amount
Name Use
1 Technician’s installation manual Installation instructions
4 Rubber mounting pads Padding of the outdoor unit
1 Drain elbow Connecting drain hose to outdoor
2
Transition unions 1/2” - 3/8” Flare connection transitions in outdoor unit
2 T Flare connection transitions in outdoor unit
2 Transition unions 3/8” - 1/4” Flare connection transitions in outdoor unit
4
ransition unions 1/2" - 5/8"
6

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Airwell Multisplit YAZE CINCO DCI bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Airwell Multisplit YAZE CINCO DCI in de taal/talen: Engels als bijlage per email.

De handleiding is 1,25 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

loading

Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info