19
Example 1: Setting “Public function” for Relay 2.
Note that “Public function” can be set for all GewaLink-channels or all coded 4096-channels.
Default setting is all GewaLink-channels. Selected type for “Public function” is set by
recording any GewaLink-channel or coded 4096-channel to the selected relay.
Note that “Public function” is deleted, for security reason, when an IR-channel is recorded for
a relay. The “Public function” must always be reselected after the IR-recording.
First, program Relay 2 for monostable function with all GewaLink-channels, follow the
instruction Program relay for IR and Monostable functioning on page 16.
Continue by programming the function of the relay (according to the table):
1. Press the programming button P.
2. Press Btn2 (Selects Relay 2)
3. Press Btn1 (Selects ../Public/..)
4. Press Btn3 (Selects Public function On)
5. Done! (Sucess: 3 flashes and simultaneously 3 draws by the relay.)
Example 2: Setting “Polycode” for Relay 3.
Polycode is a sequence of 4 GewaLink-channels, e.g. four-digit access code. The sequence
can consist of GewaLink-channels and/or coded 4096-channels.
Do as follows to program the function for the relay (according to the table):
1. Press the programming button P.
2. Press Btn3 (Selects Relay 3)
3. Press Btn1 (Selects ../Polycode/..)
4. Press Btn4 (Recording sequence starts)
5. The indicator lamp flashes 2 times, press the desired button on the IR-transmitter.
6. Release the button on the IR-transmitter when the indicator lamp flashes 1 time.
7. Repeat steps 5 and 6 for all four IR-codes of the Polycode.
8. Done! (Sucess: 3 flashes and simultaneously 3 draws by the relay.)
Typical Installation of Door Automatics
When installation is made for controlling door automatics with additional external detector
outdoors and control switch (e.g., elbow switch) indoors, it is important that the external
detector and the control switch are connected on separate terminals for external connections
(1-2/Brown-White and 3-4/Brown-White).
Warning!
If the external detector and the control switch is connected and programmed for the same
terminal, any short circuit of the detector/detector cable will be registered as a press on the
control switch, and the relay is activated (door opens!).