1. General
This manual is meant to provide the user with the
essential information required for installing, using and
servicing the pumps.
A fault-finding chart indicating possible cause and
remedy for every problem which might occur, is
included.
2. Technical characteristics and materials
The electric pumps are the centrifugal, radial, close-
coupled type, with single impeller.
Cast iron pump-body and support, stainless steel
threaded counter flanges.
Stainless steel motor shaft; bronze impeller for the
high head range; cast iron impeller for the low head
range.
Mechanical seal housing standardized to DIN 24960.
The mechanical seal is lubricated by the pumped
liquid.
All the electric pumps come fitted with threaded
counter-flanges.
Amply dimensioned ball-bearings pre-packed with
special grease for life.
2 pole electric motors of enclosed type, IP 55, with
external ventilation; insulated according to Class F.
Standard supply voltages:
50 Hz=230/400 V
up to 7,5 kW - 400/700 V
for higher power ratings.
60 Hz=230/400 V for all powers.
Standard voltage V 230 - 50 Hz.
On request, special voltages available.
In the standard versions the electric pumps are
suitable for fluid temperatures up to 90°C.
Maximum working pressure: 10 Bar.
3. Applications
The electric pumps are suitable for application in the
civil, agricultural and industrial fields, to pump chemi-
cally or mechanically non aggressive liquids. Any
suspended solid particles should not exceed 2% by
weight. The following are but a few typical applications:
water supply systems, irrigation schemes, pressure
tank feed, pressure boosting, air conditioning system,
heating systems.
4. Installation
The pumps may also be located outdoor, provided
they are suitable protected by a roofing; they can also
be installed inclined or vertically.
Warning:
For operation in hot damp environments, the pump
should not be installed orientated to different directions
than normal, to avoid condensation water building up
inside the motor.
Avoid vertical position with motor facing down ward
(see installation diagram - Fig. 5).
Being generously dimensioned, these pumps can be
supported by the pipework of the system to which
they are applied, even though it would be preferable
- where possible - to secure them firmly to a bedplated
by means of four holding-down bolts fitted through
the holes provided in the pump feet. Firm mounting
will aid to damp down vibrations, if any.
A satisfactory installation should conform to the
following indications:
The suction pipe, the inside diameter of which should
never be smaller than the pump inlet, should be
dimensioned consistently with the system and the
pumped liquid. Bear in mind that the maximum theo-
retical suction lift not only is reduced by the NPSHr
required by the pump, which is a peculier characteristic
of the pump itself, but is also reduced by the height
above sea level of the installation and the friction
losses occurring in the suction line.
Therefore, in order to avoid cavitation, which would
generate noise, performance drop and vibrations that
might exert undue mechanicals stress on the pump,
the following relation should always be observed:
hp + hz ≥ (NPSHr + 0.5) + hf + hpv
where:
hp
is the absolute pressure acting on the free surface of
the liquid in the suction reservoir, expressed in meters
of liquid. hp is the quotient between the barometric
pressure and the specific weight of the liquid.
hz
is the difference in level between the pump axis and
the free surface of the liquid in the suction reservoir
expressed in metres. hz is negative when the liquid
level is below the pump axis.
hf
is the head loss occurring within the suction line and
the fittings fitted to it, such as connectors, foot valve,
sluice valves, bens, etc.
2
INSTRUCTIONS FOR THE INSTALLATION AND USE OF ELECTROPUMPS
fig. 1 - Pump installation
The head losses can be read from the diagram shown
in our catalogue, and in order to reduce them to a
minimum - mainly where suction is remarkable (over
4-5 metres) or when operating at the highest flow
rates - it is advisable to use a section pipe larger than
the pump inlet. In all cases it is advisable that the
pump be installed as close as possible to the source
of the pumped liquid.
3
hpv
is the vapour pressure of the liquid at the operating
temperature, expressed in metres of liquid. hpv is
the quotient between the vapour pressure and the
specific weight of the liquid.
0.5
is a margin of safety.
From the above relation it can be gathered that the
maximum permissible suction lift in an installation
depends on the value of the atmospheric pressure
(i.e. the height above sea level of the installation) and
the liquid temperature. To facilitate the user’s task,
tables are provided which - the datum being water
at 4°C and at sea level - indicate the decrease in the
hydraulic pressure head as a function of the height
above sea level and the suction losses as a function
of the temperature.
Height above
sea level (m)
Suction losses
in m.
500 0,55
1000 1,1
1500 1,65
2000 2,2
2500
3000 3,3
2,75
21,5
Water
temperature (°C)
Suction
loss (m)
20 0,2
40 0,7
60 2,0
80 5,0
90 7,4
110 15,4
120
Wrong
Reducer and negative inclination
generate air locks
Scanty immersion=vortex
and whirlpools
• Sharp bends
• Narrow piping
Right
• Eccentric reducer
• Positive inclination
• Good immersion
• Ample bends
Suction pipe dia.≥ pump inlet
Check valve at the delivery
B
A
10

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Speroni CX bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Speroni CX in de taal/talen: Duits, Engels, Frans, Italiaans, Spaans als bijlage per email.

De handleiding is 13,65 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

loading

Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info