Configuration and function check REV24RF..
1 Configuration
1.1 DIP switches
ON / OFF 1 2 3 4 5 6 7 8 9 10
See
See 1.1.1
Sensor calibration on
Periodic pump run on
1.1.5
Sensor calibration off Periodic pump run off
1.1.2
Setpoint limitation 16…35 °C
Optimum start control:1 h/°C
1.1.6
Setpoint limitation 3…35 °C Optimum start control: ¼ h/°C
1.1.3
Temperature display °F
Optimum start control: ½ h/°C
Temperature display °C Optimum start control: Off
1.1.4
PID self-learning
(Cooling on)
1.1.7
PID 6
(Heating on)
PID12 Quartz
1.1.8
2-Point
Radio clock
1.1.9 DIP switch reset
ON
1 342
2211Z32
56 7 89
When changing one or several DIP switch positions, a DIP switch reset must be made by pressing the DIP switch reset button (also refer to Fig.
8). Otherwise, the previous settings will be maintained!
1.1.9
Note: The factory setting of all DIP switches is OFF
1.1.1 Sensor calibration: DIP switch 1
Set the DIP switch to ON and press the DIP switch reset button:
The display shows CAL. The room temperature currently acquired blinks.
Press
or to make a recalibration of max. ± 5 °C. To save the entry,
set the DIP switch to OFF and press the DIP switch reset button (also refer to
Fig. ).
1.1.2 Setpoint limitation: DIP switch 2
DIP switch ON: Setpoint limitation 16…35 °C
DIP switch OFF: Setpoint limitation 3…35 °C
(factory setting)
Save the entry by pressing the DIP switch reset button.
1.1.3 Temperature display in °C or °F:
DIP switch 3
DIP switch ON: Temperature display in °F
DIP switch OFF: Temperature display in °C
(factory setting)
Save the entry by pressing the DIP switch reset button (also refer to Fig.
).
1.1.4 Control action: DIP switches 4 and 5
DIP switch 4 ON and 5 ON: PID self-learning
Adaptive control for all types of application.
DIP switch 4 ON and 5 OFF: PID 6
For fast controlled systems, applications at locations with great
temperature variations.
DIP switch 4 OFF and 5 ON: PID 12
For normal controlled systems, applications at locations
with normal temperature variations.
DIP switch 4 OFF and 5 OFF: 2-Point
For difficult controlled systems, 2-position controller with
a switching differential of 0.5 °C (factory setting).
Save the entry by pressing the DIP switch reset button
(also refer to Fig.
).
1.1.5 Periodic pump run: DIP switch 6
Can only be used when circulating pump or valve is controlled!
This function protects the pump or valve against seizing during longer off
periods. Periodic pump run is activated for 3 minutes every 24 hours at 12:00
(display showing symbol ).
DIP switch ON: Periodic pump run on (also refer to Fig. )
DIP switch OFF: Periodic pump run off (factory setting)
Save the entry by pressing the DIP switch reset button.
1.1.6 Optimum start control: DIP switches 7 and 8
Optimum start control shifts switch on point P.1 such that the adjusted setpoint
will be reached at the required point in time. The setting depends on the type of
controlled system, that is, on heat transmission (piping network, radiators),
building dynamics (building mass, insulation) and heat output (boiler output,
flow temperature)
(also refer to graph in Fig.
/ 1.1.6).
DIP switch 7 ON and 8 ON: 1 h/°C For slow controlled systems
DIP switch 7 ON and 8 OFF: ¼ h/°C For fast controlled systems
DIP switch 7 OFF and 8 ON: ½ h/°C For medium controlled systems
DIP switch 7 OFF and 8 OFF: OFF Off, no impact (factory setting)
Save the entry by pressing the DIP switch reset button.
Legend to graph in Fig. .
.:
t Temperature (°C)
t Forward shift of switch on point (h)
TRx Actual value of room temperature
Pon Start point for optimum start control
1.1.7 Heating or cooling mode: DIP switch 9
DIP switch 9 ON:
Cooling
DIP switch 9 OFF:
Heating mode (factory setting)
Save the entry by pressing the DIP switch reset button
(also refer to Fig. ).
1.1.8 Radio clock: DIP switch 10
Can only be used if receiver DCF77 is integrated (time signal from Frankfurt)!
DIP switch ON: Clock runs on built-in quartz
DIP switch OFF: Time signal DCF77 from Frankfurt
Save the entry by pressing the DIP switch reset button
(also refer to Fig. ).
1.1.9 DIP switch reset (Fig. )
When changing one or several DIP switch positions, press the DIP switch reset
knob to make a DIP switch reset.
Otherwise, the previous settings will be maintained!
(Also refer to Fig. )
2 Accessing the expert level
Move the selector slider to the RUN position and press simultaneously
and for 3 seconds, then release the buttons and, within 3 seconds, press
simultaneously and for 3 seconds, release and keep depressed for another 3 seconds. This enables you to access the expert level for making the
settings on that level. on display (also refer to Fig. G).
Starting with code 00, the display shows the choice of languages. Navigation on the expert level is made possible with
and . Confirm the settings by
pressing .
DE
EN
FR
IT
NL
ES
PT
CS
HU
PL
SV
FI
DA
TR
EL
RO
9

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Siemens RCR10-868 bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Siemens RCR10-868 in de taal/talen: Alle talen als bijlage per email.

De handleiding is 1,5 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

loading

Andere handleiding(en) van Siemens RCR10-868

Siemens RCR10-868 Gebruiksaanwijzing - Deutsch - 2 pagina's

Siemens RCR10-868 Gebruiksaanwijzing - English - 2 pagina's

Siemens RCR10-868 Gebruiksaanwijzing - Français - 2 pagina's


Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info