93
installation guide
2 lives with 1 neutral connection (2 1N a.c. 400 V / 50 Hz):
The voltage between the phases and the neutral is 230 V a.c. Between the lives
there is a voltage of 400 V. If there is not a voltage of 400 V between the
lives, two wires have been taken from the same live in the meter cupboard
and the hob must be connected with two neutral wires, as indicated above
under 2 lives with 2 neutrals. Install a connecting bridge between the
connection points 4-5. Your groups must be fused with at least 16 A (2x). The
connecting power cable must have a minimum core cross section of 2,5 mm
2
.
3 lives with 1 neutral connection (3 1N a.c. 400 V / 50 Hz):
The voltage between the phases and the neutral is 230 V a.c. There is a voltage
of 400 V between the lives. Fit a connecting bridge between the connection
points 4-5. Phase 3 carries no load. Your groups must be fused with at least
16 A (3x). The connecting power cable must have a minimum core cross section
of 2,5 mm
2
.
92
installation guide
The appliance can be connected in the following ways:
1 phase connection (1 1N a.c. 230 V / 50 Hz):
The voltage between live and neutral is 230 V a.c.
Install connecting bridges between connection points 1-2 and 4-5.
Your group must be protected by a fuse of at least 32 A. The connecting power
cable must have a minimum core cross section of 6 mm
2
.
2 lives with 2 neutrals connection (2 2N a.c. 230 V / 50 Hz):
The voltage between live and neutral is 230 V a.c. There may be a voltage of
0 V between the phases if they are connected to the same phase in the meter
cupboard but also 400 V if they are connected to 2 different phases. Your
groups must be fused with at least 16 A (2x). The connecting power cable must
have a minimum core cross section of 2,5 mm
2
.