696298
25
Verklein
Vergroot
Pagina terug
1/104
Pagina verder
ENGLISH
7. CIRCULATION PUMP : . It would be better to install it on the return in order to avoid that it could disconnect itself at very high water
temperatures but checking that it does not drive water in the open expansion tank otherwise it should cause a continuous water
oxygenation with consequent, fast corrosion of boiler body. It must be not to avoid a forced circulation in the open expansion tank.
Furthermore it must be electrically connected to a thermostat or a electronic control unit that can be purchased with the thermo-
replace as OPTIONAL part.
8. ANTI-CONDENSATION MIXING VALVE – (see chapter)
ATTENTION: temperature safety sensors must be in place on the machine or at a distance no greater than 30 cm from the ow
connection of the thermo-product. Whenever the thermo products lack a device, those missing can be installed on the thermo
product ow pipe, within a distance no greater than 1m from the thermo product. All those parts must no have for any reason
meditate intercept bodies that could accidentally exclude them and must be placed in rooms which are protected from frost. On
the contrary, if they freeze, the boiler body could break or even explode.
ATTENTION: For no reason must the re be ignited before the system has been completely lled with water; doing this
would lead to serious damage of the entire structure. The system must be lled by means of the loading pipe directly from the
open tank in a way to prevent an excessive pressure of the water network deforming the body of the thermo heating stove.
The system must be kept constantly full of water even during the periods when the use of the thermo-heating stove is not requested.
During the winter, inactivity must be faced with the addition of antifreeze.
CLOSED EXPANSION TANK SYSTEM
It is COMPULSORY that the CLOSED expansion Tank system is provided with:
1. A SAFETY VALVE - maximum operation pressure allowed for the system is : see DECLARATION OF PERFORMANCE - CE MARKING
INFORMATION. Higher pressures can cause deformation and breakage of the boiler body. ATTENTION: The inside diameter of the
supply pipe which connects the thermoproduct with the security valve must be equal to the internal diameter of the supply junction
present in the thermoproduct. The above mentioned connection pipe must be without siphoning parts.
2. ANTI-CONDENSATION MIXING VALVE – (see chapter)
3. AUTOMATIC THERMAL DISCHARGE VALVE DSA or TEMPERATURE SAFETY RELIEF VALVE, with double safety sensor
4. CLOSED EXPANSION Tank can be installed on the thermo product return pipe. ATTENTION: The inside diameter of the return pipe
which connects the thermoproduct with the closed expansion vessel must be equal to the internal diameter of the return junction
present in the thermoproduct. The above mentioned connection pipe must be without siphoning parts.
5. PUMP CONTROL THERMOSTAT
6. NOISE ALARM ACTIVATION THERMOSTAT
7. NOISE ALARM
8. TEMPERATURE INDICATOR
9. PRESSURE INDICATOR
10. PUMP SYSTEM
ATTENTION: temperature safety sensors must be in place on the machine or at a distance no greater than 30 cm from the ow
connection of the thermo-product. Whenever the thermo products lack a device, those missing can be installed on the thermo
product ow pipe, within a distance no greater than 1m from the thermo product.. All those parts must no have for any reason
meditate intercept bodies that could accidentally exclude them and must be placed in rooms which are protected from frost. On
the contrary, if they freeze, the boiler body could break or even explode.
IT IS MANDATORY that the thermo products for domestic heating inserted in CLOSED Tank heating systems, must be internally equipped,
with a cooling circuit, prepared by the unit manufacturer, which is activated by a thermal safety valve (see chapter VAST) which does not
require auxiliary power and can guarantee that the standard set temperature limit is not exceeded. Connection between the power supply
unit and the valve must be free from interceptions. Cooling circuit upstream pressure must be at least 1,5 bar.
VMA ANTICONDENSATION MIXING VALVE IT IS MANDATORY PURCHASED AS OPTIONAL
The Anti-condensation mixing valve nds applications in solid fuel heat generators as it prevents cold water return in the exchanger. Routes
1 and 3 are always open and, along with the pump installed on the return (R), they guarantee water circulation inside the biomass boiler
exchanger (CB- chapter INSTALLATION LAY-OUT). An elevated return temperature, allows eciency improvement, reduces formation of
smoke condensation and prolongs the boiler life span.
Valves on the market have dierent calibrations. La NORDICA advises use of model 55°c with 1” hydraulic connections. Once the valve
calibration temperature is reached, route 2 opens and the boiler water goes to the system via the ow (M).

VAST  AUTOMATIC THERMAL DISCHARGE VALVE DSA PURCHASED AS OPTIONAL
Solid fuel thermo products must be installed with safety devices determined by laws in vigour.
For this reason the thermo products is equipped with a heat discharge coil.
The heat discharge coil must have one side connected to the water network (chapter INSTALLATION LAY-OUT - chap. DIMENSION SHEET- A
) and the other rot drainage network (C). When the safety temperature is reached, the automatic thermal discharge valve DSA, the bulb of
25
25

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw La Nordica Termocamino Base DSA bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van La Nordica Termocamino Base DSA in de taal/talen: Duits, Engels, Frans, Italiaans, Spaans als bijlage per email.

De handleiding is 9,15 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

loading

Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info