12.2 Protective Conductor Resistance Measurement with Ramp Curve
– Measurements on PRCDs with Current-monitored Protective Conductor Using PROFITEST PRCD Test Adapter as Accessory
Application
In certain PRCD types, the protective conductor current is moni-
tored. Direct application or disconnection of the test current of
200 mA, which is required for protective conductor resistance
measurements, results in tripping of the PRCD and, conse-
quently, a cut-off of the protective conductor connection. Protec-
tive conductor measurement is no longer possible in this case.
A special ramp curve for the application or disconnection of the
test current in combination with the PROFITEST PRCD test adapter
allows for performing protective conductor resistance measure-
ments without PRCDs being tripped.
Timed Sequence of the Ramp Function
Due to the physical properties of the PRCD, the measuring cycles
of this ramp function lie within the range of several seconds.
Moreover, while the polarity of the test current is being reversed,
an additional waiting period during polarity reversal becomes nec-
essary.
This waiting period has been included in the test sequence in
operating mode „automatic polarity reversal“ .
If you change the polarity direction manu-
ally, e.g. from „+pole with ramp“
to „–pole with ramp“
, the test instrument recog-
nizes the change in the current flow direc-
tion, disables measurements for the
required waiting period and simultane-
ously shows the respective symbol, see figure on the right.
Visualization of the measuring and waiting phases during protective con-
ductor resistance measurements on PRCDs with the PROFITEST MXTRA
Tripping of a PRCD due to faulty contact
During measurement, safe contact between the test probes of the
2-pole adapter and the DUT or the sockets of the PROFITEST PRCD
test adapter is to be ensured. Interruptions may lead to heavy
fluctuations in the test current which may cause the PRCD to trip
in the worst case.
In this event, the tripping of the PRCD is
automatically recognized by the test
instrument as well and an error message
is generated, see figure on the right. In
this case as well, the test instrument
automatically takes into account the
required waiting period before re-
enabling the PRCD and allowing any new measurements.
Connection
Please consult the operating instructions of the PROFITEST
PRCD adapter, particularly chapter 4.1. There you will also find
information on the connection terminals for offset measure-
ments and protective conductor resistance measurements.
Selecting Polarity Parameter
Select the requested polarity parameter with
ramp.
Measuring ROFFSET
Perform an offset measurement as described on page 47, to
assure that the test adapter‘s connector contacts are not in-
cluded in the measurement results.
Note
The offset only remains saved to memory until you
change the polarity parameter. If you perform the mea-
surement with manual polarity reversal (+pole or –pole),
you have to repeat the offset measurement before each
measurement with another polarity.
Measuring Protective Conductor Resistance
Check whether the PRCD is activated. If this is not the case,
activate it.
Perform the protective conductor measurement as described
above in section 12.1. Start the test sequence by briefly
pressing key ON/START. By pressing and holding key ON/START
you can extend the preset duration of the measuring phase.
Start measurement
During the magnetization phase (rising curve) and the
subsequent measuring phase (constant current) the
symbol on the right is shown.
If you abort the measurement during the rise phase, no measur-
ing result can be issued and displayed.
After the measurement, the demagnetization phase
(declining curve) and a subsequent waiting period is sig-
nalled with the inverse symbol shown on the right.
During this period, no new measurements are possible.
Only when the symbol on the right is shown, can the
measurement result be read and measurements started
with the same or another polarity.
Measuring phase Demagnetization
and waiting period
Result
Time [s]
Rise
phase
Test Current [ A]
01 3 6
0.25
prior to polarity reversal
or
restart
49

Hulp nodig? Stel uw vraag in het forum

Spelregels
1

Forum

Gossen-Metrawatt-PROFITEST--MXTRA

Zoeken resetten

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Gossen Metrawatt PROFITEST MXTRA bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Gossen Metrawatt PROFITEST MXTRA in de taal/talen: Engels als bijlage per email.

De handleiding is 2,28 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

loading

Andere handleiding(en) van Gossen Metrawatt PROFITEST MXTRA

Gossen Metrawatt PROFITEST MXTRA Gebruiksaanwijzing - Nederlands - 92 pagina's


Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info