TDMA CONTROL 601/701:
10
Published 07/2007
Hot Water Back up Heating Extra Com-
fort Temp 40...80°C
If the circulation and bath button is pressed three times
within 5 seconds the hot water back up heating target
temperature is raised to the set value for a time, thereby
acheiving a higher, comfortable, hot water temperature.
Using this function for providing hotter water only when
required allows significantly higher energy savings. This
function also operates during otherwise time switch con-
trolled back up heating shut down periods.
Hot Water Back up Heating:
Time Switch: On / Off
When the time switch is set to „On“, hot water back up
heating only occurs during the two selected time windows
/ operating periods.
Hot Water Back up Heating:
Each Day/Daily/Wkends-Wkdays
The time switch can be pre-set to accomodate individual
customer requirements. Two operating periods can be set.
Each Day: Different operating periods on different days.
The operating periods for each day are entered sepa-
rately.
Daily: The same operating periods are required each day.
The operating periods need only to be set once.
Weekends/Weekdays: The operating periods need only
be entered once for weekdays and once for weekend (Sat-
urday and Sunday) operating.
Example: Hot Water Back up Heating
Time Switch:
On
Time Switch Time:
Weekends/Weekdays
Weekday On:
08:00 (am)
Weekday Off:
16:00 (pm)
Weekend On:
09:00 (am)
Weekend Off:
17:00 (pm)
Back up heating for hot water will be activated as neces-
sary on weekdays between 08.00 and 16.00 and at
weekends between 09.00 and 17.00.
ADVICE:
In Variations 2 and 3 using CONTROL 601 and Varia-
tion 3 using CONTROL 701 hot water back up heating
can also be controlled via the boiler. The menu points
under „Water Input Data“ remain and the „Boiler
On/Off“ function is activated when hot water back up
heating is demanded.
Hot Water Back up Heating: Input - Function – Output
Input
Function
Upper thermal store sensor
(in delivery package)
Time controlled hot water
back up heating
Circulation – Bath button
One off raising of the tar-
get temperature for hot
water back up heating
Output: Hot water back up heating, Boiler On/Off
2.4.2 Time Controlled Hot Water Circulation
The time controlled hot water circulation enables large en-
ergy savings without any reduction in comfort. The circula-
tion pump can be activated via a button positioned in the
living space of the house and an integrated time switch. If
this button (circulation and bath button) is pressed once,
the circulation function is activated and the circulation
pump will run for the set time period.
See Advice on page 8.
Circulation running time: 1...20 M i n.
The running time of the circulation pump can be set here.
The running time should be such that the hot water tap
which is furthest from the thermal store will provide hot
water.
After the pump switches off there follows an interval of 15
minutes during which the pump will not operate, even if
the button is pressed again.
Circuulation Time Switch: On / Off
If the circulation time switch is set to „On“, the circulation
pump will be activated during the set operating time peri-
ods for the set running time (circulation running time / in-
terval). Three operating periods can be set.
Setting the time clock is carried out as described in para-
graph 2.4.1.
Example: Hot Water Circulation
Circulation running time:
2 minutes
Circulation Time Switch:
On
Time Switch Time:
Weekend/Weekday
Weekday On:
08:00
Weekday Off:
16:00
Weekend On:
09:00
Weekend Off:
17:00
The circulation pump can be activated on weekdays be-
tween 08.00 and 16.00 and at weekends between
09.00 and 17.00 with a pump operating period of 2
minutes and an interval between operation of 15 min-
utes. Outside these time periods the pump will only run
if activated by pressing the circulation – bath button.
2.5 Heating, Heating Circuit and Heating Support
Operating Functions (Heating Input Data)
2.5.1 Heating
Main Menu 12:34
Heating Input
The heating system settings are entered at the following
menu points.
Heat limit: Daytime external
temp: 0..40°C
10

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Consolar Control 601 bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Consolar Control 601 in de taal/talen: Engels als bijlage per email.

De handleiding is 5,12 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Stel vragen via chat aan uw handleiding

Stel uw vraag over deze PDF

loading

Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info